Combination Starter Components
UL 98 Manual Disconnect Switches
TeSys™ GS Disconnect Switches
TeSys™ GS Fusible Disconnect Switches
Catalog Number |
Rating (A) |
Poles |
Maximum Rating (HP) |
Short-Circuit Current Rating, 600 Vac Max. |
||||
---|---|---|---|---|---|---|---|---|
240 V |
480 V |
600 V |
250 Vdc |
Fuse Type |
SCCR (kA) |
|||
GS1DDU3 |
30 |
3 |
7.5 |
15 |
20 |
5 |
CC |
100 |
GS1DU3 |
30 |
3 |
7.5 |
15 |
20 |
5 |
J |
100 |
GS2EEU3 |
30 |
3 |
7.5 |
15 |
20 |
5 |
CC |
100 |
GS2EU3N |
30 |
3 |
7.5 |
15 |
20 |
5 |
J |
100 |
GS2GU3N |
60 |
3 |
15 |
30 |
50 |
10 |
J |
100 |
GS2JU3N |
100 |
3 |
30 |
60 |
75 |
20 |
J |
200 |
GS2MU3N |
200 |
3 |
60 |
125 |
150 |
40 |
J |
200 |
GS2QU3N |
400 |
3 |
125 |
250 |
350 |
50 |
J |
200 |
GS2SU3 |
600 |
3 |
200 |
400 |
500 |
— |
J |
200 |
GS2TU3 |
800 |
3 |
200 |
500 |
500 |
— |
L |
200 |
TeSys™ VLS Disconnect Switches
TeSys VLS Non-Fusible Disconnect Switches
Catalog Number | Mount Type | General Use @ 600 V (Amperes) | Max. Component SCCR (kA) | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Circuit Breaker @ 480 V | Fuses @ 480 V | Fuses @ 600 V | |||||||||
Type | Max. Size (A) | Max. SCCR (kA) | Type | Max. Size (A) | Max. SCCR (kA) | Type | Max. Size (A) | Max. SCCR (kA) | |||
VLS3P030R2 | Rear | 30 | H-Frame | 100 | 100 | CC, J, or T | 100 | 100 | CC, J, or T | 60 | 50 |
VLS3P063R2 | Rear | 60 | H- or J-Frame | 150 | 100 | CC, J, or T | 200 | 100 | CC, J, or T | 60 | 50 |
VLS3P080R2 | Rear | 100 | J-Frame* | 200 | 100 | CC, J, or T | 200 | 100 | CC, J, or T | 100 | 50 |
VLS3P100R2 | Rear | 100 | J-Frame* | 250 | 100 | CC, J, or T | 200 | 100 | CC, J, or T | 100 | 50 |
VLS3P125R2 | Rear | 100 | J-Frame* | 250 | 100 | CC, J, or T | 200 | 100 | CC, J, or T | 100 | 50 |
VLS3P030D2 | Door | 30 | H-Frame | 100 | 100 | CC, J, or T | 100 | 100 | CC, J, or T | 60 | 50 |
VLS3P063D2 | Door | 60 | H- or J-Frame | 150 | 100 | CC, J, or T | 200 | 100 | CC, J, or T | 60 | 50 |
VLS3P080D2 | Door | 100 | J-Frame* | 200 | 100 | CC, J, or T | 200 | 100 | CC, J, or T | 100 | 50 |
VLS3P100D2 | Door | 100 | J-Frame* | 250 | 100 | CC, J, or T | 200 | 100 | CC, J, or T | 100 | 50 |
VLS3P125D2 | Door | 100 | J-Frame* | 250 | 100 | CC, J, or T | 200 | 100 | CC, J, or T | 100 | 50 |
TeSys™ LK Disconnect Switches
TeSys LK Non-Fusible Disconnect Switches
Catalog Number |
Rating (A) |
Poles |
Maximum Rating (HP) |
Short-Circuit Current Rating, 600 Vac Max. |
||||
---|---|---|---|---|---|---|---|---|
240 V |
480 V |
600 V |
250 Vdc |
Fuse Type |
SCCR (kA) |
|||
LK4DU3CN |
30 |
3 |
10 |
20 |
30 |
— |
J |
100 |
LK4GU3CN |
60 |
3 |
20 |
40 |
50 |
— |
J |
100 |
LK4JU3CN |
100 |
3 |
20 |
50 |
50 |
— |
J |
100 |
LK4JU3N |
100 |
3 |
30 |
75 |
100 |
15 |
J |
200 |
LK4MU3N |
200 |
3 |
75 |
150 |
200 |
15 |
J |
200 |
LK4QU3N |
400 |
3 |
125 |
250 |
350 |
50 |
J |
200 |
LK4SU3N |
600 |
3 |
200 |
400 |
350 |
50 |
J |
200 |
LK4TU3N |
800 |
3 |
200 |
500 |
500 |
— |
L |
100 |
LK4UU3N |
1000 |
3 |
200 |
500 |
500 |
— |
L |
100 |
LK4WU3N |
1200 |
3 |
200 |
500 |
500 |
— |
L |
100 |
Class 9422 Disconnect Switches
Class 9422 Flange Mounted, Variable Depth Fusible and Non-Fusible Disconnect Switches
Disconnect Switch Size (A) |
Variable Depth Min.–Max. (in.) |
Max. Horsepower Ratings |
Fuse Type |
Fuse Clip Rating Non-Interchangeable Type for Class H, J, K or R Fuses (A) |
Catalog Number* |
||||||
---|---|---|---|---|---|---|---|---|---|---|---|
AC System Volts (Motor Volts) |
Vdc |
||||||||||
208 (200) |
240 (230) |
480 (460) |
600 (575) |
250 |
600 |
250 V |
600 V |
||||
30 |
6.625–18 |
7.5 |
7.5 |
15 |
20 |
5 |
15 |
None |
— |
— |
9422TCN30 |
H, J, K, R |
30 |
— |
9422TCF30 9422TCF33 |
||||||||
60 |
6.625–18 |
— |
15 |
30 |
50 |
10 |
30 |
None |
— |
— |
9422TDN60 |
H, J, K, R |
60 |
30 |
9422TDF60 9422TDF63 |
||||||||
100 |
6.625–18 |
25 |
30 |
60 |
75 |
20 |
50 |
None |
— |
— |
9422TEN10 |
H, J, K, R |
100 |
100 |
9422TEF10 |
||||||||
200 |
9.12–19.25* |
40 |
60 |
125 |
150 |
40 |
50 |
None |
— |
— |
9422TF1 |
H, J, K, R |
200 |
200 |
9422TF2 9422TF3* |
||||||||
400 Fixed Depth* |
11.38 (A5 or A6 Handle) |
75 |
125 |
250 |
350 |
50 |
50 |
None |
— |
— |
|
400 Variable Depth* |
15.87–19 (A7 or A8 Handle)* |
H, J, K, R |
400 |
400 |
UL 248 Switches
TeSys™ DF Fuse Holders
TeSys DF Fuse Holders
Fuse Holder |
Standards |
Maximum Voltage |
Current |
Short-Circuit Current Rating |
---|---|---|---|---|
DFCC |
IEC, UL (UL Listed) |
600 Vac |
30 A |
200 kA |
DF10 |
IEC, UL (UL Recognized) |
690 Vac |
33 A |
200 kA |
DF14 |
IEC, UL (UL Recognized) |
690 Vac |
50 A |
200 kA |
DF22 |
IEC, UL (UL Recognized) |
690 Vac |
125 A |
200 kA |
TeSys™ FB Fuse Holders
Type FB 600 V Fuse Holders
Rating (A) |
No. of Poles |
Catalog Number |
Short-Circuit Current Rating |
|
---|---|---|---|---|
Class J |
Class R* | |||
30 |
2 |
9080FB2611J |
9080FB2611R |
200 kA |
3 |
9080FB3611J |
9080FB3611R |
||
60 |
1 |
— |
9080FB1621R |
|
2 |
9080FB2621J |
— |
||
3 |
9080FB3621J |
9080FB3621R |
||
100 |
3 |
— |
9080FB3631R |
UL 489 Molded-Case Circuit Breakers
PowerPact™ Circuit Breakers and Motor Circuit Protectors
PowerPact™ Catalog Numbering System
Frame |
Rating |
Termination |
Poles |
Voltage |
Amperage |
Suffix Code |
Suffix Code |
|||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
B |
J |
L |
3 |
6 |
125 |
AB |
SA |
|||||||||
Frame Designation |
Interrupting Rating |
Termination |
Poles |
Voltage |
||||||||||||
B 125 A Frame |
See Table 11 |
A I-Line |
1 1-Pole |
4 480 V |
||||||||||||
H 150 A Frame |
D Drawout |
2 2-Pole |
6 600 V |
|||||||||||||
J 250 A Frame |
F Bus Bar (No Lugs) |
3 3-Pole |
||||||||||||||
Q 250 A Frame |
L Lugs on Both Ends |
4 4-Pole |
||||||||||||||
L 600 A Frame |
M Lugs Line Side Only |
|||||||||||||||
M 800 A Frame |
N Plug-in |
|||||||||||||||
P 1200 A Frame |
P Lugs Load Side Only |
|||||||||||||||
R 3000 A Frame |
S Rear Connected Studs |
PowerPact Interrupting Ratings System
Voltage |
Interrupting Rating |
||||||
---|---|---|---|---|---|---|---|
B |
D |
G |
J |
K |
L |
R |
|
240 Vac |
10 kA |
25 kA |
65 kA |
100 kA |
65 kA |
125 kA |
200 kA |
480 Vac |
18 kA |
35 kA |
65 kA |
65 kA |
100 kA |
200 kA |
|
600 Vac |
14 kA |
18 kA |
25 kA |
65 kA |
50 kA |
100 kA |
|
Frame (X = available) |
|||||||
B-Frame (15–125 A)* |
X |
X |
X |
X* |
|||
H-Frame (15–150 A) |
X |
X |
X |
X |
X |
||
J-Frame (150–250 A) |
X |
X |
X |
X |
X |
||
Q-Frame (70–250 A) |
X |
X |
X |
X |
|||
L-Frame (200–600 A) |
X |
X |
X |
X |
X |
||
M-Frame (300–800 A) |
X |
X |
|||||
P-Frame (250–1200 A) |
X |
X |
X* |
X* |
|||
R-Frame (600–3000 A) |
X |
X |
X |
X |
BV4 Motor Circuit Protector (MCP) Selection*
Frame |
Motor Circuit Protector Ampacity (In) |
Adjustable Instantaneous Trip (li) |
Catalog Numbers |
|
---|---|---|---|---|
Standard Protection |
High Protection |
|||
TeSys BV4 |
2 |
12–28 |
BV4T002D |
BV4T002J |
3.5 |
21–49 |
BV4T003D |
BV4T003J |
|
7 |
42–98 |
BV4T007D |
BV4T007J |
|
13 |
53–195 |
BV4T013D |
BV4T013J |
|
25 |
110–360 |
BV4T025D |
BV4T025J |
|
50 |
176–650 |
BV4T050D |
BV4T050J |
|
80 |
320–1150 |
BV4T080D |
BV4T080J |
|
115 |
600–1150 |
BV4T115D |
BV4T115J |
PowerPact H- and J-Frame Electronic Motor Circuit Protectors
Frame |
Sensor Rating |
Full Load Ampere Range |
Adjustable Instantaneous Trip Range |
Suffix |
Catalog Numbers |
||
---|---|---|---|---|---|---|---|
J-Interrupting Cat. No. |
L-Interrupting Cat. No. |
R-Interrupting Cat. No. |
|||||
H-Frame |
30 A |
1.5–25 A |
9–325 A |
M71 |
HJL36030M71 |
HLL36030M71 |
HRL36030M71 |
50 A |
14–42 A |
84–546 A |
M72 |
HJL36050M72 |
HLL36050M72 |
HRL36050M72 |
|
100 A |
30–80 A |
180–1040 A |
M73 |
HJL36100M73 |
HLL36100M73 |
HRL36100M73 |
|
150 A |
58–130 A |
348–1690 A |
M74 |
HJL36150M74 |
HLL36150M74 |
HRL36150M74 |
|
J-Frame |
250 A |
114–217 A |
684–2500 A |
M75 |
JJL36250M75 |
JLL36250M75 |
JRL36250M75 |
UL 489 Miniature Circuit Breakers and UL 1077 Supplementary Protectors
Multi 9™ Circuit Breakers and Supplementary Protectors
Multi 9 Catalog Numbering System
Range |
Function |
Number |
Poles |
Amperage |
||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
M9 |
F |
42 |
1 |
10 |
||||||||||||||||
Range |
Function |
Number |
Poles |
Amperage |
||||||||||||||||
M9 Multi 9 |
F MCB |
Internal code number depending on the standard and electrical characteristics. |
1 1-Pole |
From 0.5– 63 A |
||||||||||||||||
P DPN |
2 2-Pole |
|||||||||||||||||||
R RCCB |
3 3-Pole |
|||||||||||||||||||
D RCBO |
4 4-Pole |
|||||||||||||||||||
V Vigi C60 Add-on |
||||||||||||||||||||
Y Vigi N40 Add-on |
||||||||||||||||||||
C CTRL |
Multi 9 UL 489 Breaking Capacity
Number of Poles |
Current Rating (A) |
Voltage, AC |
|||
---|---|---|---|---|---|
120 V |
240 V |
277 V |
480/277 V |
||
1 Pole |
1–35 |
14 |
14 |
10 |
— |
40–63 |
10 |
10 |
— |
— |
|
2 Pole |
1–35 |
14 |
14 |
10 |
10 |
40–63 |
10 |
10 |
— |
— |
|
3 Pole |
1–35 |
14 |
14 |
10 |
10 |
40–63 |
10 |
10 |
— |
— |
Multi 9 UL 1077 Breaking Capacity
Number of Poles |
Current Rating (A) |
Voltage, AC |
|||
---|---|---|---|---|---|
120 V |
240 V |
277 V |
480/277 V |
||
1 Pole |
0.5–35 |
14 |
14 |
10 |
— |
40–63 |
10 |
10 |
5 |
— |
|
2 Pole |
1–35 |
14 |
14 |
10 |
10 |
40–63 |
10 |
10 |
5 |
5 |
|
3 and 4 Pole |
1–35 |
14 |
14 |
10 |
10 |
40–63 |
10 |
10 |
5 |
5 |
UL 60947 Contactors
TeSys™ K Contactors
TeSys K Contactors (Except for Spring Terminal Clamps)
Catalog Number |
Standard Motor Ratings @ 50/60 Hz (HP) |
Cont. Current Ratings |
Max. Component SCCR (kA)* |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Single-Phase |
Three-Phase |
Circuit Breakers @ |
Circuit Breakers @ 600 V |
Fuses @ 600 V |
|||||||||
120 V |
240 V |
208 V |
240 V |
480 V |
600 V |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
||
LC1K06 |
1/2 |
1 |
1.5 |
1.5 |
3 |
3 |
10 |
20 |
65 |
20 |
25 |
25 |
100 |
LC1K09 |
1/2 |
1.5 |
2 |
3 |
5 |
5 |
20 |
20 |
65 |
20 |
25 |
30 |
100 |
LC1K12 |
1 |
2 |
3 |
3 |
7.5 |
10 |
20 |
20 |
65 |
20 |
25 |
30 |
100 |
NOTE: This table lists the maximum SCCR of the component when protected
by any circuit breaker or fuse. If the maximum component SCCR is 65
kA and a 25 kA rated circuit breaker is used, then the system will
be 25 kA, the SCCR rating of the circuit breaker.
|
TeSys™ D Contactors
TeSys D 3-Pole Contactors
Catalog Number |
Standard Motor Ratings @ 50/60 Hz (HP) |
Cont. Current Rating (A) |
Max. Component SCCR (kA)* |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Single-Phase |
Three-Phase |
Circuit Breakers @ 480 V |
Circuit Breakers @ 600 V |
Fuses @ |
|||||||||
120 V |
240 V |
208 V |
240 V |
480 V |
600 V |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
||
LC1D09 |
1/3 |
1 |
2 |
2 |
5 |
7.5 |
25 |
35 |
85 |
35 |
50 |
25 |
100 |
LC1D12 |
1/2 |
2 |
3 |
3 |
7.5 |
10 |
25 |
35 |
85 |
35 |
50 |
30 |
100 |
LC1D18 |
1 |
3 |
5 |
5 |
10 |
15 |
32 |
60 |
85 |
35 |
50 |
40 |
100 |
LC1D25 |
2 |
3 |
7.5 |
7.5 |
15 |
20 |
40 |
60 |
85 |
60 |
50 |
60 |
100 |
LC1D32 |
2 |
5 |
10 |
10 |
20 |
25 |
50 |
60 |
85 |
60 |
50 |
80 |
100 |
LC1D38 |
2 |
5 |
10 |
10 |
20 |
25 |
50 |
60 |
85 |
60 |
50 |
80 |
100 |
LC1D40A |
3 |
5 |
10 |
10 |
30 |
30 |
60 |
110 |
100 |
110 |
50 |
90 |
100 |
LC1D50A |
3 |
7.5 |
15 |
15 |
40 |
40 |
70 |
110 |
100 |
110 |
50 |
110 |
100 |
LC1D65A |
5 |
10 |
20 |
20 |
40 |
50 |
80 |
110 |
100 |
110 |
50 |
125 |
100 |
LC1D80 |
7.5 |
15 |
25 |
30 |
60 |
60 |
110 |
150 |
100 |
150 |
50 |
175 |
100 |
LC1D95 |
7.5 |
15 |
25 |
30 |
60 |
60 |
110 |
— |
— |
— |
— |
— |
— |
LC1D115 |
— |
— |
30 |
40 |
75 |
100 |
160 |
250 |
100 |
250 |
50 |
250 |
100 |
LC1D150 |
— |
— |
40 |
50 |
100 |
125 |
160 |
250 |
100 |
250 |
50 |
300 |
100 |
NOTE: This
table lists the maximum SCCR of the component when protected by any
circuit breaker or fuse. If the maximum component SCCR is 100 kA and
a 25 kA rated circuit breaker is used, then the system will be 25
kA, the SCCR rating of the circuit breaker.
|
TeSys D 4-Pole Contactors
Catalog Number |
Continuous Current Rating (A) |
No. of Poles |
Max. Component SCCR (kA)* |
||||||
---|---|---|---|---|---|---|---|---|---|
Circuit
Breakers @ |
Circuit Breakers @ 600 V |
Fuses @ 600 V |
|||||||
N.O. |
N.C. |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
||
LC1DT20 |
25 |
4 |
0 |
35 |
85 |
35 |
50 |
25 |
100 |
LC1D098 |
25 |
2 |
2 |
35 |
85 |
35 |
50 |
25 |
100 |
LC1DT25 |
25 |
4 |
0 |
35 |
85 |
35 |
50 |
30 |
100 |
LC1D128 |
25 |
2 |
2 |
35 |
85 |
35 |
50 |
30 |
100 |
LC1DT32 |
32 |
4 |
0 |
60 |
85 |
35 |
50 |
40 |
100 |
LC1D188 |
32 |
2 |
2 |
60 |
85 |
35 |
50 |
40 |
100 |
LC1DT40 |
40 |
4 |
0 |
60 |
85 |
60 |
50 |
60 |
100 |
LC1D258 |
40 |
2 |
2 |
60 |
85 |
60 |
50 |
60 |
100 |
LC1DT60A |
60 |
4 |
0 |
110 |
100 |
110 |
50 |
TBD |
100 |
LC1DT80A |
80 |
4 |
0 |
110 |
100 |
110 |
50 |
TBD |
100 |
LC1D80004 |
110 |
4 |
0 |
150 |
100 |
175 |
50 |
175 |
100 |
LC1D80008 |
110 |
2 |
2 |
150 |
100 |
175 |
50 |
175 |
100 |
LC1D115004 |
160 |
4 |
0 |
250 |
100 |
250 |
50 |
250 |
100 |
NOTE: This
table lists the maximum SCCR of the component when protected by any
circuit breaker or fuse. If the maximum component SCCR is 100 kA and
a 25 kA rated circuit breaker is used, then the system will be 25
kA, the SCCR rating of the circuit breaker.
|
TeSys D LC2D Contactors
Catalog Number |
Max. Component SCCR (kA) |
|||||
---|---|---|---|---|---|---|
Circuit Breaker @ 480 V |
Circuit Breaker @ 600 V |
Fuses @ 600 V |
||||
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
|
LC2D40A |
110 |
100 |
110 |
50 |
90 |
100 |
LC2D50A |
110 |
100 |
110 |
50 |
110 |
100 |
LC2D65A |
110 |
100 |
110 |
50 |
125 |
100 |
LC2D115 |
250 |
100 |
250 |
50 |
250 |
100 |
LC2D150 |
250 |
100 |
250 |
50 |
300 |
100 |
LC2D115004 |
250 |
100 |
250 |
50 |
250 |
100 |
Additional TeSys™ D Contactor Ratings
UL/CSA Lighting Ratings (HP)
Catalog Number |
Ballast |
Tungsten |
||
---|---|---|---|---|
600 V |
480 Y / 277 V |
480 V |
600 V |
|
20 |
20 |
— |
— |
|
25 |
— |
— |
— |
|
32 |
25 |
— |
— |
|
40 |
40 |
— |
— |
|
LC1D32* |
50 |
50 |
— |
— |
LC1D40A |
60 |
— |
— |
60 |
LC1D50A |
70 |
— |
— |
70 |
LC1D65A |
80 |
— |
— |
70 |
LC1D80, LC1D80004 |
100 |
— |
100 |
— |
LC1D115, LC1D1150004 |
115 |
— |
115 |
— |
LC1D150, LC1D1500004 |
150 |
— |
150 |
— |
Elevator Duty Ratings (HP)
Catalog Number |
Single-Phase |
Three-Phase |
|||
---|---|---|---|---|---|
240 V |
208 V |
240 V |
480 V |
600 V |
|
LC1D12 |
1.5 |
2 |
3 |
7.5 |
7.5 |
LC1D18* |
3 |
5 |
5 |
— |
— |
LC1D25 |
3 |
5 |
7.5 |
15 |
20 |
LC1D32 |
5 |
10 |
7.5 |
— |
— |
LC1D40A* |
5 |
10 |
10 |
— |
— |
LC1D50A* |
7.5 |
15 |
15 |
— |
— |
LC1D50* |
7.5 |
10 |
15 |
25 |
30 |
LC1D65* |
10 |
15 |
20 |
40 |
50 |
LC1D80 |
15 |
20 |
25 |
50 |
50 |
LC1D150 |
15 |
25 |
30 |
60 |
75 |
Definite Purpose Ratings, 3-Phase, Breaking All Lines (Hermetic Refrigeration Compressor)
Catalog Number |
FLA |
Locked Rotor Amperes (LRA) |
FLA Cycles |
||
---|---|---|---|---|---|
240 V |
480 V |
600 V |
|||
LC1D09 |
9 |
54 |
45 |
36 |
100,000 |
LC1D12 |
12 |
72 |
60 |
48 |
100,000 |
LC1D18 |
18 |
108 |
90 |
72 |
100,000 |
LC1D25 |
25 |
150 |
125 |
100 |
100,000 |
LC1D32 |
32 |
192 |
160 |
128 |
100,000 |
LC1D40A |
40 |
240 |
200 |
160 |
100,000 |
LC1D50A |
50 |
300 |
250 |
200 |
100,000 |
LC1D65A |
65 |
390 |
325 |
260 |
100,000 |
LC1D80 (AC) |
80 |
480 |
400 |
320 |
100,000 |
LC1D80 (DC) |
75 |
450 |
375 |
300 |
100,000 |
LC1D115 |
115 |
690 |
575 |
460 |
100,000 |
LC1D150 |
150 |
900 |
750 |
600 |
100,000 |
TeSys™ F Contactors
TeSys F Contactors
Catalog Number |
Standard Motor Ratings @ |
Continuous Current Rating (A) |
Max. Component SCCR (kA)* |
Max. Wire Size |
||||||
---|---|---|---|---|---|---|---|---|---|---|
Three-Phase |
Circuit Breakers @ 480 V |
Fuses @ 600 V |
||||||||
208 V |
240 V |
480 V |
600 V |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
|||
LC1F115** |
30 |
40 |
75 |
100 |
175 |
200 |
65 |
200 |
100 |
2/0 AWG |
LC1F150** |
40 |
50 |
100 |
125 |
200 |
250 |
65 |
200 |
100 |
3/0 AWG |
LC1F185** |
50 |
60 |
125 |
150 |
200 |
250 |
65 |
400 |
100 |
3/0 AWG |
LC1F225 |
60 |
75 |
150 |
150 |
250 |
— |
— |
— |
— |
— |
LC1F265 |
60 |
75 |
150 |
200 |
285 |
— |
— |
600 |
100 |
300 MCM |
LC1F330 |
75 |
100 |
200 |
250 |
370 |
— |
— |
600 |
100 |
500 MCM |
LC1F400 |
100 |
125 |
250 |
300 |
420 |
— |
— |
— |
— |
— |
LC1F500 |
150 |
200 |
400 |
500 |
700 |
— |
— |
— |
— |
— |
LC1F630 |
250 |
300 |
600 |
800 |
1000 |
— |
— |
— |
— |
— |
LC1F800 |
350 |
400 |
800 |
900 |
1000 |
— |
— |
— |
— |
— |
LC1F780 |
— |
450 |
900 |
900 |
1350 |
— |
— |
— |
— |
— |
LC1F1000 |
350 |
400 |
900 |
— |
1250 |
— |
— |
— |
— |
— |
LC1F1400 |
— |
— |
— |
— |
1400 |
— |
— |
— |
— |
— |
LC1F1700 |
— |
— |
— |
— |
1700 |
— |
— |
— |
— |
— |
LC1F2100 |
— |
— |
— |
— |
2100 |
— |
— |
— |
— |
— |
NOTE: This table lists the maximum SCCR of the component when protected
by any circuit breaker or fuse. If the maximum component SCCR is 65
kA and a 25 kA rated circuit breaker is used, then the system will
be 25 kA, the SCCR rating of the circuit breaker.
|
Additional TeSys™ F Contactor Ratings
UL/CSA Lighting Ratings (HP)
Catalog Number |
Ballast |
Tungsten |
|
---|---|---|---|
480 V |
600 V |
480 V |
|
LC1F115 |
115 |
— |
115 |
LC1F150 |
150 |
— |
150 |
LC1F185 |
— |
200 |
200 |
LC1F265 |
— |
265 |
265 |
LC1F330 |
300 |
— |
300 |
Elevator Duty Ratings (HP)
Catalog Number |
Single-Phase |
Three-Phase |
|||
---|---|---|---|---|---|
240 V |
208 V |
240 V |
480 V |
600 V |
|
LC1F185 |
20 |
25 |
30 |
60 |
75 |
LC1F265 |
— |
40 |
40 |
— |
— |
LC1F330 |
— |
50 |
50 |
— |
— |
LC1F400 |
— |
60 |
60 |
— |
— |
LC1F500 |
— |
75 |
75 |
— |
— |
Definite Purpose Ratings, 3-Phase, Breaking All Lines (Hermetic Refrigeration Compressor)
Contactor |
FLA |
LRA |
FLA Cycles |
||
---|---|---|---|---|---|
240 V |
480 V |
600 V |
|||
LC1F115 |
135 |
800 |
800 |
520 |
100,000 |
LC1F150 |
150 |
900 |
750 |
700 |
100,000 |
LC1F185 |
220 |
1500 |
1500 |
1200 |
100,000 |
LC1F225 |
220 |
1500 |
1500 |
1200 |
100,000 |
LC1F265 |
270 |
1800 |
1900 |
1500 |
100,000 |
LC1F400 |
350 |
2000 |
2000 |
1800 |
100,000 |
LC1F500 |
700 |
4500 |
4500 |
4200 |
6,000 |
LC1F630 |
880 |
5000 |
5000 |
4850 |
6,000 |
LC1F780 |
1330 |
7500 |
7500 |
7290 |
6,000 |
TeSys™ N Contactors
TeSys N Contactors
Catalog Number* |
Standard Motor Ratings @ |
Cont. Current Rating (A) |
NEMA Size |
Max. Component SCCR (kA)* |
||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Three-Phase |
Circuit Breakers @ 480 V |
Circuit Breakers @ 600 V |
Fuses @ |
|||||||||
200 V |
230 V |
460 V |
575 V |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
Max. Size (A) |
Max. SCCR (kA) |
|||
T02AN13 |
1.5 |
1.5 |
2 |
2 |
9 |
00 |
60 |
85 |
60 |
50 |
60 |
100 |
T02BN13 |
3 |
3 |
5 |
5 |
18 |
0 |
60 |
85 |
60 |
50 |
60 |
100 |
T02CN13 |
7.5 |
7.5 |
10 |
10 |
27 |
1 |
60 |
85 |
60 |
50 |
80 |
100 |
T02DN13 |
10 |
15 |
25 |
25 |
45 |
2 |
110 |
100 |
110 |
50 |
125 |
100 |
T02EN13 |
25 |
30 |
50 |
50 |
90 |
3 |
200 |
65 |
— |
— |
200* |
100 |
T02FN13 |
40 |
50 |
100 |
100 |
135 |
4 |
250 |
65 |
— |
— |
200* |
100 |
T02GN13 |
75 |
100 |
200 |
200 |
270 |
5 |
— |
— |
— |
— |
600* |
100 |
T02HN13 |
150 |
200 |
400 |
400 |
540 |
6 |
— |
— |
— |
— |
— |
— |
T02JN13 |
— |
300 |
600 |
600 |
810 |
7 |
— |
— |
— |
— |
— |
— |
NOTE: This table
lists the maximum SCCR of the component when protected by any circuit
breaker or fuse. If the maximum component SCCR is 100 kA and a 25
kA rated circuit breaker is used, then the system will be 25 kA, the
SCCR rating for the circuit breaker.
|
Type S Contactors
Type S Contactors*
Catalog Number |
Standard Motor Ratings @ |
Max. Resistive AC1 Current (A) |
NEMA Size |
Max. Component SCCR (kA)* |
||||
---|---|---|---|---|---|---|---|---|
Three-Phase |
Circuit Breakers @ 480 V* |
Fuses @ 600 V |
||||||
200 V |
230 V |
460 V |
575 V |
|||||
8502SAO12 |
1.5 |
1.5 |
2 |
2 |
9 |
00 |
100 |
100* |
8502SBO2 |
3 |
3 |
5 |
5 |
18 |
0 |
100 |
100* |
8502SCO2 |
7.5 |
7.5 |
10 |
10 |
27 |
1 |
100 |
100* |
8502SDO2 |
10 |
15 |
25 |
25 |
45 |
2 |
100 |
100* |
8502SEO2 |
25 |
30 |
50 |
50 |
90 |
3 |
100 |
100* |
8502SFO2 |
40 |
50 |
100 |
100 |
135 |
4 |
100 |
100* |
8502SGO2 |
75 |
100 |
200 |
200 |
270 |
5 |
100 |
100* |
8502SHO2 |
150 |
200 |
400 |
400 |
540 |
6 |
65 |
100* |
8502SJO2 |
— |
300 |
600 |
600 |
810 |
7 |
30 |
30 |
Type S Contactor Maximum Component SCCR*
Catalog Number |
Circuit Breakers @ 480 V* |
Fuses @ 600 V |
||
---|---|---|---|---|
Max. Size (A) |
Max. SCCR (kA)* |
Max. Size (A) |
Max. SCCR (kA)* |
|
8502SAO12 |
70 |
100 |
60* |
100 |
8502SBO2 |
70 |
100 |
60* |
100 |
8502SCO2 |
70 |
100 |
60* |
100 |
8502SDO2 |
100 |
100 |
100* |
100 |
8502SEO2 |
150 |
100 |
200* |
100 |
8502SFO2 |
225 |
100 |
200* |
100 |
8502SGO2 |
400 |
100 |
400* |
100 |
8502SHO2 |
800 |
65 |
600* |
100 |
8502SJO2 |
2000 |
30 |
1500 |
30 |
Definite Purpose Contactors
DP Compact Contactors
Definite Purpose Type DP Compact Contactors
Catalog Number |
Max. Inductive AC3 Current (A) |
Locked Rotor Amperes |
Max. Resistive AC1 Current (A) |
Max. Component SCCR (kA)* |
|||
---|---|---|---|---|---|---|---|
Circuit Breakers @ |
Fuses @ |
||||||
277 V |
460 V |
575 V |
|||||
1-Pole Contactors |
|||||||
8910DP11 |
20 |
120 |
100 |
80 |
30 |
100 |
100 |
8910DP21 |
25 |
150 |
125 |
100 |
35 |
100 |