8536DB0901R03/21

Combination Starter Components

UL 98 Manual Disconnect Switches

TeSys™ GS Disconnect Switches

TeSys GS Disconnect Switch — GS2GU3N

TeSys™ GS Fusible Disconnect Switches

Catalog Number

Rating (A)

Poles

Maximum Rating (HP)

Short-Circuit Current Rating, 600 Vac Max.

240 V

480 V

600 V

250 Vdc

Fuse Type

SCCR (kA)

GS1DDU3

30

3

7.5

15

20

5

CC

100

GS1DU3

30

3

7.5

15

20

5

J

100

GS2EEU3

30

3

7.5

15

20

5

CC

100

GS2EU3N

30

3

7.5

15

20

5

J

100

GS2GU3N

60

3

15

30

50

10

J

100

GS2JU3N

100

3

30

60

75

20

J

200

GS2MU3N

200

3

60

125

150

40

J

200

GS2QU3N

400

3

125

250

350

50

J

200

GS2SU3

600

3

200

400

500

J

200

GS2TU3

800

3

200

500

500

L

200

TeSys™ VLS Disconnect Switches

TeSys VLS Non-Fusible Disconnect Switches — VLS3P063R2

TeSys VLS Non-Fusible Disconnect Switches

Catalog Number Mount Type General Use @ 600 V (Amperes) Max. Component SCCR (kA)
Circuit Breaker @ 480 V Fuses @ 480 V Fuses @ 600 V
 
Type Max. Size (A) Max. SCCR (kA) Type Max. Size (A) Max. SCCR (kA) Type Max. Size (A) Max. SCCR (kA)
VLS3P030R2 Rear 30 H-Frame 100 100 CC, J, or T 100 100 CC, J, or T 60 50
VLS3P063R2 Rear 60 H- or J-Frame 150 100 CC, J, or T 200 100 CC, J, or T 60 50
VLS3P080R2 Rear 100 J-Frame* 200 100 CC, J, or T 200 100 CC, J, or T 100 50
VLS3P100R2 Rear 100 J-Frame* 250 100 CC, J, or T 200 100 CC, J, or T 100 50
VLS3P125R2 Rear 100 J-Frame* 250 100 CC, J, or T 200 100 CC, J, or T 100 50
VLS3P030D2 Door 30 H-Frame 100 100 CC, J, or T 100 100 CC, J, or T 60 50
VLS3P063D2 Door 60 H- or J-Frame 150 100 CC, J, or T 200 100 CC, J, or T 60 50
VLS3P080D2 Door 100 J-Frame* 200 100 CC, J, or T 200 100 CC, J, or T 100 50
VLS3P100D2 Door 100 J-Frame* 250 100 CC, J, or T 200 100 CC, J, or T 100 50
VLS3P125D2 Door 100 J-Frame* 250 100 CC, J, or T 200 100 CC, J, or T 100 50

TeSys™ LK Disconnect Switches

TeSys LK Disconnect Switch — LK4SU3N

TeSys LK Non-Fusible Disconnect Switches

Catalog Number

Rating (A)

Poles

Maximum Rating (HP)

Short-Circuit Current Rating, 600 Vac Max.

240 V

480 V

600 V

250 Vdc

Fuse Type

SCCR (kA)

LK4DU3CN

30

3

10

20

30

J

100

LK4GU3CN

60

3

20

40

50

J

100

LK4JU3CN

100

3

20

50

50

J

100

LK4JU3N

100

3

30

75

100

15

J

200

LK4MU3N

200

3

75

150

200

15

J

200

LK4QU3N

400

3

125

250

350

50

J

200

LK4SU3N

600

3

200

400

350

50

J

200

LK4TU3N

800

3

200

500

500

L

100

LK4UU3N

1000

3

200

500

500

L

100

LK4WU3N

1200

3

200

500

500

L

100

Class 9422 Disconnect Switches

Flange Mounted, Variable Depth Disconnect Switch — 9422TF1

Class 9422 Flange Mounted, Variable Depth Fusible and Non-Fusible Disconnect Switches

Disconnect Switch Size (A)

Variable Depth Min.–Max. (in.)

Max. Horsepower Ratings

Fuse Type

Fuse Clip Rating Non-Interchangeable Type for Class H, J, K or R Fuses (A)

Catalog Number*

AC System Volts (Motor Volts)

Vdc

208 (200)

240 (230)

480 (460)

600 (575)

250

600

250 V

600 V

30

6.625–18

7.5

7.5

15

20

5

15

None

9422TCN30

H, J, K, R

30
60


30

9422TCF30 9422TCF33

60

6.625–18

15

30

50

10

30

None

9422TDN60

H, J, K, R

60

30
60

9422TDF60 9422TDF63

100

6.625–18

25

30

60

75

20

50

None

9422TEN10

H, J, K, R

100

100

9422TEF10

200

9.12–19.25*

40

60

125

150

40

50

None

9422TF1

H, J, K, R

200

200
400

9422TF2 9422TF3*

400 Fixed Depth*

11.38 (A5 or A6 Handle)

75

125

250

350

50

50

None

9422TG1**

 

400 Variable Depth*

15.87–19 (A7 or A8 Handle)*

H, J, K, R

400

400

9422TG2**

UL 248 Switches

TeSys™ DF Fuse Holders

TeSys DF Fuse Holders — DFCC3

TeSys DF Fuse Holders

Fuse Holder

Standards

Maximum Voltage

Current

Short-Circuit Current Rating

DFCC

IEC, UL (UL Listed)

600 Vac

30 A

200 kA

DF10

IEC, UL (UL Recognized)

690 Vac

33 A

200 kA

DF14

IEC, UL (UL Recognized)

690 Vac

50 A

200 kA

DF22

IEC, UL (UL Recognized)

690 Vac

125 A

200 kA

TeSys™ FB Fuse Holders

Type FB Fuse Holder — 9080FB3611J

Type FB 600 V Fuse Holders

Rating (A)

No. of Poles

Catalog Number

Short-Circuit Current Rating

Class J

Class R*
30

2

9080FB2611J

9080FB2611R

200 kA

3

9080FB3611J

9080FB3611R

60

1

9080FB1621R

2

9080FB2621J

3

9080FB3621J

9080FB3621R

100

3

9080FB3631R

UL 489 Molded-Case Circuit Breakers

PowerPact™ Circuit Breakers and Motor Circuit Protectors

PowerPact B Circuit Breaker — BJL36125

PowerPact™ Catalog Numbering System

Frame

Rating

Termination

Poles

Voltage

Amperage

Suffix Code

Suffix Code

B

J

L

3

6

125

AB

SA

                                 
                                 
                                 
                                 

Frame Designation

 

Interrupting Rating

 

Termination

 

Poles

 

Voltage

 

B 125 A Frame

 

See Table 11

 

A I-Line

 

1 1-Pole

 

4 480 V

 

H 150 A Frame

       

D Drawout

 

2 2-Pole

 

6 600 V

 

J 250 A Frame

       

F Bus Bar (No Lugs)

 

3 3-Pole

     

Q 250 A Frame

       

L Lugs on Both Ends

 

4 4-Pole

       

L 600 A Frame

       

M Lugs Line Side Only

         

M 800 A Frame

       

N Plug-in

         

P 1200 A Frame

       

P Lugs Load Side Only

         

R 3000 A Frame

       

S Rear Connected Studs

         

PowerPact Interrupting Ratings System

Voltage

Interrupting Rating

B

D

G

J

K

L

R

240 Vac

10 kA

25 kA

65 kA

100 kA

65 kA

125 kA

200 kA

480 Vac

 

18 kA

35 kA

65 kA

65 kA

100 kA

200 kA

600 Vac

 

14 kA

18 kA

25 kA

65 kA

50 kA

100 kA

Frame (X = available)

B-Frame (15–125 A)*

 

X

X

X

X*

   

H-Frame (15–150 A)

 

X

X

X

 

X

X

J-Frame (150–250 A)

 

X

X

X

 

X

X

Q-Frame (70–250 A)

X

X

X

X

     

L-Frame (200–600 A)

 

X

X

X

 

X

X

M-Frame (300–800 A)

   

X

X

     

P-Frame (250–1200 A)

   

X

X

X*

X

*

 

R-Frame (600–3000 A)

   

X

X

X

X

 

BV4 Motor Circuit Protector (MCP) Selection*

Frame

Motor Circuit Protector Ampacity (In)

Adjustable Instantaneous Trip (li)

Catalog Numbers

Standard Protection

High Protection

TeSys BV4

2

12–28

BV4T002D

BV4T002J

3.5

21–49

BV4T003D

BV4T003J

7

42–98

BV4T007D

BV4T007J

13

53–195

BV4T013D

BV4T013J

25

110–360

BV4T025D

BV4T025J

50

176–650

BV4T050D

BV4T050J

80

320–1150

BV4T080D

BV4T080J

115

600–1150

BV4T115D

BV4T115J

PowerPact H- and J-Frame Electronic Motor Circuit Protectors

Frame

Sensor Rating

Full Load Ampere Range

Adjustable Instantaneous Trip Range

Suffix

Catalog Numbers

J-Interrupting Cat. No.

L-Interrupting Cat. No.

R-Interrupting Cat. No.

H-Frame

30 A

1.5–25 A

9–325 A

M71

HJL36030M71

HLL36030M71

HRL36030M71

50 A

14–42 A

84–546 A

M72

HJL36050M72

HLL36050M72

HRL36050M72

100 A

30–80 A

180–1040 A

M73

HJL36100M73

HLL36100M73

HRL36100M73

150 A

58–130 A

348–1690 A

M74

HJL36150M74

HLL36150M74

HRL36150M74

J-Frame

250 A

114–217 A

684–2500 A

M75

JJL36250M75

JLL36250M75

JRL36250M75

UL 489 Miniature Circuit Breakers and UL 1077 Supplementary Protectors

Multi 9™ Circuit Breakers and Supplementary Protectors

Multi 9 UL 489 Circuit Breaker — M9F42110

Multi 9 UL 1077 Supplementary Protector — M9F22110

Multi 9 Catalog Numbering System

Range

Function

Number

Poles

Amperage

M9

F

42

1

10

                                         
                                         
                                         
                                         
 

Range

   

Function

 

Number

 

Poles

 

Amperage

 

M9 Multi 9

   

F MCB

 

Internal code number depending on the standard and electrical characteristics.

 

1 1-Pole

 

From 0.5– 63 A

         

P DPN

           

2 2-Pole

       
         

R RCCB

           

3 3-Pole

       
         

D RCBO

           

4 4-Pole

       
         

V Vigi C60 Add-on

                     
         

Y Vigi N40 Add-on

                     
         

C CTRL

                           

Multi 9 UL 489 Breaking Capacity

Number of Poles

Current Rating (A)

Voltage, AC

120 V

240 V

277 V

480/277 V

1 Pole

1–35

14

14

10

40–63

10

10

2 Pole

1–35

14

14

10

10

40–63

10

10

3 Pole

1–35

14

14

10

10

40–63

10

10

Multi 9 UL 1077 Breaking Capacity

Number of Poles

Current Rating (A)

Voltage, AC

120 V

240 V

277 V

480/277 V

1 Pole

0.5–35

14

14

10

40–63

10

10

5

2 Pole

1–35

14

14

10

10

40–63

10

10

5

5

3 and 4 Pole

1–35

14

14

10

10

40–63

10

10

5

5

UL 60947 Contactors

TeSys™ K Contactors

TeSys K Contactor — LC1K09

TeSys K Contactors (Except for Spring Terminal Clamps)

Catalog Number

Standard Motor Ratings @ 50/60 Hz (HP)

Cont. Current Ratings

Max. Component SCCR (kA)*

Single-Phase

Three-Phase

Circuit Breakers @
480 V

Circuit Breakers @ 600 V

Fuses @ 600 V

120 V

240 V

208 V

240 V

480 V

600 V

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

LC1K06

1/2

1

1.5

1.5

3

3

10

20

65

20

25

25

100

LC1K09

1/2

1.5

2

3

5

5

20

20

65

20

25

30

100

LC1K12

1

2

3

3

7.5

10

20

20

65

20

25

30

100

NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum component SCCR is 65 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA, the SCCR rating of the circuit breaker.

TeSys™ D Contactors

TeSys D Contactor — LC1D12

TeSys D 3-Pole Contactors

Catalog Number

Standard Motor Ratings @ 50/60 Hz (HP)

Cont. Current Rating (A)

Max. Component SCCR (kA)*

Single-Phase

Three-Phase

Circuit Breakers @ 480 V

Circuit Breakers @ 600 V

Fuses @
600 V

120 V

240 V

208 V

240 V

480 V

600 V

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

LC1D09

1/3

1

2

2

5

7.5

25

35

85

35

50

25

100

LC1D12

1/2

2

3

3

7.5

10

25

35

85

35

50

30

100

LC1D18

1

3

5

5

10

15

32

60

85

35

50

40

100

LC1D25

2

3

7.5

7.5

15

20

40

60

85

60

50

60

100

LC1D32

2

5

10

10

20

25

50

60

85

60

50

80

100

LC1D38

2

5

10

10

20

25

50

60

85

60

50

80

100

LC1D40A

3

5

10

10

30

30

60

110

100

110

50

90

100

LC1D50A

3

7.5

15

15

40

40

70

110

100

110

50

110

100

LC1D65A

5

10

20

20

40

50

80

110

100

110

50

125

100

LC1D80

7.5

15

25

30

60

60

110

150

100

150

50

175

100

LC1D95

7.5

15

25

30

60

60

110

LC1D115

30

40

75

100

160

250

100

250

50

250

100

LC1D150

40

50

100

125

160

250

100

250

50

300

100

NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA, the SCCR rating of the circuit breaker.

TeSys D 4-Pole Contactors

Catalog Number

Continuous Current Rating (A)

No. of Poles

Max. Component SCCR (kA)*

Circuit Breakers @
480 V

Circuit Breakers @ 600 V

Fuses @ 600 V

N.O.

N.C.

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

LC1DT20

25

4

0

35

85

35

50

25

100

LC1D098

25

2

2

35

85

35

50

25

100

LC1DT25

25

4

0

35

85

35

50

30

100

LC1D128

25

2

2

35

85

35

50

30

100

LC1DT32

32

4

0

60

85

35

50

40

100

LC1D188

32

2

2

60

85

35

50

40

100

LC1DT40

40

4

0

60

85

60

50

60

100

LC1D258

40

2

2

60

85

60

50

60

100

LC1DT60A

60

4

0

110

100

110

50

TBD

100

LC1DT80A

80

4

0

110

100

110

50

TBD

100

LC1D80004

110

4

0

150

100

175

50

175

100

LC1D80008

110

2

2

150

100

175

50

175

100

LC1D115004

160

4

0

250

100

250

50

250

100

NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA, the SCCR rating of the circuit breaker.

TeSys D LC2D Contactors

Catalog Number

Max. Component SCCR (kA)

Circuit Breaker @ 480 V

Circuit Breaker @ 600 V

Fuses @ 600 V

 

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

LC2D40A

110

100

110

50

90

100

LC2D50A

110

100

110

50

110

100

LC2D65A

110

100

110

50

125

100

LC2D115

250

100

250

50

250

100

LC2D150

250

100

250

50

300

100

LC2D115004

250

100

250

50

250

100

Additional TeSys™ D Contactor Ratings

UL/CSA Lighting Ratings (HP)

Catalog Number

Ballast

Tungsten

600 V

480 Y / 277 V

480 V

600 V

LC1D09*, LC1DT20*

20

20

LC1D12*, LC1DT25*

25

LC1D18*, LC1DT32*

32

25

LC1D25*, LC1DT40*

40

40

LC1D32*

50

50

LC1D40A

60

60

LC1D50A

70

70

LC1D65A

80

70

LC1D80, LC1D80004

100

100

LC1D115, LC1D1150004

115

115

LC1D150, LC1D1500004

150

150

Elevator Duty Ratings (HP)

Catalog Number

Single-Phase

Three-Phase

240 V

208 V

240 V

480 V

600 V

LC1D12

1.5

2

3

7.5

7.5

LC1D18*

3

5

5

LC1D25

3

5

7.5

15

20

LC1D32

5

10

7.5

LC1D40A*

5

10

10

LC1D50A*

7.5

15

15

LC1D50*

7.5

10

15

25

30

LC1D65*

10

15

20

40

50

LC1D80

15

20

25

50

50

LC1D150

15

25

30

60

75

Definite Purpose Ratings, 3-Phase, Breaking All Lines (Hermetic Refrigeration Compressor)

Catalog Number

FLA

Locked Rotor Amperes (LRA)

FLA Cycles

240 V

480 V

600 V

LC1D09

9

54

45

36

100,000

LC1D12

12

72

60

48

100,000

LC1D18

18

108

90

72

100,000

LC1D25

25

150

125

100

100,000

LC1D32

32

192

160

128

100,000

LC1D40A

40

240

200

160

100,000

LC1D50A

50

300

250

200

100,000

LC1D65A

65

390

325

260

100,000

LC1D80 (AC)

80

480

400

320

100,000

LC1D80 (DC)

75

450

375

300

100,000

LC1D115

115

690

575

460

100,000

LC1D150

150

900

750

600

100,000

TeSys™ F Contactors

TeSys F Contactor — LC1F400

TeSys F Contactors

Catalog Number

Standard Motor Ratings @
50/60 Hz (HP)

Continuous Current Rating (A)

Max. Component SCCR (kA)*

Max. Wire Size

Three-Phase

Circuit Breakers @ 480 V

Fuses @ 600 V

208 V

240 V

480 V

600 V

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

LC1F115**

30

40

75

100

175

200

65

200

100

2/0 AWG

LC1F150**

40

50

100

125

200

250

65

200

100

3/0 AWG

LC1F185**

50

60

125

150

200

250

65

400

100

3/0 AWG

LC1F225

60

75

150

150

250

LC1F265

60

75

150

200

285

600

100

300 MCM

LC1F330

75

100

200

250

370

600

100

500 MCM

LC1F400

100

125

250

300

420

LC1F500

150

200

400

500

700

LC1F630

250

300

600

800

1000

LC1F800

350

400

800

900

1000

LC1F780

450

900

900

1350

LC1F1000

350

400

900

1250

LC1F1400

1400

LC1F1700

1700

LC1F2100

2100

NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum component SCCR is 65 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA, the SCCR rating of the circuit breaker.

Additional TeSys™ F Contactor Ratings

UL/CSA Lighting Ratings (HP)

Catalog Number

Ballast

Tungsten

480 V

600 V

480 V

LC1F115

115

115

LC1F150

150

150

LC1F185

200

200

LC1F265

265

265

LC1F330

300

300

Elevator Duty Ratings (HP)

Catalog Number

Single-Phase

Three-Phase

240 V

208 V

240 V

480 V

600 V

LC1F185

20

25

30

60

75

LC1F265

40

40

LC1F330

50

50

LC1F400

60

60

LC1F500

75

75

Definite Purpose Ratings, 3-Phase, Breaking All Lines (Hermetic Refrigeration Compressor)

Contactor

FLA

LRA

FLA Cycles

240 V

480 V

600 V

LC1F115

135

800

800

520

100,000

LC1F150

150

900

750

700

100,000

LC1F185

220

1500

1500

1200

100,000

LC1F225

220

1500

1500

1200

100,000

LC1F265

270

1800

1900

1500

100,000

LC1F400

350

2000

2000

1800

100,000

LC1F500

700

4500

4500

4200

6,000

LC1F630

880

5000

5000

4850

6,000

LC1F780

1330

7500

7500

7290

6,000

TeSys™ N Contactors

TeSys N Contactor — T02CN13

TeSys N Contactors

Catalog Number*

Standard Motor Ratings @
50/60 Hz (HP)

Cont. Current Rating (A)

NEMA Size

Max. Component SCCR (kA)*

Three-Phase

Circuit Breakers @ 480 V

Circuit Breakers @ 600 V

Fuses @
600 V

200 V

230 V

460 V

575 V

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

Max. Size (A)

Max. SCCR (kA)

T02AN13

1.5

1.5

2

2

9

00

60

85

60

50

60

100

T02BN13

3

3

5

5

18

0

60

85

60

50

60

100

T02CN13

7.5

7.5

10

10

27

1

60

85

60

50

80

100

T02DN13

10

15

25

25

45

2

110

100

110

50

125

100

T02EN13

25

30

50

50

90

3

200

65

200*

100

T02FN13

40

50

100

100

135

4

250

65

200*

100

T02GN13

75

100

200

200

270

5

600*

100

T02HN13

150

200

400

400

540

6

T02JN13

300

600

600

810

7

NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA, the SCCR rating for the circuit breaker.

Type S Contactors

Type S Contactor — 8502SAO11

Type S Contactors*

Catalog Number

Standard Motor Ratings @
50/60 Hz (HP)

Max. Resistive AC1 Current (A)

NEMA Size

Max. Component SCCR (kA)*

Three-Phase

Circuit Breakers @ 480 V*

Fuses @ 600 V

200 V

230 V

460 V

575 V

8502SAO12

1.5

1.5

2

2

9

00

100

100*

8502SBO2

3

3

5

5

18

0

100

100*

8502SCO2

7.5

7.5

10

10

27

1

100

100*

8502SDO2

10

15

25

25

45

2

100

100*

8502SEO2

25

30

50

50

90

3

100

100*

8502SFO2

40

50

100

100

135

4

100

100*

8502SGO2

75

100

200

200

270

5

100

100*

8502SHO2

150

200

400

400

540

6

65

100*

8502SJO2

300

600

600

810

7

30

30

Type S Contactor Maximum Component SCCR*

Catalog Number

Circuit Breakers @ 480 V*

Fuses @ 600 V

Max. Size (A)

Max. SCCR (kA)*

Max. Size (A)

Max. SCCR (kA)*

8502SAO12

70

100

60*

100

8502SBO2

70

100

60*

100

8502SCO2

70

100

60*

100

8502SDO2

100

100

100*

100

8502SEO2

150

100

200*

100

8502SFO2

225

100

200*

100

8502SGO2

400

100

400*

100

8502SHO2

800

65

600*

100

8502SJO2

2000

30

1500

30

Definite Purpose Contactors

DP Compact Contactors

Definite Purpose Type DP Compact Contactor — 8910DP22V09

Definite Purpose Type DP Compact Contactors

Catalog Number

Max. Inductive AC3 Current (A)

Locked Rotor Amperes

Max. Resistive AC1 Current

(A)

Max. Component SCCR (kA)*

Circuit Breakers @
480 V *

Fuses @
600 V*

277 V

460 V

575 V

1-Pole Contactors

8910DP11

20

120

100

80

30

100

100

8910DP21

25

150

125

100

35

100