Uploading a Duplicate Configuration with a USB Key
![]() |
---|
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Failure to follow these instructions will result in death or serious injury.
|
- Copy the duplicate configuration file to a folder named "Restore" at the root of the USB key.
- Power off the Com’X, then plug the USB key into the USB port on the Com’X front panel.
- Power on the Com’X, and wait for it to reboot.
When the power LED turns green, the reboot is complete.
- Reconnect to the Com’X.
- Click .
- Type the new site location name, then click Save changes to save the modification. NOTE: The site location name may not include any of the following: '/:*?<>| or space.
- Click the Device Settings tab.
- Select the Com’X in the Device tree view.
- Type the Com’X name in the General Properties collapsible menu.
- Click Save changes to save your modification.
- Click the Measurement table tab to check the correct connection, setting, and functioning on the new site.
- Select Commissioning tab to activate
logging and publication according to destination platform.
(see Commissioning for more information)