Anbefalet beskyttelse før indgangen på UPS'en for Easy UPS 3-Phase Modular
3+0 parallelt system for kapacitet | 2+0
parallelt system for kapacitet 2+1 parallelt system for redundans |
1+0 enkelt system 1+1 parallelt system for redundans |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
UPS-klassifikation | Afbrydertype | Io | Ir | Isd | Afbrydertype | Io | Ir | Isd | Afbrydertype | Io | Ir | Isd |
50 kW |
NSX250H TM250D (C25H3TM250) |
– |
250 |
5-10 |
NSX160H TM160D (C16H3TM160) |
– |
160 |
1250 (fast) |
NSX100H TM80D (C10H3TM080) |
– |
80 |
640 (fast) |
100 kW |
NSX630H mic2.3 (C63H32D630) |
500 |
1 |
1,5-10 |
NSX400H mic2.3 (C40H32D400) |
320 |
1 |
1,5-10 |
NSX160H TM160D (C16H6TM160) |
160 |
160 |
1250 (fast) |
150 kW | – | – | – | – |
NSX630H mic2.3 (C63H32D630) |
500 |
1 |
1,5-10 |
NSX250H TM250 (C25H3TM250) |
250 |
250 |
5-10 |
200 kW | – | – | – | – |
NSX630H mic2.3 (C63H32D630) |
630 |
1 |
1,5-10 |
NSX400H MiC.2.3 (C40H32D400) |
320 |
1 |
1,5-10 |
250 kW | – | – | – | – | – | – | – | – |
NSX400H MiC.2.3 (C40H32D400) |
400 |
1 |
1,5-10 |