990-91377E-012

Rendement

200 kW Mode normal Mode ECO
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

96.5%

96.6%

96.5%

96.5%

98.9%

98.8%

98.9%

98.9%

50 % de la charge

97.0%

97.1%

97.1%

97.1%

99.3%

99.3%

99.3%

99.2%

75 % de la charge

96.9%

97.0%

97.1%

97.2%

99.3%

99.4%

99.4%

99.4%

100 % de la charge

96.5%

96.7%

96.9%

97.0%

99.4%

99.4%

99.4%

99.4%

200 kW eConversion Mode batterie
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

98.4%

98.4%

98.3%

98.3%

96.0%

96.0%

96.0%

95.5%

50 % de la charge

99.0%

99.0%

99.0%

99.0%

96.6%

96.6%

96.6%

96.3%

75 % de la charge

99.2%

99.2%

99.2%

99.2%

96.6%

96.6%

96.6%

96.5%

100 % de la charge

99.3%

99.3%

99.3%

99.3%

96.4%

96.4%

96.4%

96.4%

250 kW Mode normal Mode ECO
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

96.6%

96.6%

96.6%

96.5%

98.9%

98.9%

98.9%

98.9%

50 % de la charge

97.0%

97.1%

97.1%

97.2%

99.3%

99.3%

99.3%

99.3%

75 % de la charge

96.9%

97.0%

97.1%

97.2%

99.4%

99.4%

99.4%

99.4%

100 % de la charge

96.5%

96.7%

96.8%

97.0%

99.4%

99.4%

99.4%

99.4%

250 kW eConversion Mode batterie
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

98.4%

98.4%

98.3%

98.3%

96.1%

96.1%

96.1%

95.7%

50 % de la charge

99.0%

99.0%

99.0%

99.0%

96.6%

96.6%

96.6%

96.4%

75 % de la charge

99.2%

99.2%

99.2%

99.2%

96.6%

96.6%

96.6%

96.5%

100 % de la charge

99.3%

99.3%

99.3%

99.3%

96.4%

96.4%

96.4%

96.4%

300 kW Mode normal Mode ECO
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

96.6%

96.6%

96.6%

96.5%

98.9%

99.0%

98.9%

98.9%

50 % de la charge

97.0%

97.1%

97.1%

97.2%

99.3%

99.3%

99.3%

99.3%

75 % de la charge

96.9%

97.0%

97.1%

97.2%

99.4%

99.4%

99.4%

99.4%

100 % de la charge

96.5%

96.7%

96.8%

97.0%

99.4%

99.4%

99.4%

99.4%

300 kW eConversion Mode batterie
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

98.4%

98.4%

98.3%

98.3%

96.2%

96.2%

96.2%

95.8%

50 % de la charge

99.0%

99.0%

99.0%

99.0%

96.7%

96.7%

96.7%

96.4%

75 % de la charge

99.2%

99.2%

99.2%

99.2%

96.6%

96.6%

96.6%

96.5%

100 % de la charge

99.3%

99.3%

99.3%

99.3%

96.4%

96.4%

96.4%

96.4%

350 kW Mode normal Mode ECO
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

96.6%

96.6%

96.6%

96.5%

99.0%

99.0%

99.0%

99.0%

50 % de la charge

97.0%

97.1%

97.1%

97.1%

99.3%

99.3%

99.3%

99.3%

75 % de la charge

96.8%

97.0%

97.1%

97.2%

99.3%

99.4%

99.4%

99.4%

100 % de la charge

96.5%

96.7%

96.8%

97.0%

99.4%

99.4%

99.4%

99.4%

350 kW eConversion Mode batterie
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

98.4%

98.4%

98.4%

98.3%

96.3%

96.3%

96.3%

95.9%

50 % de la charge

99.1%

99.0%

99.0%

99.0%

96.7%

96.7%

96.7%

96.5%

75 % de la charge

99.2%

99.2%

99.2%

99.2%

96.6%

96.6%

96.6%

96.5%

100 % de la charge

99.3%

99.3%

99.3%

99.3%

96.4%

96.4%

96.4%

96.4%

400 kW Mode normal Mode ECO
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

96.6%

96.6%

96.6%

96.5%

99.0%

99.0%

99.0%

99.0%

50 % de la charge

97.0%

97.1%

97.1%

97.1%

99.3%

99.3%

99.3%

99.3%

75 % de la charge

96.8%

97.0%

97.1%

97.2%

99.3%

99.4%

99.4%

99.4%

100 % de la charge

96.5%

96.7%

96.8%

97.0%

99.4%

99.4%

99.4%

99.4%

400 kW eConversion Mode batterie
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

98.4%

98.4%

98.4%

98.3%

96.3%

96.3%

96.3%

95.9%

50 % de la charge

99.1%

99.0%

99.0%

99.0%

96.7%

96.7%

96.7%

96.5%

75 % de la charge

99.2%

99.2%

99.2%

99.2%

96.6%

96.6%

96.6%

96.5%

100 % de la charge

99.3%

99.3%

99.3%

99.3%

96.4%

96.4%

96.4%

96.4%

450 kW Mode normal Mode ECO
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

96.6%

96.6%

96.6%

96.5%

99.0%

99.0%

99.0%

99.0%

50 % de la charge

97.0%

97.1%

97.1%

97.1%

99.3%

99.3%

99.3%

99.3%

75 % de la charge

96.8%

96.9%

97.0%

97.1%

99.3%

99.3%

99.4%

99.4%

100 % de la charge

96.4%

96.6%

96.8%

96.9%

99.3%

99.4%

99.4%

99.4%

450 kW eConversion Mode batterie
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

98.5%

98.4%

98.4%

98.3%

96.3%

96.3%

96.3%

96.0%

50 % de la charge

99.1%

99.0%

99.0%

99.0%

96.7%

96.7%

96.7%

96.5%

75 % de la charge

99.2%

99.2%

99.2%

99.2%

96.6%

96.6%

96.6%

96.5%

100 % de la charge

99.3%

99.3%

99.3%

99.3%

96.4%

96.4%

96.4%

96.4%

500 kW Mode normal Mode ECO
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

96.6%

96.6%

96.6%

96.5%

99.0%

99.0%

99.0%

99.0%

50 % de la charge

97.0%

97.1%

97.1%

97.1%

99.3%

99.3%

99.3%

99.3%

75 % de la charge

96.8%

96.9%

97.0%

97.1%

99.3%

99.3%

99.4%

99.4%

100 % de la charge

96.4%

96.6%

96.8%

96.9%

99.3%

99.4%

99.4%

99.4%

500 kW eConversion Mode batterie
Tension (V) 380 400 415 440 380 400 415 440
25 % de la charge

98.5%

98.4%

98.4%

98.3%

96.3%

96.3%

96.3%

96.0%

50 % de la charge

99.1%

99.0%

99.0%

99.0%

96.7%

96.7%

96.7%

96.5%

75 % de la charge

99.2%

99.2%

99.2%

99.2%

96.6%

96.6%

96.6%

96.5%

100 % de la charge

99.3%

99.3%

99.3%

99.3%

96.4%

96.4%

96.4%

96.4%