990–91203–001

Battery Breaker Kit GVSBBK100K200H Specifications

DANGER
hazard of electric shock, explosion or arc flash
The battery breaker kit GVSBBK100K200H must only be used with the Galaxy VS UPS.
Failure to follow these instructions will result in death or serious injury.
Battery breaker LV438279
Maximum configuration 200 kW: 1 hour runtime
100-150 kW: 4 hour runtime
Battery type VRLA
Maximum battery short-circuit level (kA) 35
Minimum short-circuit current to trip circuit breaker (A) 1500
QR code for this page