Kurzschlussfunktionen des Wechselrichters (Bypass nicht verfügbar)
IK1 – Kurzschluss zwischen einer Phase und Neutral
IK1 400 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
33/11 |
33/22 |
33/33 |
29/104 |
23/603 |
15 |
50/25 |
50/50 |
50/75 |
44/235 |
34/1356 |
20 |
67/45 |
67/89 |
67/134 |
58/418 |
46/2411 |
30 |
100/100 |
100/200 |
100/300 |
87/940 |
68/5420 |
40 |
133/180 |
133/360 |
133/530 |
116/1670 |
91/9640 |
50 |
167/280 |
167/560 |
167/830 |
145/2610 |
114/15070 |
60 |
200/400 |
200/800 |
200/1200 |
174/3760 |
137/21700 |
80 |
267/710 |
267/1420 |
267/2140 |
232/6690 |
182/38580 |
100 |
334/1110 |
334/2230 |
334/3340 |
291/10450 |
228/60270 |
120 |
400/1600 |
400/3210 |
400/4810 |
349/15050 |
274/86800 |
150 |
500/2500 |
500/5010 |
500/7510 |
436/23510 |
342/135620 |
IK2 – Kurzschluss zwischen zwei Phasen
IK2 400 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
34/11 |
33/23 |
33/34 |
28/99 |
22/571 |
15 |
50/26 |
50/51 |
50/76 |
42/223 |
33/1285 |
20 |
67/45 |
67/90 |
67/135 |
56/397 |
44/2284 |
30 |
101/100 |
100/200 |
100/300 |
84/890 |
67/5140 |
40 |
135/180 |
134/360 |
134/540 |
112/1590 |
89/9140 |
50 |
168/280 |
167/570 |
167/840 |
141/2480 |
111/14280 |
60 |
202/410 |
201/810 |
201/1210 |
169/3570 |
133/20560 |
80 |
269/730 |
268/1450 |
268/2150 |
225/6350 |
178/36550 |
100 |
336/1130 |
335/2260 |
335/3370 |
281/9920 |
222/57110 |
120 |
404/1630 |
401/3250 |
401/4850 |
337/14280 |
266/82230 |
150 |
505/2550 |
502/5090 |
502/7580 |
422/22320 |
333/128490 |
IK3 – Kurzschluss zwischen drei Phasen
IK3 400 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
30/9 |
30/18 |
30/27 |
29/88 |
23/574 |
15 |
45/20 |
45/40 |
45/60 |
43/198 |
34/1290 |
20 |
60/36 |
60/71 |
60/107 |
57/351 |
45/2294 |
30 |
90/80 |
90/160 |
90/240 |
86/790 |
68/5160 |
40 |
119/140 |
119/290 |
119/430 |
115/1400 |
90/9180 |
50 |
149/220 |
149/450 |
149/670 |
143/2200 |
113/14340 |
60 |
179/320 |
179/640 |
179/960 |
172/3160 |
136/20650 |
80 |
239/570 |
239/1140 |
239/1710 |
229/5620 |
181/36710 |
100 |
298/890 |
298/1780 |
298/2670 |
287/8780 |
226/57350 |
120 |
358/1280 |
358/2570 |
358/3850 |
344/12640 |
271/82590 |
150 |
448/2000 |
448/4010 |
448/6010 |
430/19760 |
339/129040 |