Kortsluitcapaciteiten van omvormer (Bypass niet beschikbaar)
IK1 – kortsluiting tussen fase en nulleider
IK1 400 V
S [kVA] |
10ms; I[A]/I2t [A2t] |
20ms; I[A]/I2t [A2t] |
30ms; I[A]/I2t [A2t] |
100ms; I[A]/I2t [A2t] |
1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
33 / 11 |
33 / 22 |
33 / 33 |
29 / 104 |
23 / 603 |
15 |
50 / 25 |
50 / 50 |
50 / 75 |
44 / 235 |
34 / 1356 |
20 |
67 / 45 |
67 / 89 |
67 / 134 |
58 / 418 |
46 / 2411 |
IK2 - kortsluiting tussen twee fasen
IK2 400 V
S [kVA] |
10ms; I[A]/I2t [A2t] |
20ms; I[A]/I2t [A2t] |
30ms; I[A]/I2t [A2t] |
100ms; I[A]/I2t [A2t] |
1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
34 / 11 |
33 / 23 |
33 / 34 |
28 / 99 |
22 / 571 |
15 |
50 / 26 |
50 / 51 |
50 / 76 |
42 / 223 |
33 / 1285 |
20 |
67 / 45 |
67 / 90 |
67 / 135 |
56 / 397 |
44 / 2284 |
IK3 - kortsluiting tussen drie fasen
IK3 400 V
S [kVA] |
10ms; I[A]/I2t [A2t] |
20ms; I[A]/I2t [A2t] |
30ms; I[A]/I2t [A2t] |
100ms; I[A]/I2t [A2t] |
1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
30 / 9 |
30 / 18 |
30 / 27 |
29 / 88 |
23 / 574 |
15 |
45 / 20 |
45 / 40 |
45 / 60 |
43 / 198 |
34 / 1290 |
20 |
60 / 36 |
60 / 71 |
60 / 107 |
57 / 351 |
45 / 2294 |