Load Derating for UPS with IP52 Kit Installed
| NOTICE |
|---|
|
Risk of overheating
Failure to follow these instructions can result in equipment damage.
|
380/400/415/480 V UPS
| UPS rating | Maximum continuous load at 30 °C (86 °F) | Maximum continuous load at 35 °C (95 °F) | Maximum continuous load at 40 °C (104 °F) | Operating temperature and load derating |
|---|---|---|---|---|
|
20 kW |
20 kW |
20 kW |
20 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
30 kW |
30 kW |
30 kW |
30 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
40 kW |
40 kW |
34 kW |
30 kW |
0 °C to 30 °C (32 °F to 86 °F): No derating; 30 °C to 40 °C (32 °F to 104 °F): Reduce load with 3% for every °C. |
| 40 kW (N+1 power module) |
40 kW |
40 kW |
40 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
50 kW |
40 kW |
34 kW |
30 kW |
40 kW maximum load on UPS. Output overload alarm settings need to be adjusted by Schneider Electric Service. |
| 50 kW (N+1 power module) |
50 kW |
50 kW |
50 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
60 kW |
60 kW |
60 kW |
50 kW |
0 °C to 35 °C (32 °F to 95 °F): No derating; 35 °C to 40 °C (95 °F to 104 °F): Reduce load with 3% for every °C. |
| 60 kW (N+1 power module) |
60 kW |
60 kW |
60 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
80 kW |
80 kW |
68 kW |
50 kW |
0 °C to 30 °C (32 °F to 86 °F): No derating; 30 °C to 40 °C (86 °F to 104 °F): Reduce load with 3% for every °C. |
| 80 kW (N+1 power module) |
80 kW |
80 kW |
80 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
100 kW |
80 kW |
68 kW |
50 kW |
80 kW maximum load on UPS. Output overload alarm settings need to be adjusted by Schneider Electric Service. |
| 100 kW (N+1 power module) |
100 kW |
100 kW |
84 kW |
0 °C to 35 °C (32 °F to 95 °F): No derating; 35 °C to 40 °C (95 °F to 104 °F): Reduce load with 3% for every °C. |
|
120 kW |
120 kW |
102 kW |
84 kW |
0 °C to 30 °C (32 °F to 86 °F): No derating; 30 °C to 40 °C (86 °F to 104 °F): Reduce load with 3% for every °C. |
|
150 kW |
120 kW |
102 kW |
84 kW |
120 kW maximum load on UPS. Output overload alarm settings need to be adjusted by Schneider Electric Service. |
200/208/220 V UPS
| UPS rating | Maximum continuous load at 30 °C (86 °F) | Maximum continuous load at 35 °C (95 °F) | Maximum continuous load at 40 °C (104 °F) | Operating temperature and load derating |
|---|---|---|---|---|
|
10 kW |
10 kW |
10 kW |
10 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
15 kW |
15 kW |
15 kW |
15 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
20 kW |
20 kW |
17 kW |
15 kW |
0 °C to 30 °C (32 °F to 86 °F): No derating; |
| 20 (N+1 power module) |
20 kW |
20 kW |
20 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
25 kW |
20 kW |
17 kW |
15 kW |
20 kW maximum load on UPS. Output overload alarm settings need to be adjusted by Schneider Electric Service. |
| 25 (N+1 power module) |
25 kW |
25 kW |
25 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
30 kW |
30 kW |
30 kW |
25 kW |
0 °C to 35 °C (32 °F to 95 °F): No derating; |
|
40 kW |
40 kW |
34 kW |
25 kW |
0 °C to 30 °C (32 °F to 86 °F): No derating; |
| 40 (N+1 power module) |
40 kW |
40 kW |
40 kW |
0 °C to 40 °C (32 °F to 104 °F): No derating. |
|
50 kW |
40 kW |
34 kW |
25 kW |
40 kW maximum load on UPS. Output overload alarm settings need to be adjusted by Schneider Electric Service. |
| 50 (N+1 power module) |
50 kW |
50 kW |
50 kW |
0 °C to 35 °C (32 °F to 95 °F): No derating; |
|
60 kW |
60 kW |
51 kW |
42 kW |
0 °C to 30 °C (32 °F to 86 °F): No derating; |
|
75 kW |
60 kW |
51 kW |
42 kW |
60 kW maximum load on UPS. Output overload alarm settings need to be adjusted by Schneider Electric Service. |