Capacités de court-circuit de l'onduleur (bypass non disponible)
IK1 – Court-circuit entre une phase et le neutre
IK1 480 V
S [kVA] |
10ms; I[A]/I2t [A2t] |
20ms; I[A]/I2t [A2t] |
30ms; I[A]/I2t [A2t] |
100ms; I[A]/I2t [A2t] |
1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
20 |
56 / 31 |
56 / 62 |
56 / 93 |
48 / 290 |
38 / 1674 |
IK1 208 V
S [kVA] |
10ms; I[A]/I2t [A2t] |
20ms; I[A]/I2t [A2t] |
30ms; I[A]/I2t [A2t] |
100ms; I[A]/I2t [A2t] |
1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
64 / 41 |
64 / 82 |
64 / 123 |
56 / 386 |
44 / 2229 |
IK2 - Court-circuit entre deux phases
IK2 480 V
S [kVA] |
10ms; I[A]/I2t [A2t] |
20ms; I[A]/I2t [A2t] |
30ms; I[A]/I2t [A2t] |
100ms; I[A]/I2t [A2t] |
1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
20 |
56 / 31 |
56 / 63 |
56 / 94 |
47 / 276 |
37 / 1586 |
IK2 208 V
S [kVA] |
10ms; I[A]/I2t [A2t] |
20ms; I[A]/I2t [A2t] |
30ms; I[A]/I2t [A2t] |
100ms; I[A]/I2t [A2t] |
1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
65 / 42 |
64 / 84 |
64 / 125 |
54 / 367 |
43 / 2112 |
IK3 - Court-circuit entre trois phases
IK3 480 V
S [kVA] |
10ms; I[A]/I2t [A2t] |
20ms; I[A]/I2t [A2t] |
30ms; I[A]/I2t [A2t] |
100ms; I[A]/I2t [A2t] |
1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
20 |
50 / 25 |
50 / 49 |
50 / 74 |
48 / 244 |
38 / 1593 |
IK3 208 V
S [kVA] |
10ms; I[A]/I2t [A2t] |
20ms; I[A]/I2t [A2t] |
30ms; I[A]/I2t [A2t] |
100ms; I[A]/I2t [A2t] |
1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
57 / 33 |
57 / 66 |
57 / 99 |
55 / 325 |
43 / 2121 |