Insulation alarm relay (Ins. Al. Relay)
You can set the insulation alarm relay mode depending on the status of insulation.
To access the setting, select .
-
Parameter: Relay
-
Allowed values: FS / Std.
-
Default: FS
When the insulation alarm relay is configured in failsafe (FS) mode:
-
The insulation alarm relay is activated, that is, energized, in the following case:
-
No insulation fault is detected.
-
-
The insulation alarm relay is deactivated, that is, de-energized, in the following cases:
-
Insulation fault is detected.
-
The product is inoperative (detected by auto-test).
-
The auxiliary power supply is lost.
-
When you trigger an auto-test
-
When the insulation alarm relay is configured in standard (Std.) mode:
-
The insulation alarm relay is activated, that is, energized, in the following cases:
-
Insulation fault is detected.
-
The product is inoperative (detected by auto-test).
-
When you trigger an auto-test
-
-
The insulation alarm relay is deactivated, that is, de-energized, in the following cases:
-
No insulation fault is detected.
-
Insulation fault is detected and acknowledged (if is set to ON).
-
The auxiliary power supply is lost.
-