Other changes in v421

The relationship between the logging mode and the insert outage records feature in the Data Recorder module has changed in v421.

If the Insert Outage Records register is set to yes - zero fill enabled, the LogMode register must be set to high speed continuous or else the module will remain offline.

NOTE: If you have set up custom frameworks on your meter, make sure that you adjust the settings in those frameworks, if needed, so the data recorders remain online.