Configuring LPCT connected to secondary side of conventional CT
I1–I3
- Open ION Setup > select the meter > Setup Assistant.
- Click Metering Setup > Basic tab.
- Set the LPCT and conventional CT primary values:
- Select PM1 CT Prim > Edit. The LVCS Configuration Setup dialog box opens.
- Enter the LPCT primary value.
- Click OK.
- Select the Conventional CT check box.
- Enter the conventional CT primary value. The calculated PM1 CT Prim value is displayed.
- Click OK.
- Set the LPCT and conventional CT secondary values:
- Select PM1 CT Sec > Edit. The LVCS Configuration Setup dialog box opens.
- Enter the LPCT secondary value.
- Click OK.
- Select the Conventional CT check box.
- Enter the conventional CT secondary value. The calculated PM1 CT Sec ratio is displayed.
- Click OK.
I4, I5
Configure these settings in Metering Setup > Advanced tab.