7EN02-0390-03

Configuring your meter as a Modbus slave using the display

You can use the display to configure your meter as a Modbus slave.
  1. Press the Home button.
  2. Navigate to Setup Menu > Communications Setup, scroll and select COM1 or COM4Setup.
  3. Configure the serial port’s Modbus parameters as required.
    Parameter Setting

    Protocol

    Modbus RTU or Modbus Master

    RS485 Bias

    • OFF if the meter is a Modbus slave
    • ON if the meter is a Modbus master
  4. Configure the meter’s other serial port parameters as required.

    For Modbus mastering, you must add the Modbus slave devices using ION Setup.

See your device’s Modbus map, available from www.schneider-electric.com for Modbus register information.

Related topics

See “Setting up your meter using the display” on page 34 for instructions on display menu navigation.