Configuring serial communications settings using ION Setup

Use ION Setup to configure the meter’s serial communications settings.

Before configuring serial parameters, make sure you have a unique unit ID for your meter and know the serial network settings (protocol, baud rate, parity and stop bits).

  1. Start ION Setup.
  2. Open the Setup Assistant for your device.
  3. Select Communications > Serial Settings.
  4. Select Com1 or Com4 tab, depending on which hardware serial port you are configuring.
  5. Select a setting and then click Edit to configure the setting to match your communications system.

    Serial communications settings available using ION Setup

    Parameter Values Description
    Protocol ION, Modbus RTU, Modbus Master, DNP v3.00, DLMS, EtherGate, GPS: Truetime/Datum, GPS: Arbiter, GPS: Arbiter-Vorne, Factory, None Sets the communications protocol for your meter’s RS-485 port
    NOTE: the none setting stops communications using this port.
    Baud Rate 2400, 4800, 9600, 19200, 38400, 57600, 115200 Sets the data rate, in bits per second
    Rx Timeout 0.1-15 Sets the transmit delay (timeout for receiving an entire message from a device) in seconds1
    Unit ID 1 to 9999

    Sets the meter’s unique ID on the RS-485 network

    NOTE: Modbus serial device range 1 to 247
    Serial Port 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 Sets the parity and stop bits for the port
    RS485 Bias Off, On Turns on biasing when mastering devices over the RS-485 port
    1 Only applies to a subset of protocols