Configuring data logging using ION Setup

Use ION Setup to configure the meter’s data recorders.

Changing the meter’s data recorder configuration clears existing data in that data recorder.

NOTICE
Data Loss
Ensure that all important data has been recorded before configuring data recording.
Failure to follow these instructions can result in data loss.

The steps below apply to data recorders: Load Profile, EgyDmd Log, Harm High Log, Harm Mean Log, Hist High Log, Hist Low Log, Hist Mean Log, Loss Log, Sag/Swell Log, DailyNom Log,

NOTE: The Sg/Sw Buffer Log uses a wizard.

NOTE: EN50160 Logs and IEC 4-30 Logs and System Resources — the amount of memory used by system resources in the meter) are read-only and cannot be configured using Setup Assistant.

  1. Start ION Setup.
  2. Open the Setup Assistant for your meter.
  3. Navigate to Logging > Memory.
  4. In the Status tab, select the data log and click Edit.
    The Log Depth Setup window appears.
  5. Configure the settings as applicable:
    Parameter Description
    Log Interval How frequently records are logged
    Log Depth Maximum number of records stored in the log
    Log Memory Information only. This is automatically calculated, and displays how much memory the log uses based on the Log Interval and Log Depth
    Log Storage Information only. This is automatically calculated, and displays how much total memory is left after subtracting the Log Memory usage