Power/Ground Modules, Ground Cords

Schneider Electric offers 208 V or 240 V modules designed to complete the control circuit of a controlled power panel.

Class 4800 / Refer to Catalog 4800CT2001

Power and Ground Modules

4 Red Duplex Receptacles and 4 Ground Jacks


4 Red Duplex Receptacles and 4 Ground Jacks


Power Modules: When both ground jacks and power receptacles are required, these UL Listed modules offer convenience and save labor in field wiring. The units include four power receptacles, four twist-to-lock ground jacks, and a ground bus with a generous number of lugs for external ground connections. The main ground connection in the module accommodates up to a #1/0 cable. The units are completely factory wired; only field power connections and ground connections are necessary. They are furnished with Type 304, brushed stainless steel face plates.

Multiple Mounting options for the product:
(1) backbox 12 x 8 x 4
(2) Bottom of Standard or Duplex Isolation Power System
(3) Standard Gang Box supplied by customer

Power Modules

Catalog Number Hospital Grade Ground Jacks Power Receptacles Mounting

SGPMF4DR4

(4) 30 A, 250 V, Green (4) 20 A, Duplex Red Backbox SB120804

SGPMF4DI4

(4) 20 A, Duplex Ivory

SGPMF4TB4

(4) 20 A, Single Twist Lock

SGPMF4SR4

(4) 20 A, Single Red

SGPMF4SI4

(4) 20 A, Single Ivory

SGPMP4DR4

(4) 20 A, Duplex Red Duplex or Standard Isolation Power System[1]

SGPMP4DI4

(4) 20 A, Duplex Ivory

SGPMP4TB4

(4) 20 A, Single Twist Lock

SGPMP4SR4

(4) 20 A, Single Red

SGPMP4SI4

(4) 20 A, Single Ivory

SGPMG4DR4

(4) 20 A, Duplex Red Customer supplied eight gang box

SGPMG4DI4

(4) 20 A, Duplex Ivory

SGPMG4TB4

(4) 20 A, Single Twist Lock

SGPMG4SR4

(4) 20 A, Single Red

SGPMG4SI4

(4) 20 A, Single Ivory









Master Ground Station: These modules can be used as a collection point for grounds in a large area, such as a coronary care unit or intensive care ward. The primary application is where the equipment ground bus in the isolated power panel is not conveniently located or cannot accept the large number of connections required for the area. This unit can be connected to the ground point by a single conductor and located in a more convenient area. The module contains a bus bar with 18 lugs for field connections and has a Type #304 brushed stainless steel cover plate. It is designed for installation into a 12 in. x 8 in. x 4 in. back box.

4 Ground Jacks


4 Ground Jacks

Master Ground Station – Ground Modules

Catalog Number Description Mounting

SGPMF0NN0

Master ground station, ******** Backbox SB120804

SGPMF2NN0

(2) 30 A, 250 V, Green Hospital Grade ground jacks

SGPMF4NN0

(4) 30 A, 250 V, Green Hospital Grade ground jacks

SGPMP2NN0

(2) 30 A, 250 V, Green Hospital Grade ground jacks Duplex or Standard Isolation Power System

SGPMP4NN0

(4) 30 A, 250 V, Green Hospital Grade ground jacks

SGPMG0NN0

Master ground station, ********  

SGPMG2NN0

(2) 30 A, 250 V, Green Hospital Grade ground jacks Customer supplied two Gang Box

SGPMG4NN0

(4) 30 A, 250 V, Green Hospital Grade ground jacks Customer supplied four Gang Box

Hospital Ground Cords and Jacks

Ground Jack


Ground Cord with Lug End


Ground Cord with Clip End

  • Highly flexible wire with a heavy-duty lug or clip end

  • Ground cord with lug end is UL Listed (UL 467)

  • Various lengths available

Catalog Number Description

SHGC15L

15 foot, with plug and lug for #10 stud

SHGC15C

15 foot, with plug and heavy duty clip

SHGC12L

12 foot, with plug and lug for #10 stud

SHGC12C

12 foot, with plug and heavy duty clip

SHGC10L

10 foot, with plug and lug for #10 stud

SHGC10C

10 foot, with plug and heavy duty clip

SHGJ1R

Hospital grade ground jack, 30 A, 250 V green

Receptacle Modules for Controlled Panels

X-ray/laser power receptacle modules provide a convenient source of power for portable X-ray and laser equipment. The receptacle provided in each module is matched to the NEMA plug configuration of the equipment with which it will be used and is mounted behind the door on the stainless steel face plate. The door features a concealed hinge and a touch latch.

Optional “IN USE LIGHT” – used with Control Panel to inform customer that power is not available at this Laser Module – it is IN USE AT ANOTHER LOCATION.

Fault Locator System

The fault locator system works with the Line Isolation Monitor to identify the branch circuit with high leakage current.

The fault locator system kit is designed to be mounted in pre-punched holes on the interior. The kit includes:

  • Overcurrent protection

  • One fault locator module

  • Jumper wire with quick connects

  • Two control transformer (CT) strips.

A locator module monitors 12 circuits:

  • One module—monitors circuit 1–12 and aligns with panel numbers

The jumper wire includes quick connects to allow modules to be programmed from the factory to align CT strips with the LEDs on the face of the unit.

Part Number Description Interiors

EDS441LNAKIT1

Insulation fault locator kit
to monitor 12 branch circuits
All standard / duplex interiors
LV side of dual voltage interiors

EDS441LNAKIT2

Insulation fault locator kit
to monitor 16 branch circuits
All standard / duplex interiors
LV side of dual voltage interiors

Annunciator Panel (Nurse Station—Remotes)

IG2000P remote indicators are available in an annunciator panel for monitoring from a single central location. Available in combinations of 1–16 devices as standard. Special quantity requests can be obtained from the factory.

Back box SB120804 Back box SB121204 Back Box SB121604
Catalog Number QTY IG2000P Catalog Number QTY IG2000P Catalog Number QTY IG2000P

SRAS2F

2

SRAS9F

9

SRAS13F

13

SRAS3F

3

SRAS10F

10

SRAS14F

14

SRAS4F

4

SRAS11F

11

SRAS15F

15

SRAS5F

5

SRAS12F

12

SRAS16F

16

SRAS6F

6

SRAS7F

7

SRAS8F

8
   

Kits

Seismic Kit

The Schneider Electric Medical Panels, Standard Isolation Panels, Dual Isolation Panels, have been qualified to the seismic limits with the installation of special hardware for trim installation and use of bolt on breakers

Catalog Number Description

4800S10200015

Trim hardware to replace hardware shipped with device.
OSP label for where required

Replacement Parts / Kits

Catalog Number Description

4800S10200000

Transformer Mounting hardware and isolation pads

4800S10200002

Mounting hardware, Power and Ground Modules

4800S10200004

Mounting hardware, Power and Ground Modules

4800S10200009

Mounting hardware Fault locator system

4800S10200306

Mounting hardware Isolation Power System Trim

4800S10200705

Line Isolation Monitor – rear mounted hardware

4800KEY

Replacement KEY for Isolation Power System

4800IG6BKTVM

Mounting bracket to mount IG6M in Square D branded Isolation Power Systems

4800IG6C

Line Isolation Monitor connector cord and terminal block

4800IG6CBKTVM

4800IG6C and 4800IG6BKTVM shipped together

Ground Kit options

Description Catalog Number
Installed in every Isolation Panel System Accepting AL/CU wire

PK23GTA

Q1100AN

Field installable Copper Ground Kit

PK27GTACU

Field installable Chicago Code Ground Bus Copper

4800B521301722

Footnotes

  1. Must have TRIM with Removal blank plate for field accessories example: ST8238R.