Electrical characteristics

True RMS 4–quadrant metering up to the 63rd harmonic on three-phase systems, 256 samples per cycle.

Measurement accuracy

Active energy (Wh)

IEC 62053-22 Class 0.2 S

Reactive energy (VARh)

IEC 62053-24 Class 0.5 S

Power monitoring device (PMD)

IEC 61557-12 PMD/SD/K70/0.2 and PMD/SS/K70/0.2

Active power (P)

IEC 61557-12 Class 0.2

Reactive power (QV)

IEC 61557-12 Class 1

Apparent power (SV)

IEC 61557-12 Class 0.2

Apparent energy (EapV)

IEC 61557-12 Class 0.2

Current (I)

IEC 61557-12 Class 0.2

Voltage (U)

IEC 61557-12 Class 0.2

Frequency (f)

IEC 61557-12 Class 0.02

NOTE: Reactive energy and demand values, by default, are based only on the fundamental frequency, and do not include higher harmonics. Active and apparent energy and demand values are measured using the entire signal including harmonics. Contact Technical Support for more information.

Power quality

Power quality instrument (PQI)

IEC 62586-2 PQI-S

IEC 61000-4-30 Class S (Udin = 230 V)

Confirm if the ION7400/PM8000 is compliant to 4–15 as is the ION9000.

IEC 61000–4–15 Class F1 (Udin = 230 V / 50 Hz, 120 V / 60 Hz)

Voltage unbalance (Unb)

IEC 61557-12 Class 0.2

Voltage harmonics (Uh)

IEC 61557-12 Class 1

Voltage THD (THDu)

IEC 61557-12 Class 1

Current harmonics (Ih)

IEC 61557-12 Class 1

Current THD (THDi)

IEC 61557-12 Class 1

Waveform capture

16–256 cycles per sample

Voltage inputs

Specified accuracy range 57 to 400 V L-N / 100 to 690 V L-L (Wye) or 100 to 600 V L-L (Delta)
Specified accuracy frequency 50/60 Hz ± 15%
Overload 600 V L-N or 1035 V L-L
Impedance > 5 MΩ
Measurement category III

Current inputs

Specified accuracy current range

50 mA–10 A

Withstand

20 A continuous, 50 A @ 10 sec/hr, 500 A @ 1 sec/hr

Impedance 0.3 mΩ (typical)
Burden 0.01 VA max at 5 A

Control power

AC control power
Operating range

50/60 Hz ± 10%: 90–415 V ± 10%

400 Hz: 90–120 V ± 10%

Burden (meter only)

max: 7.2 W/18 VA @ 415 V (45–65 Hz)

max: 4.5 W/8 VA @ 120 V (400 Hz)

Burden (fully optioned meter)

max: 18 W/36 VA @ 415 V (45–65 Hz)

The frequency range above (45 — 65 Hz) is consistent with the ION7400 and PM8000 install sheets.

max. 18 W/28 VA @ 120 V (400 Hz)

Ride-through time (no optional accessories)

100 ms (6 cycles at 60 Hz) min., any condition

200 ms (12 cycles at 60 Hz) typ., 120V AC

500 ms (30 cycles at 60 Hz) typ., 415 V AC

DC control power
Operating range

110–415 V DC ± 15%

Burden (meter only)

max. 6 W at 300 V DC

Burden (fully optioned meter)

17 W at 300 V DC

Ride-through time 100 ms (6 cycles at 60 Hz) min., any condition

Low-voltage DC control power

DC control power
Operating range

20–60 V DC ± 10%

Burden (fully optioned meter)

max: 17 W at 18–60 V DC

Digital output (Form A)

Number

1

Type Form A solid-state
Maximum load voltage 30 V AC/60 V DC
Maximum load current 75 mA
ON resistance 13–40 Ω at 25 °C (77 °F)
Signal type Continuous or pulse
Pulse frequency ≤ 25 Hz

Digital inputs

Number

3

Type

Externally excited, polarity independent

Event timestamp accuracy ± 1 ms
Not convinced that this spec should be here. Seems too firmware ish for the specs section
Maximum voltage 30 V AC/60 V DC
Pulse frequency ≤ 25 Hz
Response time

20 ms

Minimum pulse width 20 ms
Current draw

ON: ≤ 2.5 mA

OFF: ≤ 0.5 mA

Voltage ON state 4–30 V AC/4–60 V DC
Voltage OFF state 0–1.4 V AC/0–2.0 V DC
IRIG-B IRIG-B00x format (unmodulated IRIG-B time code)

Coded expressions 0 to 7 are supported but the year data is not used.