7EN02-0336-07

Input/output ION modules, ports and labels

You can configure the Digital Output, Digital Input, Analog Input, Analog Output, Pulser and Calibration Pulser ION modules to specify which port handles the outgoing or incoming signals.

To assign a port to one of these modules, modify the Port setup register by picking a port from the enumerated list.

NOTE: If the port you want to use does not appear in the Port setup register list, that port is in use by another module. Edit the Port setup register of the module using that port and set it to Not Used. The port is then available to other modules.

Factory configured settings

Onboard input and output ports

ION module type ION module name Hardware port (device label) Port name (ION label) Description
Digital Output Port D1 D1 Port D1 Form A output
Calibration Pulser MU WhPulser LED N/A Top LED Watt energy pulsing

(located on meter body)

Digital Input Port S1 S1 Port S1 Externally excited
Digital Input Port S2 S2 Port S2 Externally excited
Digital Input Port S3 S3 Port S3 Externally excited

Option module(s) input and output ports

ION module type ION module name Hardware port (device label) Port setup register name Description
Digital Input Port A/B/C/D S1–S6 S1–S6

Port A S1–S6

Port B S1–S6

Port C S1–S6

Port D S1–S6

Option module digital inputs
Digital Output Port A/B/C/D D1–D2 Relay 1–Relay 2

Port A D1–D2

Port B D1–D2

Port C D1–D2

Port D D1–D2

Option module digital output
Analog Input Port A/B/C/D A1–A4 A1–A4

Port A A1–A4

Port B A1–A4

Port C A1–A4

Port D A1–A4

Option module analog input
Analog Output Port A/B/C/D Q1–Q2 Q1–Q2

Port A Q1–Q2

Port B Q1–Q2

Port C Q1–Q2

Port D Q1–Q2

Option module analog output
NOTE: When configuring your meter, the configuration interface may show all of the possible ports, regardless of what is physically available on your meter.

See the ION Reference, available from www.se.com for more information about ION modules.