H-Frame and J-Frame MCP Selector

Class 611 / Refer to Catalog 0611CT1001

H-, J-Frame Motor Circuit Protectors

Application of PowerPact™ H-Frame and J-Frame Electronic Motor Circuit Protectors (MCP)

Horsepower Rating of Induction-Type Squirrel-Cage and Wound-Rotor Motors 3Ø 60 Hz

NEC Full Load Amperes

PowerPact H-Frame and
J-Frame Electronic MCP

Starter Size

200 Vac

230 Vac

480 Vac

575 Vac

00

     

1/2

0.9 A

HJL36030M71

and

HLL36030M71

1/2–10 hp

 
   

1/2

 

1.1 A

     

3/4

1.3 A

   

3/4

1

1.7 A

   

1

 

2.1 A

 

1/2

   

2.2 A

     

1-1/2

2.4 A

1/2

     

2.5 A

     

2

2.7 A

   

1-1/2

 

3 A

 

3/4

   

3.2 A

   

2

 

3.4 A

3/4

     

3.7 A

     

3

3.9 A

 

1

   

4.2 A

1

     

4.8 A

   

3

 

4.8 A

 

1-1/2

   

6 A

     

5

6.1 A

 

2

   

6.8 A

1-1/2

     

6.9 A

0

   

5

 

7.6 A

2

     

7.8 A

     

7-1/2

9 A

 

3

   

9.6 A

3

 

7-1/2

10

11 A

1

   

10

 

14 A

HJL36050M72

and

HLL36050M72

10–25 hp

 

5

   

15.2 A

     

15

17 A

5

     

17.5 A

   

15

 

21 A

 

7-1/2

 

20

22 A

7-1/2

     

25.3 A

2

   

20

25

27 A

 
 

10

   

28 A

     

30

32 A

HJL36100M73

and

HLL36100M73

15–50 hp

10

     

32.2 A

3

   

25

 

34 A

   

30

 

40 A

     

40

41 A

 

15

   

42 A

15

     

48.3 A

 
   

40

50

52 A

 

20

   

54 A

20

   

60

62 A

HJL36150M74

and

HLL36150M74

30–100 hp

   

50

 

65 A

 

25

   

68 A

   

60

75

77 A

25

     

78.2 A

4

 

30

   

80 A

30

     

92 A

 
   

75

 

96 A

     

100

99 A

 

40

   

104 A

40

     

120 A

JJL36250M75

and

JLL36250M75

50–150 hp

     

100

 

124 A

5

     

125

125 A

 

50

   

130 A

     

150

144 A

 

50

     

150 A

 

60

   

154 A

   

125

 

156 A

60

     

177.1 A

   

150

 

180 A

 

75

 

200

192 A

75

 

221 A

 
   

200

 

240 A

   

100

   

248 A

Shaded area is not covered by J-frame electronic motor circuit protector.

Was this helpful?