0611CT1603

Insulation of Connectors

The table below indicates the connection requirements for PowerPact B-frame devices to ensure insulation of live parts for the various types of connectors.

Connection accessories such as spreaders, PDC lugs, and some compression lugs are supplied with interphase barriers. Long terminal shields provide IP40 degree of protection.

PowerPact B-Frame Circuit Breakers: Insulation of Live Parts

 

EverLink Connector With or Without Control Wire Terminal

Mechanical Lug Connector

Terminal Nut Connectors

Insulation accessory options per conductor type

Type of conductor

No insulating accessory

Interphase barriers

Long terminal shield

No insulating accessory

Interphase barriers

Long terminal shield

No insulating accessory

Interphase barriers

Long terminal shield

Cables

 

Possible

Possible

Possible

Possible

Insulated Bars

Possible

Possible

Possible

Cables + Compression Lugs

Forbidden

Mandatory

Possible*

Cables + Compression Lugs with Heat-Shrink Sheath

Possible

Possible

Possible

Spreader Kits

Forbidden

Mandatory

Cables + Power Distribution Connector

Forbidden

Mandatory

Possible*