0611CT1603

Insulation of Live Parts

For two, three, or four pole products, accessories are available to ensure insulation and IP rating:

  • Long terminal shields (IP40)

  • Interphase barriers

  • Rear insulation screen.

Long Terminal Shields (IP40)

Products can be equipped with long terminal shields. They can be mounted upstream and downstream and are used for protection against direct contact with power circuits. They provide IP40 degree of protection and IK07 mechanical impact protection. The long terminal shield can be mounted after product installation on a plate or DIN rail, and can be removed and put in place even if there are auxiliary wires installed. They are not compatible with EverLink connectors.

They are used for connection with cables or insulated bars.

They are comprised of two parts assembled with two locks and captive screws, forming an IP40 cover.

  • The top part is transparent to show the connection and is equipped with sliding grids with break marks for precise adaptation to cables or insulated bars.

  • The rear part completely blocks off the connection zone. Partially cut squares can be removed to adapt to all types of connection for cables with lugs or copper bars.

Interphase Barriers

Interphase barriers provide phase to phase isolation at the power-connection points:

  • They clip easily onto the circuit breaker.

  • They are not compatible with long terminal shields or EverLink connectors.

  • There are two ways of mounting: short / long insulation.