Thermographic Inspection
DANGER |
---|
Hazard of electric shock, explosion, or arc flash
Failure to follow these instructions will result in death or serious injury.
|
Infrared thermographic inspection techniques may
be useful in evaluating the operating condition of circuit breakers
and terminations. Comparison to stored infrared thermographic images
may be useful for the preventative maintenance of circuit breakers
and end-use equipment. The actual amount of heat emitted is a function
of both load current and ambient conditions. Interpretation of infrared
images requires experience and training in this type of inspection.
Allow initially energized circuit breakers at least three hours to reach operating temperature. Compare the thermographic images of individual circuit breakers to previously stored images of the same circuit breakers.
Additional Information |
For more information concerning Square D™ circuit breakers, refer to the appropriate instruction manual. These manuals contain installation instructions, mounting information, safety features, wiring diagrams, and troubleshooting charts for specific circuit breakers. |