Configuring ION Setup
- Click ION Setup shortcut on your desktop (or click , point to the folder that contains ION Setup , then select ION Setup ).
- Right-click on the computer icon and select Insert Item.
- Select Site and click OK.
The New Site window displays.
To configure the new site, you need to identify the serial port to which the device is connected. Perform the following steps:
- Connect the USB to RS485 serail adapter to the device.
- Connect the adapter to the USB port of the computer.
- Power ON the device.
- Open the Device Manager and identify the serial port to which the device is connected.
- Configure the site settings with the following values:
Option Description Name Enter the name as required. Comm Link Select Serial. Comm Port Select the serial port to which the device is connected. See Device Manager. Port Settings Select 19200 Baud and 8E1 Format. - Click OK.The site is created.
- Right-click on the created site and select Insert Item.
- Select Device and click OK.
The New Device window displays.
- Configure the device settings with the following values:
Option Description Name Enter the name as required. Type -
Select Vigilohm IMD Insulation Monitoring Device for IMD devices.
-
Select Vigilohm IFL Insulation Fault Locator for IFL devices.
Unit ID Enter the Modbus ID of the device. To view your device Modbus ID, navigate to .Group Enter the group name as required. -
- Click OK.The device is created under the site.