NEC 210.19 Conductors–Minimum Ampacity and Size
Branch Circuits Not More Than 600 Volts
General. Branch-circuit conductors shall have an ampacity not less than the maximum load to be served. Conductors shall be sized to carry not less than the larger of 210.19(A)(1)(a) or (b).
For branch circuits not more than 600 volts, conductors shall have an ampacity not less than the maximum load to be served. Conductors shall be sized to carry not less than the larger of (a) or (b).
The conductor ampacity may require other correction or adjustment factors applicable to the conductor installation.
a. | Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum branch-circuit conductor size shall have an allowable ampacity not less than the noncontinuous load plus 125% of the continuous load. |
b. | The minimum branch-circuit conductor size shall have an allowable ampacity not less than the maximum load to be served after the application of any adjustment or correction factors. |
Exception: If the assembly, including the overcurrent devices protecting
branch
circuit(s), is listed for operation at 100%
of its rating, the allowable ampacity of the branch-circuit conductors
shall be permitted to be not less than the sum of the continuous load
plus the noncontinuous load.