Single-Phase Dwelling Services and Feeders
Section 310.15(B)(7)
For one-family dwellings and the individual dwelling units of two family and multifamily dwellings, service and feeder conductors supplied by a single-phase, 120/240 volt system shall be permitted to be sized in accordance with 310.15(B)(7)(1) through (4).
For one-family dwellings and the individual dwelling units of two-family and multifamily dwellings, single-phase feeder conductors consisting of 2 ungrounded conductors and the neutral conductor from a 208Y/120 volt system shall be permitted to be sized in accordance with 310.15(B)(7)(1) through (3).
-
For a service rated 100 through 400 amperes, the service conductors supplying the entire load associated with a one-family dwelling, or the service conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling, shall be permitted to have an ampacity not less than 83 percent of the service rating.
-
For a feeder rated 100 through 400 amperes, the feeder conductors supplying the entire load associated with a one-family dwelling, or the feeder conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling, shall be permitted to have an ampacity not less than 83 percent of the feeder rating.
-
In no case shall a feeder for an individual dwelling unit be required to have an ampacity greater than that specified in NEC 310.15(B)(7)(1) or (2).
-
Grounded conductors shall be permitted to be sized smaller than the ungrounded conductors, if the requirements of 220.61 and 230.42 for service conductors or the requirements of 215.2 and 220.61 for feeder conductors are met.