Specifications
Input Specifications
UPS rating | 250 kVA | 300 kVA | 400 kVA | ||||||
---|---|---|---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
Connections | L1, L2, L3, N, PE | ||||||||
Input voltage range (V) | 323-477 (full load) | ||||||||
Frequency range (Hz) | 40-70 | ||||||||
Nominal input current (A) | 404 | 384 | 370 | 485 | 461 | 444 | 647 | 614 | 592 |
Maximum input current (A) |
474 |
451 |
434 |
568 |
540 |
520 |
757 |
719 |
693 |
Input current limitation (A) | 600 | 720 | 960 | ||||||
Total harmonic distortion (THDI) | <3% for linear loads <5% for non-linear loads |
||||||||
Input power factor | >0.99 | ||||||||
Maximum short circuit rating | Icc=35 kA | ||||||||
Ramp-in | 7 seconds |
Bypass Specifications
UPS rating | 250 kVA | 300 kVA | 400 kVA | ||||||
---|---|---|---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
Connections | L1, L2, L3, N, PE | ||||||||
Overload capacity | ≤115% continuous 125% for 10 minutes 150% for 1 minute |
||||||||
Minimum bypass voltage (V) | 209 | 221 | 228 | 209 | 221 | 228 | 209 | 221 | 228 |
Maximum bypass voltage (V) | 475 | 480 | 477 | 475 | 480 | 477 | 475 | 480 | 477 |
Frequency (Hz) | 50 or 60 | ||||||||
Frequency range (%) | ±1, ±2, ±4, ±5, ±10. Default is ±10 (user selectable). | ||||||||
Nominal bypass current (A) |
384 |
364 |
351 |
460 |
437 |
422 |
614 |
583 |
562 |
Maximum short circuit rating | Icc=35 kA |
Output Specifications
UPS rating | 250 kVA | 300 kVA | 400 kVA | ||||||
---|---|---|---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
Connections | L1, L2, L3, N, PE | ||||||||
Overload capacity* | 105% continuous 125% for 10 minutes 150% for 1 minute |
||||||||
Output voltage regulation | ±1% | ||||||||
Dynamic load response | 20 milliseconds | ||||||||
Output power factor | 1 | ||||||||
Nominal output current (A) |
380 |
361 |
348 |
456 |
433 |
417 |
608 |
577 |
556 |
Total harmonic distortion (THDU) | <2% at 100% linear load <4% at 100% non-linear load |
||||||||
Output frequency (Hz) | 50 or 60 | ||||||||
Slew rate (Hz/sec) | Programmable: 0.5 to 2.0 Default is 0.5 |
||||||||
Output performance classification (according to IEC/ EN62040-3) | VFI-SS-111 | ||||||||
Load power factor | 0.5 leading to 0.5 lagging without derating | ||||||||
Output short circuit current (inverter) | 630 A/200 ms | 820 A/200 ms | 1000 A/200 ms |
Battery Specifications
UPS rating | 250 kVA | 300 kVA | 400 kVA |
---|---|---|---|
Max. charging power in % of output power | 24 | ||
Maximum charging power (kW) | 60 | 72 | 96 |
Nominal battery voltage (VDC) | ±216 to ±300 | ||
Nominal float voltage (VDC) | ±243 to ±337.5 | ||
End of discharge voltage (full load) (VDC) | ±172.8 to ±240 | ||
Battery current at full load and nominal battery voltage (A) |
615-443 |
738-531 |
985-709 |
Battery current at full load and minimum battery voltage (A) |
769-554 |
923-664 |
1231-886 |
Temperature compensation (per cell)* | Programmable from 0 to 7 mV/°C. Default is 0 mV/°C. | ||
Ripple current | <5% C10 |
Recommended Upstream Protection
UPS rating | 250 kVA | 300 kVA | 400 kVA | |||
---|---|---|---|---|---|---|
Input | Bypass | Input | Bypass | Input | Bypass | |
Breaker type | NSX630F Mic 2.3 (LV432877) | NSX630F Mic 2.3 (LV432877) | NS630bN Mic 2.0 (33463/NS33463) | NS630bN Mic 2.0 (33463/NS33463) | NS800N Mic 2.0 (33469/NS33469) | NS800N Mic 2.0 (33469/NS33469) |
In setting | Io=500 | Io=500 | 1 | 1 | 1 | 1 |
Ir setting | 0.95 | 0.9 | 0.9 | 0.9 | 0.95 | 0.9 |
Im setting | Isd=1.5-10 | Isd=1.5-10 | Isd=1.5-10 | Isd=1.5-10 | Isd=1.5-10 | Isd=1.5-10 |
Recommended Cables Sizes
DANGER |
---|
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or
electrical codes. the maximum allowable cable size is 240 mm².
Failure to follow these instructions will result in death or serious injury.
|
Cable sizes in this manual are based on table A.52-5 of IEC 60364-5-52 with the following assertions:
-
90 °C conductors
-
An ambient temperature of 30 °C
-
Use of copper conductors
-
Installation method C
PE size is based on table 54.3 of IEC 60364-5-54.
If the ambient temperature is greater than 30 °C, larger conductors are to be used in accordance with the correction factors of the IEC.
250 kVA UPS
Cable size per phase (mm2) | Neutral cable size (mm2) | PE cable size (mm2)) | |
---|---|---|---|
Input | 2 x 120 | 2 x 120 | 120 |
Bypass | 2 x 120 | 2 x 120 | 120 |
Output | 2 x 120 | 2 x 120 | 120 |
Battery | 2 x 185 | 2 x 185 | 185 |
300 kVA UPS
Cable size per phase (mm2) | Neutral cable size (mm2) | PE cable size (mm2)) | |
---|---|---|---|
Input | 2 x 150 | 2 x 150 | 150 |
Bypass | 2 x 150 | 2 x 150 | 150 |
Output | 2 x 150 | 2 x 150 | 150 |
Battery | 2 x 240 | 2 x 240 | 240 |
400 kVA UPS
Cable size per phase (mm2) | Neutral cable size (mm2) | PE cable size (mm2)) | |
---|---|---|---|
Input | 2 x 240 | 2 x 240 | 240 |
Bypass | 2 x 240 | 2 x 240 | 240 |
Output | 2 x 240 | 2 x 240 | 240 |
Battery | 4 x 150 | 4 x 150 | 2 x 150 |
Recommended Bolts and Cable Lugs
Cable Size (mm²) | Bolt Size | Cable Lug Type |
---|---|---|
120 | M12x35 mm | TLK 120-12 |
150 | M12x35 mm | TLK 150-12 |
185 | M12x35 mm | TLK 185-12 |
240 | M12x35 mm | TLK 240-12 |
Torque Specifications
Bolt Size | Torque |
---|---|
M12 | 50 Nm |
Requirements for a Third Party Battery Solution
Battery breaker boxes from Schneider Electric are recommended for the battery interface. Please contact Schneider Electric for more information.
Third Party Battery Breaker Requirements
DANGER |
---|
Hazard of electric shock, explosion, or arc flash
All selected battery breakers must be equipped with instantaneous
trip functionality with an undervoltage release coil or a shunt trip
release coil.
Failure to follow these instructions will result in death or serious injury.
|
Design Requirements for Battery Breaker
Battery breaker rated DC voltage > Normal battery voltage | the normal voltage of the battery configuration is defined as the highest nominal occurring battery voltage. This can be equivalent to the float voltage which may be defined as number of battery blocks x number of cells x cell float voltage. |
Battery breaker rated DC current > Rated discharge battery current | This current is controlled by the UPS and must include maximum discharge current. This will typically be the current at the end of discharge (minimum operation DC voltage or in overload condition or a combination). |
DC landings | Three DC landings (+, -, N) for DC cables are required. |
AUX switches for monitoring | One AUX switch must be installed in each battery breaker and connected to the UPS. the UPS can monitor one battery breaker. |
Short-circuit breaking capability | the short-circuit breaking capability must be higher than the short-circuit DC current of the (largest) battery configuration. |
Minimum trip current | the minimum short-circuit current to trip the battery breaker must match the (smallest) battery configuration, to make the breaker trip in case of a short circuit, up to the end of its life time. |
Guidance for Organizing Battery Cables
UPS Weights and Dimensions
UPS rating | Weight kg | Height mm | Width mm | Depth mm |
---|---|---|---|---|
250 kVA | 425 | 1970 | 600 | 850 |
300 kVA | 449 | 1970 | 600 | 850 |
400 kVA | 538 | 1970 | 600 | 850 |
UPS Shipping Weights and Dimensions
UPS rating | Weight kg | Height mm | Width mm | Depth mm |
---|---|---|---|---|
250 kVA | 470 | 2117 | 800 | 1000 |
300 kVA | 503 | 2117 | 800 | 1000 |
400 kVA | 584 | 2117 | 800 | 1000 |
Clearance
Environmental
Operating | Storage | |
---|---|---|
Temperature | 0 °C to 30 °C | -15 °C to 40 °C for systems with batteries -25 °C to 55 °C for systems without batteries |
Relative humidity | 0-95% non-condensing | |
Elevation derating
according to IEC 62040-3 |
Power
derating factor: 0-1500 m: 1.000 1500-2000 m: 0.975 |
< 15000 m above sea level (or in an environment with equivalent air pressure) |
Audible noise | <70 dBA at 100% load according to ISO3746 | |
Protection class | IP20 (air filter as standard) | |
Color | RAL 9003 |
Heat Dissipation
UPS rating | 250 kVA | 300 kVA | 400 kVA | |||
---|---|---|---|---|---|---|
W | BTU/hr | W | BTU/hr | W | BTU/hr | |
Normal mode | 14500 | 49488 | 17400 | 59386 | 23200 | 79181 |
Battery mode | 14000 | 47782 | 16800 | 57338 | 22400 | 76451 |
ECO mode | 2000 | 6826 | 2400 | 8191 | 3200 | 10922 |
Compliance
Safety | IEC 62040-1:2017,
Edition 2.0, Uninterruptible power systems (UPS) – Part 1:
Safety requirements IEC 62040-1: 2008-6, 1st edition, Uninterruptible Power Systems (UPS) – Part 1: General and safety requirements for UPS IEC 62040-1:2013-01, 1st edition amendment 1 |
EMC | IEC 62040-2:2016,
Edition 3.0, Uninterruptible power systems (UPS) – Part 2:
Electromagnetic compatibility (EMC) requirements. IEC 62040-2:2005-10, 2nd edition, Uninterruptible Power Systems (UPS) – Part 2: Electromagnetic compatibility (EMC) requirements |
Performance | IEC 62040-3: 2011-03, 2nd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the performance and test requirements |
Environmental | IEC 62040-4: 2013-04, 1st edition Uninterruptible Power Systems (UPS) - Part 4: Environmental aspects – Requirements and reporting |
Markings |
CE, RCM, EAC, WEEE |
Transportation |
ISTA 2B |
Pollution degree | 2 |
Overvoltage category | III |
Earthing system | TN-S, TN-C, TT, or IT |