Configuring network parameters
- Navigate to .
- Modify the parameters value as per the following table:NOTE: Use the contextual menu buttons to modify the parameters value.
Parameter Allowed Values Default Value Description App THR
THR
THR for medium voltage systems.
Filtering -
2s
-
20s
-
200s
20s
Select the filtering time depending on the application. V.Adapt -
None
-
P1N
P1N
Select the adaptor if the network voltage is greater than the rated network voltage of the device.
-
Select None value for testing the device before installation when P1N is not connected.
-
Select P1N value for during operation when P1N is connected.
Injection -
20V
-
40V
-
60V
-
80V
60V
Select the injection depending on the application.
NOTE: The advised values are 60V or 80V.HRG -
OFF
-
0.1....2 MΩ
OFF
-
Select OFF when no grounding resistance is connected.
-
Select the value of the neutral grounding resistance, which is connected to the device.
Pri.DC Resis 0....50 kΩ
0 kΩ
Select the value of resistance of the compatible Schneider Electric voltage transformer primary winding. No. of Transfo -
0
-
1
-
3
0
Select the value of number of transformer connected. -