7EN72-0185-13

ION 4-30 measurement performance

Measurement uncertainty and measuring range are defined for each power quality parameter based on the class of measurement.

NOTE: ION meters exceed the standard requirements.

Class A measurement performance (Indoor(I), Fixed(F), Udin = 230 VAC) Edition 3

Parameter

Measuring range

Uncertainty

4.6 Clock Uncertainty*

N/A

50 Hz: +/- 20 ms

60 Hz: +/- 16.7 ms

Non-sync: +/- 1 s / 24-h

5.1 Power Frequency

50 Hz: 42.5 to 57.5 Hz

60 Hz: 51 to 69 Hz

+/- 0.01 Hz

5.2 Magnitude of Supply Voltage

10 to 150% of Udin

+/- 0.1% of Udin

5.3 Flicker

0.2 to 10 Pst

5% or 0.05 Pst, whichever is greater

5.4 Supply Voltage Dips & Swells

N/A

Amplitude +/- 0.2% of Udin

Duration +/- 1 cycle

5.5 Voltage Interruptions

N/A

Duration +/- 1 cycle

5.7 Supply Voltage Unbalance

U2 (0.5 to 5)%

U0 (0.5 to 5)%

+/- 0.15%

5.8 Voltage Harmonics

Up to 50th order

10% to 200% of IEC 61000-2-4 Class 3

IEC 61000-4-7 Class 1

Um ≥ 1% Unom: +/- 5% Um

Um < 1% Unom: +/- 0.05% Unom

5.9 Voltage Interharmonics

Up to 50th order

10% to 200% of IEC 61000-2-4 Class 3

IEC 61000-4-7 Class 2

Um ≥ 1% Unom: +/- 5% Um

Um < 1% Unom: +/- 0.05% Unom

5.10 Mains Signaling Voltage

Up to 3 kHz

0 to 15% of Udin

(1 to 3)% Udin: +/- 0.15%

(3 to 15)% Udin: +/- 5%

5.11 Rapid Voltage Changes

N/A

Amplitude +/- 0.2% Udin

Duration +/- 1 cycle

5.12 Underdeviation and Overdeviation

10 to 150% of Udin

+/- 0.1% Udin

5.13.2 Current Magnitude

Specified Crest factor of 3

1% of reading for (10 to 100) % of In

5.13.4 Current Harmonics

Up to 50th order

IEC 61000-4-7 Class 1

Im ≥ 1% Inom: +/- 5% Im

Im < 1% Inom: +/- 0.05% Inom

5.13.5 Current Interharmonics

Up to 50th order

IEC 61000-4-7 Class 1

Im ≥ 3% Inom: +/- 5% Im

Im < 3% Inom: +/- 0.15% Inom

5.13.6 Current Unbalance

I2 (0.5 to 5)%

I0 (0.5 to 5)%

+/- 0.15%

Class S measurement performance (Indoor(I), Fixed(F), Udin = 230 VAC) Edition 3

Parameter

Measuring range

Uncertainty

4.6 Clock Uncertainty

N/A

+/- 5 s / 24-h

5.1 Power Frequency

50 Hz: 42.5 to 57.5 Hz

60 Hz: 51 to 69 Hz

+/- 0.05 Hz

5.2 Magnitude of Supply Voltage

10 to 150% of Udin

+/- 0.5% of Udin

5.3 Flicker*

0.2 to 10 Pst

5% or 0.05 Pst, whichever is greater

5.4 Supply Voltage Dips & Swells

N/A

Amplitude +/- 0.2% of Udin

Duration +/- 1 cycle

5.5 Voltage Interruptions

N/A

Duration +/- 1 cycle

5.7 Supply Voltage Unbalance

U2 (0.5 to 5)%

U0 (0.5 to 5)%

+/- 0.15%

5.8 Voltage Harmonics

Up to 40th order

10% to 100% of IEC 61000-2-4 Class 3

IEC 61000-4-7 Class II

Um ≥ 3% Unom: +/- 5% Um

Um < 3% Unom: +/- 0.15% Unom

5.10 Mains Signaling Voltage*

Up to 3 kHz

0 to 15% of Udin

(1 to 3)% Udin: +/- 0.15%

(3 to 15)% Udin: +/- 5%

5.12 Underdeviation and Overdeviation*

10 to 150% of Udin

+/- 0.5% of Udin

5.13.2 Current Magnitude

Specified Crest factor of 3

2% of reading for (10 to 100) % of In

5.13.4 Current Harmonics

Up to 40th order

IEC 61000-4-7 Class II

Im ≥ 10% Inom: +/- 5% Im

Im < 10% Inom: +/- 0.5% Inom

5.13.6 Current Unbalance

I2 (0.5 to 5)%

I0 (0.5 to 5)%

+/- 0.15%

Class A measurement performance ( Udin = 230 VAC) Edition 1 and 2

Parameter

Range

Accuracy

5.1 Power Frequency

50 Hz: 42.5 to 57.5 Hz

60 Hz: 51 to 69 Hz

+/- 0.01 Hz

5.2 Magnitude of Supply Voltage

1 to 200% of Udin (Edition 1)

10 to 150% of Udin (Edition 2)

+/- 0.1% of Udin

5.3 Flicker

0 to 20 Pst (Edition 1)

0.2 to 10 Pst (Edition 2)

5% of reading

5.4 Supply Voltage Dips & Swells

10 to 200% of Udin

Amplitude +/- 0.2% of Udin

Duration +/- 1 cycle

5.5 Voltage Interruptions

< 10% of Udin

Amplitude +/- 0.2% of Udin

Duration +/- 1 cycle

5.7 Supply Voltage Unbalance

0 to 5%

+/- 0.15%

5.8 Voltage Harmonics

2 times the limit from IEC 61000-2-4 Class 3 up to the 50th harmonic

IEC 61000-4-7 Class I Method Usg,h

5.9 Voltage Interharmonics

2 times the limit from IEC 61000-2-4 Class 3 up to the 50th harmonic

IEC 61000-4-7 Class I Method Usg,h

5.10 Mains Signaling Voltage

Up to 3 kHz

0 to 15% of Udin

1 to 3% of Udin, +/- 0.15% of Udin;

3 to 15% of Udin, +/- 5% of measured value

5.12 Underdeviation and Overdeviation

1 to 200% of Udin (Edition 1)

10 to 150% of Udin (Edition2)

+/- 0.1% of Udin

Class S measurement performance ( Udin = 230 VAC) Edition 2

Parameter

Measuring range

Uncertainty

5.1 Power Frequency

50 Hz: 42.5 to 57.5 Hz

60 Hz: 51 to 69 Hz

+/- 0.05 Hz

5.2 Magnitude of Supply Voltage

10 to 150% of Udin

+/- 0.5% of Udin

5.3 Flicker*

0.2 to 10 Pst

+/- 5% of reading

5.4 Supply Voltage Dips & Swells

10 to 200% of Udin

Amplitude +/- 0.2% of Udin

Duration +/- 1 cycle

5.5 Voltage Interruptions

N/A

Duration +/- 1 cycle

5.7 Supply Voltage Unbalance

U2 (0.5 to 5)%

U0 (0.5 to 5)%

+/- 0.15%

5.8 Voltage Harmonics

10 to 100% the limit from IEC 61000-2-4 Class 3, calculated up to the 40th harmonic

Twice IEC 61000-4-7 Class II

5.10 Mains Signaling Voltage4

0 to 15% of Udin

1 to 3% of Udin, +/- 0.15% of Udin;

3 to 15% of Udin, +/- 5% of measured value

5.12 Underdeviation and Overdeviation4

10 to 150% of Udin

+/- 0.5% of Udin

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.