Group Motor Installations
UL 60947 Group Motor Installations
TeSys™ GV2ME + TeSys Deca Contactors
TeSys GV2ME and TeSys Deca Contactors for Group Motor Installations (UL File E164864)*
Manual Motor Starter |
Overload Trip Range (A) |
Maximum Horsepower Ratings |
SCCR (kA)1 |
||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Single-Phase |
Three-Phase |
Type of Contactor Required |
480 V |
600 Y / 347 V |
480 V with GV1L3 Limiter |
||||||
120 V |
240 V |
208 V |
240 V |
480 V |
600 V |
||||||
0.10–0.16 |
— |
— |
— |
— |
— |
— |
LC1D09 or D12 |
22 |
22 |
65 |
|
0.16–0.25 |
— |
— |
— |
— |
— |
— |
LC1D09 or D12 |
22 |
22 |
65 |
|
0.25–0.40 |
— |
— |
— |
— |
— |
— |
LC1D09 or D12 |
22 |
22 |
65 |
|
0.40–0.63 |
— |
— |
— |
— |
— |
— |
LC1D09 or D12 |
22 |
22 |
65 |
|
0.63–1 |
— |
— |
— |
— |
— |
0.5 |
LC1D09 or D12 |
22 |
22 |
65 |
|
1–1.6 |
— |
1/10 |
— |
— |
0.75 |
0.75 |
LC1D09 or D12 |
22 |
22 |
65 |
|
1.6–2.5 |
— |
1/6 |
0.5 |
0.5 |
1 |
1.5 |
LC1D09 or D12 |
22 |
22 |
65 |
|
2.5–4 |
1/8 |
1/3 |
0.75 |
0.75 |
2 |
3 |
LC1D09 or D12 |
22 |
22 |
65 |
|
4–6.3 |
0.25 |
0.5 |
1 |
1.5 |
3 |
5 |
LC1D09 or D12 |
22 |
22 |
65 |
|
6–10 |
0.5 |
1.5 |
2 |
3 |
5 |
7.5 |
LC1D09 or D12 |
22 |
22 |
65 |
|
9–14 |
0.75 |
2 |
3 |
3 |
10 |
10 |
LC1D12 or D18 |
22 |
10 |
22 |
|
13–18 |
1 |
3 |
5 |
5 |
10 |
15 |
LC1D12 or D18 |
22 |
10 |
22 |
|
17–23 |
1.5 |
3 |
5 |
7.5 |
15 |
20 |
LC1D25 or D32 |
10 |
10 |
10 |
|
20–25 |
2 |
— |
7.5 |
7.5 |
15 |
20 |
LC1D25 or D32 |
10 |
10 |
10 |
|
24–32 |
2 |
5 |
7.5 |
10 |
20 |
25 |
LC1D25 or D32 |
5 |
5 |
5 |
|
NOTE: Ratings
apply to circuit with voltages no greater than those listed.
|
TeSys™ GV2P + TeSys Deca Contactors
TeSys GV2P and TeSys Deca Contactors for Group Motor Installations (UL File E164864)*
Manual Motor Starter |
Overload Trip Range (A) |
Maximum Horsepower Ratings |
SCCR (kA) |
|||||||
---|---|---|---|---|---|---|---|---|---|---|
Single-Phase |
Three-Phase |
Type of Contactor Required |
480 V |
600 Y / 347 V |
||||||
120 V |
240 V |
208 V |
240 V |
480 V |
600 V |
|||||
0.10–0.16 |
— |
— |
— |
— |
— |
— |
LC1D09 or D12 |
22 |
22 |
|
0.16–0.25 |
— |
— |
— |
— |
— |
— |
LC1D09 or D12 |
22 |
22 |
|
0.25–0.40 |
— |
— |
— |
— |
— |
— |
LC1D09 or D12 |
22 |
22 |
|
0.40–0.63 |
— |
— |
— |
— |
— |
— |
LC1D09 or D12 |
22 |
22 |
|
0.63–1 |
— |
— |
— |
— |
— |
0.5 |
LC1D09 or D12 |
22 |
22 |
|
1–1.6 |
— |
1/10 |
— |
— |
0.75 |
0.75 |
LC1D09 or D12 |
22 |
22 |
|
1.6–2.5 |
— |
1/6 |
0.5 |
0.5 |
1 |
1.5 |
LC1D09 or D12 |
22 |
22 |
|
2.5–4 |
1/8 |
1/3 |
0.75 |
0.75 |
2 |
3 |
LC1D09 or D12 |
22 |
22 |
|
4–6.3 |
0.25 |
0.5 |
1 |
1.5 |
3 |
5 |
LC1D09 or D12 |
22 |
22 |
|
6–10 |
0.5 |
1.5 |
2 |
3 |
5 |
7.5 |
LC1D09 or D12 |
22 |
22 |
|
9–14 |
0.75 |
2 |
3 |
3 |
10 |
10 |
LC1D12 or D18 |
22 |
18 |
|
13–18 |
1 |
3 |
5 |
5 |
10 |
15 |
LC1D12 or D18 |
22 |
18 |
|
17–23 |
1.5 |
3 |
5 |
7.5 |
15 |
20 |
LC1D25 or D32 |
22 |
18 |
|
20–25 |
2 |
— |
7.5 |
7.5 |
15 |
20 |
LC1D25 or D32 |
22 |
18 |
|
NOTE: Ratings apply to circuit with voltages
no greater than those listed.
|
TeSys™ GV3P + TeSys Deca Contactors
TeSys GV3P and TeSys Deca Contactors for Group Motor Installations*
Manual Motor Starter |
Overload Trip Range (A) |
Maximum Horsepower Ratings |
Type of Contactor Required |
SCCR (kA) |
||||||
---|---|---|---|---|---|---|---|---|---|---|
Single-Phase |
Three-Phase |
480 Y / 277 V |
600 Y / 347 V |
|||||||
120 V |
240 V |
208 V |
240 V |
480 V |
600 V |
|||||
9–13 |
0.5 |
1.5 |
3 |
3 |
7.5 |
10 |
LC1D18, D25, D32, D40A, D50A, or D65A |
65 |
25 |
|
12–18 |
0.75 |
2 |
5 |
5 |
10 |
15 |
LC1D18, D25, D32, D40A, D50A, or D65A |
65 |
25 |
|
17–25 |
1.5 |
3 |
5 |
7.5 |
15 |
20 |
LC1D25, D32, D40A, D50A, or D65A |
65 |
25 |
|
23–32 |
2 |
5 |
7.5 |
10 |
20 |
25 |
LC1D32, D40A, D50A, or D65A |
65 |
25 |
|
30–40 |
3 |
— |
10 |
— |
25 |
30 |
LC1D40A, 50A or 65A |
65 |
25 |
|
37–50 |
— |
7.5 |
10 |
15 |
30 |
40 |
LC1D50A or 65A |
65 |
25 |
|
48–65 |
5 |
10 |
15 |
20 |
40 |
50 |
LC1D65A or 80 |
65 |
25 |
|
NOTE: These values are derived from the UL 60947 Type F certification (E164871).
|