8536DB0901 R02/25

Wiring Devices

Power Distribution Blocks

Short-Circuit Current Ratings with Combination of Enclosed Power Distribution Blocks and Circuit Breakers

Wire Type (Class) 

Catalog Number

Suitable Copper Conductors Range kcmil/AWG (mm2)

Overcurrent Protection Circuit Breaker Required

SCCR RMS Sym. A

Volts Max.

Line

Load

Manufacturer

Type

Maximun A

B, C

NSYEBAD11611

4–2
(16–25)
10–2
(6–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

12–2
(4–25)
12–2
(4–25)

Schneider Electric

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

12–2
(4–25)
12–2
(4–25)

Schneider Electric

BDL36125

125

18kA

BGL36125

125

35kA

BJL36125

125

65kA

 

B, C

NSYEBAD11614

4–2
(16–25)

10 (6)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

10–2
(6–25)

10 (6)

Schneider Electric

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

12–2
(4–25)

12–10
(4–6)

Schneider Electric

BDL36125

125

18kA

BGL36125

125

35kA

BJL36125

125

65kA

 

B, C

NSYEBAD12611
NSYEBAP12611
NSYEBCD12611
NSYEBCP12611

4–3/0
(16–70)

8–3/0
(10–70)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

B, C

NSYEBAD12614
NSYEBAP12614
NSYEBCD12614
NSYEBCP12614

4–3/0
(16–70)

10–2
(6–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

Enclosed Power Distribution Blocks Short-Circuit Current Ratings with Fuses

Wire Type (Class) 

Catalog Number

Suitable Copper Conductors Range
AWG (mm2)

Fuse Type / Amperage

SCCR

Line

Load

J

T

RK1

RK5

G

CC

B, C

NSYEBAD11611

14–2 (2.5–25)

14–2 (2.5–25)

175

225

100

100 kA

G, H, I, K

14–4 (2.5–16)

14–4 (2.5–16)

175

225

100

100 kA

*

14–2 (2.5–25)

14–2 (2.5–25)

NONE

10 kA

 

B, C

NSYEBAD11614

10–2
(6–25)

14–10 (2.5–4)

125

200

100

65 kA

G, H, I, K

10–4
(6–16)

14–10 (2.5–4)

125

200

100

65 kA

*

14–2 (2.5–25)

14–10 (2.5–4)

NONE

10 kA

 

B, C

NSYEBAD12611
NSYEBAP12611
NSYEBCD12611
NSYEBCP12611

8–3/0 (10–70)

8–3/0 (10–70)

225

225

200

60

60

30

100 kA

G, H, I

8–2/0 (10–50)

8–2/0 (10–50)

300

300

200

100

60

30

100 kA

*

14–3/0 (2.5–70)

14–3/0 (2.5–70)

NONE

10 kA

 

B, C

NSYEBAD12614
NSYEBAP12614
NSYEBCD12614
NSYEBCP12614

8–3/0 (10–70)

8–2
(10–25)

225

225

200

60

60

30

100 kA

B, C

8–3/0 (10–70)

12–8
(4–10)

100

110

100

30

60

30

100 kA

G, H, I

8–2/0 (10–50)

8–4
(10–16)

225

225

200

60

60

30

100 kA

G, H, I

8–2/0 (10–50)

12–8
(4–10)

100

110

100

30

60

30

100 kA

*

14–3/0 (2.5–70)

14–2 (2.5–25)

NONE

10 kA

 
*

NSYEBAD13618
NSYEBCD13618

6–400 (16–185) and
14–3/0
(2.5–70)

14–2 (2.5–25)

NONE

10 kA

 

B, C

NSYEBAP13618
NSYEBCP13618

3/0–400 (70–185)

8–2
(10–25)

400

400

400

200

60

30

100 kA

B, C

6–400 (16–185)

10–2
(6–25)

200

200

200

100

60

30

100 kA

G, H, I

6–400 (16–185)

10–2
(6–25)

300

300

200

100

60

30

100 kA

*

6–400 (16–185) and
14–3/0
(2.5–70)

14–2 (2.5–25)

NONE

10 kA

 
*

NSYEBAD25622
NSYEBCD25622

6–250 (16–120)

6–250
(16–120)

NONE

10 kA

 

B, C

NSYEBAP25622
NSYEBCP25622

1/0–250 (50–120)

1/0–250
(50–120)

600

600

50 kA

B, C

1/0–250 (50–120)

1/0–250
(50–120)

400

400

400

200

60

30

100 kA

B, C

6–250 (16–120)

6–250
(16–120)

400

400

400

100

60

30

100 kA

G, H, I

1/0–250 (50–120)

1/0–250
(50–120)

300

300

200

100

60

30

100 kA

*

6–250 (16–120)

6–250
(16–120)

NONE

10 kA

 

B, C

NSYEBAP27622

4–500 (25–240)

4–500
(25–240)

600

600

600

200

60

30

100 kA

G, H, I

2–350 (35–150)

2–350
(35–150)

600

600

600

200

60

30

100 kA

*

4–500 (25–240)

4–500
(25–240)

NONE

10 kA

 

B, C

NSYEBAP27628

250–500
(120–240)

4–2/0 (25–50)

600

600

400

200

60

30

100 kA

B, C

NSYEBCP27628

250–500
(120–240)

4–2/0 (25–50)

600

600

600

200

60

30

100 kA

B, C

NSYEBAP27628
NSYEBCP27628

4–500 (25–240)

10–2/0 (6–50)

350

350

200

100

60

30

100 kA

G, H, I

250–350
(120–150)

4–1
(25–35)

600

600

600

200

60

30

100 kA

G, H, I

4–350 (25–150)

8–1
(10–35)

350

350

200

100

60

30

100 kA

*

4–500 (25–240)

10–2/0 (6–50)

NONE

10 kA

9080LBA and 9080LBC Power Distribution Blocks Short-Circuit Current Ratings with Circuit Breakers

Catalog Number

Suitable Conductors MCM/AWG (mm2) Cu

Overcurrent Protection Circuit Breaker Required

SCCR, RMS Sym. A

Volts Max

Line

Load

Manufacturer

Type

Maximum A

9080LBA161101
9080LBA361101

6–2 (16–25)

6–2 (16–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

10–8 (6)

10–8 (6)

Schneider Electric

HDL36100

100

18 kA

HGL36100

100

35 kA

HJL36100

100

65 kA

HLL36100

100

65 kA

 

9080LBA161104
9080LBA261104
9080LBA361104

6–2 (16–25)

4 x 10 (6)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

10–8 (6)

4 x 14 (2.5)

Schneider Electric

HDL36100

100

18 kA

HGL36100

100

35 kA

HJL36100

100

65 kA

HLL36100

100

65 kA

 

9080LBA162104
9080LBA262104
9080LBA362104

10–2/0 (6–50)

4 x 10–4
(6–16)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBA362106

6–2/0 (16–50)

6 x 10–4
(6–16)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBA163104
9080LBA263104
9080LBA363104

4–2/0 (25–50)

4 x 8–2
(10–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBA163106
9080LBA263106
9080LBA363106

6–2/0 (16–50)

6 x 10–2
(6–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

480

JJL36250

250

65 kA

480

JLL36250

250

65 kA

480

6–350 (16–150)

10–2 (6–25)

Schneider Electric

JJL36250

600

25 kA

600

6–400 (16–185)

8–4 (10–16)

Schneider Electric

LJL36600

600

65 kA

480

6–400 (16–185)

8–2 (10–25)

Schneider Electric

LJL36600

600

25 kA

600

 

9080LBA163206
9080LBA263206
9080LBA363206

2 x 8–1/0 (10–50)

6 x 10–4
(6–16)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

9080LBA164108
9080LBA264108
9080LBA364108

6–2/0 (16–50)

6 x 10–2
(6–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

6–400 (16–185)

8–2 (10–25)

Schneider Electric

LJL36600

600

65 kA

600

 

9080LBA165106
9080LBA265106
9080LBA365106

4–2/0 (25–50)

6 x 8 (10)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBA165208
9080LBA265208
9080LBA365208

4–500 (25–240)

6–2/0 (16–50)

Schneider Electric

LJL36600

600

65 kA

480

25 kA

600

 

9080LBA165112
9080LBA265112
9080LBA365112

4–2/0 (25–50)

12 x 8–2
(10–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBC162101
9080LBC362101

8–1/0 (10–50)

8–1/0 (10–50)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBC162104
9080LBC262104
9080LBC362104

8–2/0 (10–50)

4 x 8–4
(10–16)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBC163106
9080LBC263106
9080LBC363106

1 x 4–2/0
(25–50)

6 x 8–2
(10–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

480

JJL36250

250

65 kA

480

JLL36250

250

65 kA

480

 

9080LBC163206
9080LBC263206
9080LBC363206

2 x 2–2/0
(35–50)

6 x 8–4
(10–16)

Schneider Electric

JDL36175

175

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

2 x 6–4 (16)

6 x 12–10 (4)

Schneider Electric

JDL36250

250

18 kA

JGL36175

175

35 kA

JJL36175

175

65 kA

JLL36175

175

65 kA

               

9080LBA164108
9080LBA264108
9080LBA364108

6–2/0 (16–50)

6 x 10–2
(6–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

6–400 (16–185)

8–2 (10–25)

Schneider Electric

LJL36600

600

65 kA

600

 

9080LBA165106
9080LBA265106
9080LBA365106

4–2/0 (25–50)

6 x 8 (10)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBA165208
9080LBA265208
9080LBA365208

4–500 (25–240)

6–2/0 (16–50)

Schneider Electric

LJL36600

600

65 kA

480

25 kA

600

 

9080LBA165112
9080LBA265112
9080LBA365112

4–2/0 (25–50)

12 x 8–2
(10–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBC162101
9080LBC362101

8–1/0 (10–50)

8–1/0 (10–50)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBC162104
9080LBC262104
9080LBC362104

8–2/0 (10–50)

4 x 8–4
(10–16)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

 

9080LBC163106
9080LBC263106
9080LBC363106

1 x 4–2/0
(25–50)

6 x 8–2
(10–25)

Schneider Electric

JDL36250

250

18 kA

480

JGL36250

250

35 kA

480

JJL36250

250

65 kA

480

JLL36250

250

65 kA

480

 

9080LBC163206
9080LBC263206
9080LBC363206

2 x 2–2/0
(35–50)

6 x 8–4
(10–16)

Schneider Electric

JDL36175

175

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

2 x 6–4 (16)

6 x 12–10 (4)

Schneider Electric

JDL36250

250

18 kA

JGL36175

175

35 kA

JJL36175

175

65 kA

JLL36175

175

65 kA

9080LBA and 9080LBC Power Distribution Blocks Short-Circuit Current Ratings with Fuses

Catalog Numbers

Suitable Conductors kcmil/AWG (mm2)

Fuse Type / Amperage

SCCR

1-Pole

2-Poles

3-Poles

Line

Load

J

T

RK1

RK5

G

CC

9080LBA161101

9080LBA361101

6–2
(10–25)

6–2
(10–25)

200

200

200

100

60

30

100 kA

10–2
(6–25)

10–2
(6–25)

100

100

100

30

60

30

100 kA

10–2
(6–25)

10–2
(6–25)

125

125

60

30

60

30

65 kA

10–4
(6–16)
(class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2 (2.5–25)

14–2 (2.5–25)

NONE

10 kA

 

9080LBA161104

9080LBA261104

9080LBA361104

6–2
(16–25)

10 (6)

200

200

200

60

60

30

100 kA

10–2
(6–25)

14–10 (2.5–4)

150

150

100

30

60

30

100 kA

12–2
(4–25)

14–10 (2.5–4)

60

60

30

50

30

100 kA

10–4
(6–16)
(class G,H,I,K)

14–10 (2.5–4) (class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2
(2.5–25)

14–10 (2.5–4)

NONE

10 kA

 

9080LBA162101

9080LBA262101

9080LBA362101

6–2/0 (16–50)

6–2/0 (16–50)

300

300

200

100

60

30

65 kA

6–1
(16–35)
(class G,H,I,K)

6–1
(16–35)
(class G,H,I,K)

300

300

200

100

60

30

65 kA

14–2/0 (2.5–50)

14–2/0 (2.5–50)

NONE

10 kA

 

9080LBA162104

9080LBA262104

9080LBA362104

6–2/0 (16–50)

10–4
(6–16)

200

200

200

100

60

30

100 kA

6–2/0 (16–50)

14–4 (2.5–16)

150

150

100

30

60

30

100 kA

6–1 (16–35)
(class G,H,I,K)

12–6
(4–10)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0 (2.5–50)

14–4 (2.5–16)

NONE

10 kA

 

9080LBA362106

6–2/0 (16–50)

10–4
(6–16)

200

200

200

100

60

30

100 kA

10–2/0
(6–50)

14–4 (2.5–16)

60

60

60

30

30

100 kA

6–1
(16–35)
(class G,H,I,K)

10–6
(6–10)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

10–1
(6–35)
(class G,H,I)

14–6 (2.5–10) (class G,H,I)

60

60

60

30

30

100 kA

14–2/0 (2.5–50)

14–4 (2.5–16)

NONE

10 kA

 

9080LBA163101

9080LBA263101

9080LBA363101

1/0–350 (70–150)

1/0–350 (70–150)

400

400

400

100

60

30

100 kA

6–350 (16–150)

6–350 (16–150)

300

300

200

100

60

30

100 kA

1/0–250 (70–120)(class G,H,I,K)

1/0–250 (70–120) (class G,H,I,K)

300

300

200

100

60

30

100 kA

6–350 (16–150)

6–350 (16–150)

NONE

10 kA

 

9080LBA163104

9080LBA263104

9080LBA363104

3/0–400 (95–185)

6–2
(16–25)

400

400

400

100

60

30

100 kA

6–400 (16–185)

10–2
(6–25)

300

300

200

100

60

30

100 kA

1/0–250 (70–120) (class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

6–400 (16–185)

14–2
(2.5–25)

NONE

10 kA

9080LBA163106

9080LBA263106

9080LBA363106

3/0–400 (95–185)

8–2
(10–25)

500

500

400

200

60

30

100 kA

6–400 (16–185)

10–2
(6–25)

350

350

200

100

60

30

100 kA

1/0–250 (70–120)(class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

6–400(16–185)

14–2 (2.5–25)

NONE

10 kA

 

9080LBA163206

9080LBA263206

9080LBA363206

2–2/0 (35–50)

8–4
(10–16)

400

400

400

100

60

30

100 kA

6–2/0 (16–50)

8–4
(10–16)

350

350

200

100

60

30

100 kA

6–2/0 (16–50)

10–4
(6–16)

250

250

200

60

60

30

100 kA

(1) 6 (16)

(2) 12 (4)

225

225

100

60

60

30

100 kA

6–1
(16–35 )
(class G,H,I,K)

8–6 (10) (class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0 (2.5–50)

14–4 (2.5–16)

NONE

10 kA

 

9080LBA164101

9080LBA364101

2–600 (35–300)

2–600 (35–300)

600

600

50 kA

2–600
(35–300)

2–600 (35–300)

400

400

400

200

60

30

100 kA

2–350 (35–150 )
(class G,H,I,K)

2–350 (35–150) (class G,H,I,K)

400

400

400

200

60

30

100 kA

2–60 0(35–300)

2–600 (35–300)

NONE

10 kA

 

9080LBA164108

9080LBA264108

9080LBA364108

3/0–400 (95–185)

8–2
(10–25)

400

400

400

200

60

30

100 kA

6–400 (16–185)

10–2
(6–25)

200

200

200

100

60

30

100 kA

1/0–250(70–120) (class G,H,I,K)

14–4 (2.5–16) (class G,H,I,K)

150

150

100

30

60

30

100 kA

6–40 0(16–185)

14–2(2.5–25)

NONE

10 kA

 

9080LBA165202

9080LBA265202

9080LBA365202

4–350 (25–150)

4–350 (25–150)

450

450

400

200

60

30

100 kA

4–350 (25–150)

4–350 (25–150)

600

600

50 kA

2–250 (35–120) (class G,H,I,K)

2–250(35–120) (class G,H,I,K)

600

600

50 kA

2–250(35–120) (class G,H,I,K)

2–250 (35–120) (class G,H,I,K)

450

450

400

200

60

30

100 kA

4–350 (25–150)

4–350 (25–150)

NONE

10 kA

9080LBA1652021

9080LBA2652021

9080LBA3652021

4–500 (25–240)

4–500 (25–240)

500

500

400

200

60

30

100 kA

2–350(35–150) (class G,H,I,K)

2–350 (35–150)(class G,H,I,K)

500

500

400

200

60

30

100 kA

4–500 (25–240)

4–500 (25–240)

NONE

10 kA

 

9080LBA165106

9080LBA265106

9080LBA365106

3/0–500 (95–240)

6–2/0 (16–50)

400

400

400

100

60

30

100 kA

4–500 (25–240)

10–2/0 (6–50)

200

200

200

100

60

30

100 kA

2–350 (35–150)(class G,H,I,K)

6–1
(16–35 )
(class G,H,I,K)

400

400

400

100

60

30

100 kA

2–350(35–150) (class G,H,I,K)

10–1
(6–35)
(class G,H,I,K)

250

250

200

100

60

30

100 kA

4–500 (25–240)

14–2/0 (2.5–50)

NONE

10 kA

 

9080LBA165112

9080LBA265112

9080LBA365112

3/0–500 (95–240)

6–2
(16–25)

400

400

400

200

60

30

100 kA

4–500 (25–240)

10–2
(6–25)

250

250

200

100

60

30

100 kA

2–350
(35–150)
(class G,H,I,K)

6–4 (16) (class G,H,I,K)

400

400

400

200

60

30

100 kA

2–350
(35–150)
(class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

250

250

200

200

60

20

100 kA

4–500 (25–240)

14–2 (2.5–25)

NONE

10 kA

 

9080LBA165208

9080LBA265208

9080LBA365208

250–500
(150–240)

4–2/0 (25–50)

600

600

400

200

60

30

100 kA

4–500 (25–240)

10–2/0 (6–50)

350

350

200

100

60

30

100 kA

250–350(150) (class G,H,I,K)

4–1
(25–35)
(class G,H,I,K)

600

600

400

200

60

30

100 kA

4–350 (25–150) (class G,H,I,K)

10–6
(6–10)
(class G,H,I,K)

350

350

200

100

60

30

100 kA

4–500 (25–240)

14–2/0 (2.5–50)

NONE

10 kA

 

9080LBA165212

9080LBA265212

9080LBA365212

250–500
(150–240)

8–4
(10–16)

400

400

200

100

60

30

100 kA

4–500 (25–240)

10–4
(6–16)

350

350

200

100

60

30

100 kA

250–350 (150) (class G,H,I,K)

8–6(10) (class G,H,I,K)

400

400

200

100

60

30

100 kA

4–350(25–150) (class G,H,I,K)

10–6
(6–10)
(class G,H,I,K)

350

350

200

100

60

30

100 kA

4–500 (25–240)

14–4 (2.5–16)

NONE

10 kA

9080LBC162101

9080LBC362101

6–1/0 (16–50)

6–1/0 (16–50)

175

175

100

60

60

30

100 kA

6–1
(16–35)
(class G,H,I,K)

6–1
(16–35)
(class G,H,I,K)

175

175

100

60

60

30

100 kA

14–1/0 (2.5–50)

14–1/0 (2.5–50)

NONE

10 kA

 

9080LBC162104

9080LBC262104

9080LBC362104

6–2/0 (10–50)

10–4
(6–16)

200

200

200

100

60

30

100 kA

10–2/0 (6–50)

14–4 (2.5–16)

150

150

100

30

60

30

100 kA

6–1
(16–35)
(class G,H,I,K)

12–6
(4–10)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0 (2.5–50)

14–4 (2.5–16)

NONE

10 kA

 

9080LBC163101

9080LBC363101

6–250 (16–120)

6–250 (16–120)

300

300

200

100

60

30

100 kA

1/0–250 (70–120) (class G,H,I,K)

1/0–250 (70–120) (class G,H,I,K)

300

300

200

100

60

30

100 kA

6–250 (16–120)

6–250 (16–120)

NONE

10kA

 

9080LBC163106

9080LBC263106

9080LBC363106

3/0–500 (95–240)

8–2
(10–25)

400

400

400

200

60

30

100 kA

4–500 (25–240)

10–2
(6–25)

300

300

200

100

60

30

100 kA

1/0–250 (70–120) (class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

Suitable Conductors kcmil/AWG (mm2)

Fuse Type / Amperage

SCCR

Line

Load

J

T

RK1

RK5

G

CC

6–2
(10–25)

6–2
(10–25)

200

200

200

100

60

30

100 kA

10–2
(6–25)

10–2
(6–25)

100

100

100

30

60

30

100 kA

10–2
(6–25)

10–2
(6–25)

125

125

60

30

60

30

65 kA

10–4
(6–16)
(class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2 (2.5–25)

14–2 (2.5–25)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

6–2
(16–25)

10 (6)

200

200

200

60

60

30

100 kA

10–2
(6–25)

14–10 (2.5–4)

150

150

100

30

60

30

100 kA

12–2
(4–25)

14–10 (2.5–4)

60

60

30

50

30

100 kA

10–4
(6–16)
(class G,H,I,K)

14–10 (2.5–4) (class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2
(2.5–25)

14–10 (2.5–4)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

6–2/0 (16–50)

6–2/0 (16–50)

300

300

200

100

60

30

65 kA

6–1
(16–35)
(class G,H,I,K)

6–1
(16–35)
(class G,H,I,K)

300

300

200

100

60

30

65 kA

14–2/0 (2.5–50)

14–2/0 (2.5–50)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

6–2/0 (16–50)

10–4
(6–16)

200

200

200

100

60

30

100 kA

6–2/0 (16–50)

14–4 (2.5–16)

150

150

100

30

60

30

100 kA

6–1 (16–35)
(class G,H,I,K)

12–6
(4–10)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0 (2.5–50)

14–4 (2.5–16)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

6–2/0 (16–50)

10–4
(6–16)

200

200

200

100

60

30

100 kA

10–2/0
(6–50)

14–4 (2.5–16)

60

60

60

30

30

100 kA

6–1
(16–35)
(class G,H,I,K)

10–6
(6–10)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

10–1
(6–35)
(class G,H,I)

14–6 (2.5–10) (class G,H,I)

60

60

60

30

30

100 kA

14–2/0 (2.5–50)

14–4 (2.5–16)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

1/0–350 (70–150)

1/0–350 (70–150)

400

400

400

100

60

30

100 kA

6–350 (16–150)

6–350 (16–150)

300

300

200

100

60

30

100 kA

1/0–250 (70–120)(class G,H,I,K)

1/0–250 (70–120) (class G,H,I,K)

300

300

200

100

60

30

100 kA

6–350 (16–150)

6–350 (16–150)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

3/0–400 (95–185)

6–2
(16–25)

400

400

400

100

60

30

100 kA

6–400 (16–185)

10–2
(6–25)

300

300

200

100

60

30

100 kA

1/0–250 (70–120) (class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

6–400 (16–185)

14–2
(2.5–25)

NONE

10 kA

3/0–400 (95–185)

8–2
(10–25)

500

500

400

200

60

30

100 kA

6–400 (16–185)

10–2
(6–25)

350

350

200

100

60

30

100 kA

1/0–250 (70–120)(class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

6–400(16–185)

14–2 (2.5–25)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

2–2/0 (35–50)

8–4
(10–16)

400

400

400

100

60

30

100 kA

6–2/0 (16–50)

8–4
(10–16)

350

350

200

100

60

30

100 kA

6–2/0 (16–50)

10–4
(6–16)

250

250

200

60

60

30

100 kA

(1) 6 (16)

(2) 12 (4)

225

225

100

60

60

30

100 kA

6–1
(16–35 )
(class G,H,I,K)

8–6 (10) (class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0 (2.5–50)

14–4 (2.5–16)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

2–600 (35–300)

2–600 (35–300)

600

600

50 kA

2–600
(35–300)

2–600 (35–300)

400

400

400

200

60

30

100 kA

2–350 (35–150 )
(class G,H,I,K)

2–350 (35–150) (class G,H,I,K)

400

400

400

200

60

30

100 kA

2–60 0(35–300)

2–600 (35–300)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

3/0–400 (95–185)

8–2
(10–25)

400

400

400

200

60

30

100 kA

6–400 (16–185)

10–2
(6–25)

200

200

200

100

60

30

100 kA

1/0–250(70–120) (class G,H,I,K)

14–4 (2.5–16) (class G,H,I,K)

150

150

100

30

60

30

100 kA

6–40 0(16–185)

14–2(2.5–25)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

4–350 (25–150)

4–350 (25–150)

450

450

400

200

60

30

100 kA

4–350 (25–150)

4–350 (25–150)

600

600

50 kA

2–250 (35–120) (class G,H,I,K)

2–250(35–120) (class G,H,I,K)

600

600

50 kA

2–250(35–120) (class G,H,I,K)

2–250 (35–120) (class G,H,I,K)

450

450

400

200

60

30

100 kA

4–350 (25–150)

4–350 (25–150)

NONE

10 kA

4–500 (25–240)

4–500 (25–240)

500

500

400

200

60

30

100 kA

2–350(35–150) (class G,H,I,K)

2–350 (35–150)(class G,H,I,K)

500

500

400

200

60

30

100 kA

4–500 (25–240)

4–500 (25–240)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

3/0–500 (95–240)

6–2/0 (16–50)

400

400

400

100

60

30

100 kA

4–500 (25–240)

10–2/0 (6–50)

200

200

200

100

60

30

100 kA

2–350 (35–150)(class G,H,I,K)

6–1
(16–35 )
(class G,H,I,K)

400

400

400

100

60

30

100 kA

2–350(35–150) (class G,H,I,K)

10–1
(6–35)
(class G,H,I,K)

250

250

200

100

60

30

100 kA

4–500 (25–240)

14–2/0 (2.5–50)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

3/0–500 (95–240)

6–2
(16–25)

400

400

400

200

60

30

100 kA

4–500 (25–240)

10–2
(6–25)

250

250

200

100

60

30

100 kA

2–350
(35–150)
(class G,H,I,K)

6–4 (16) (class G,H,I,K)

400

400

400

200

60

30

100 kA

2–350
(35–150)
(class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

250

250

200

200

60

20

100 kA

4–500 (25–240)

14–2 (2.5–25)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

250–500
(150–240)

4–2/0 (25–50)

600

600

400

200

60

30

100 kA

4–500 (25–240)

10–2/0 (6–50)

350

350

200

100

60

30

100 kA

250–350(150) (class G,H,I,K)

4–1
(25–35)
(class G,H,I,K)

600

600

400

200

60

30

100 kA

4–350 (25–150) (class G,H,I,K)

10–6
(6–10)
(class G,H,I,K)

350

350

200

100

60

30

100 kA

4–500 (25–240)

14–2/0 (2.5–50)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

250–500
(150–240)

8–4
(10–16)

400

400

200

100

60

30

100 kA

4–500 (25–240)

10–4
(6–16)

350

350

200

100

60

30

100 kA

250–350 (150) (class G,H,I,K)

8–6(10) (class G,H,I,K)

400

400

200

100

60

30

100 kA

4–350(25–150) (class G,H,I,K)

10–6
(6–10)
(class G,H,I,K)

350

350

200

100

60

30

100 kA

4–500 (25–240)

14–4 (2.5–16)

NONE

10 kA

6–1/0 (16–50)

6–1/0 (16–50)

175

175

100

60

60

30

100 kA

6–1
(16–35)
(class G,H,I,K)

6–1
(16–35)
(class G,H,I,K)

175

175

100

60

60

30

100 kA

14–1/0 (2.5–50)

14–1/0 (2.5–50)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

6–2/0 (10–50)

10–4
(6–16)

200

200

200

100

60

30

100 kA

10–2/0 (6–50)

14–4 (2.5–16)

150

150

100

30

60

30

100 kA

6–1
(16–35)
(class G,H,I,K)

12–6
(4–10)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0 (2.5–50)

14–4 (2.5–16)

NONE

10 kA

 

9080LBC163106

9080LBC263106

9080LBC363106

6–250 (16–120)

6–250 (16–120)

300

300

200

100

60

30

100 kA

1/0–250 (70–120) (class G,H,I,K)

1/0–250 (70–120) (class G,H,I,K)

300

300

200

100

60

30

100 kA

6–250 (16–120)

6–250 (16–120)

NONE

10kA

 

9080LBC163106

9080LBC263106

9080LBC363106

3/0–500 (95–240)

8–2
(10–25)

400

400

400

200

60

30

100 kA

4–500 (25–240)

10–2
(6–25)

300

300

200

100

60

30

100 kA

1/0–250 (70–120) (class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

4–500 (25–240)

14–4 (2.5–16)

NONE

10 kA

4–500 (25–240)

14–4 (2.5–16)

NONE

10 kA

 

9080LBC163206

9080LBC263206

9080LBC363206

2–2/0 (35–50)

8–4
(10–16)

400

400

400

100

60

30

100 kA

6–2/0 (16–50)

8–4
(10–16)

350

350

200

100

60

30

100 kA

10–4
(6–16)
(class G,H,I,K)

14–10 (2.5–4)(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0 (2.5–50)

14–4 (2.5–16)

NONE

10 kA

 

9080LBC165208

9080LBC365208

250–500
(150–240)

4–2/0 (25–50)

500

500

400

200

60

30

100 kA

4–500 (25–240)

6–2/0 (16–50)

450

450

400

200

60

30

100 kA

250–350 (150) (class G,H,I,K)

4–1
(25–35)
(class G,H,I,K)

500

500

400

200

60

30

100 kA

2–350 (35–150) (class G,H,I,K)

6–1
(16–35)
(class G,H,I,K)

450

450

400

200

60

30

100 kA

4–500 (25–240)

14–2/0 (2.5–50)

NONE

10 kA

9080LBC165212

9080LBC365212

4–500 (25–240)

10–2
(6–25)

400

400

400

200

60

30

100 kA

250–500
(150–240)

8–2
(10–25)

600

600

50 kA

2–350 (35–150) (class G,H,I,K)

10–4
(6–16)
(class G,H,I,K)

400

400

400

200

60

30

100 kA

250–350 (150) (class G,H,I,K)

8–4
(10–16)
(class G,H,I,K)

600

600

50 kA

4–500 (25–240)

14–2 (2.5–25)

NONE

10 kA

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.