P-frame, 3P, MicroLogic™ Electronic-Trip Unit, IEC Rated
Class 612
P-frame, 3P, MicroLogic Electronic-Trip Unit, IEC Rated
P-frame—1600 A, Individually-Mounted, MicroLogic Electronic Trip Unit, IEC Rated
Sensor |
Cat. No. |
Terminal |
||
---|---|---|---|---|
N Interrupting [1] |
H Interrupting [1] |
L Interrupting [1] |
||
3P, 690 Vac 50/60 Hz with LS0 Trip Functions |
||||
630 A |
(4) 3/0–500 Al/Cu |
|||
800 A |
||||
1000 A |
||||
1250 A |
— |
|||
1600 A |
— |
|||
3P, 690 Vac 50/60 Hz with LSI Trip Functions |
||||
630 A |
(4) 3/0–500 Al/Cu |
|||
800 A |
||||
1000 A |
||||
1250A |
— |
|||
1600A |
— |
|||
MicroLogic Ammeter Trip Unit |
||||
3P, 690 Vac 50/60 Hz with LS0 Trip Functions |
||||
630 A |
(4) 3/0–500 Al/Cu |
|||
800 A |
||||
1000 A |
||||
1250 A |
— |
|||
1600 A |
— |
|||
3P, 690 Vac 50/60 Hz with LSI Trip Functions |
||||
630 A |
(4) 3/0–500 Al/Cu |
|||
800 A |
||||
1000 A |
||||
1250 A |
— |
|||
1600 A |
— |
|||
3P, 690 Vac 50/60 Hz with LSIG Trip Functions |
||||
630 A |
(4) 3/0–500 Al/Cu |
|||
800 A |
||||
1000 A |
||||
1250 A |
— |
|||
1600 A |
— |
|||
MicroLogic Power Trip Unit |
||||
3P, 690 Vac 50/60 Hz with LSI Trip Functions |
||||
630 A |
(4) 3/0–500 Al/Cu |
|||
800 A |
||||
1000 A |
||||
1250 A |
— |
|||
1600 A |
— |
|||
3P, 690 Vac 50/60 Hz with LSIG Trip Functions |
||||
630 A |
(4) 3/0–500 Al/Cu |
|||
800 A |
||||
1000 A |
||||
1250 A |
— |
|||
1600 A |
— |
note
See Digest for accessories and other information.
Interrupting Ratings
N |
H |
L |
||||
---|---|---|---|---|---|---|
Icu |
Ics (%Icu) |
Icu |
Ics (%Icu) |
Icu |
Ics (%Icu) |
|
220/240 V |
50 kA |
75% |
70 kA |
50% |
150 kA |
100% |
380/415 V |
50 kA |
70 kA |
150 kA |
|||
440 V |
50 kA |
65 kA |
130 kA |
|||
500/525 V |
40 kA |
50 kA |
100 kA |
|||
660/690 V |
30 kA |
42 kA |
25 kA |