DOCA0132EN-01

Using the CANopen Communication Network

Overview

This chapter describes how to use the LTMR controller via the network port using the CANopen protocol.

WARNING
LOSS OF CONTROL
  • The designer of any control scheme must consider the potential failure modes of control paths and, for critical functions, provide a means to achieve an acceptable state during and after a path interruption. Examples of critical control functions are emergency stop and overtravel stop.
  • Separate or redundant control paths must be provided for critical control functions.
  • System control paths may include communication links. Consideration must be given to the implications of anticipated transmission delays or interruptions of the link.(1)
  • Each implementation of an LTMR controller must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

(1) For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control".

WARNING
UNEXPECTED RESTART OF THE MOTOR
Check that the PLC application software:
  • Considers the change from local to remote control,
  • Manages appropriately the motor control commands during those changes.
When switching to the Network control channels, depending on the communication protocol configuration, the LTMR controller can take into account the latest known state of the motor control commands issued from the PLC and restart automatically the motor.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

CANopen Protocol Principle

Introduction to CANopen Network

CANopen is a networking system based on the serial bus Controller Area Network (CAN). The CANopen Communication profile (CiA DS-301) supports both direct access to device parameters and time-critical process data communication.

The CANopen device profile for LTMR controllers is a manufacturer-specific profile. It defines standards for basic device functionality while providing ample scope for additional vendor-specific device features.

CANopen uses the full power of CAN by allowing direct peer-to-peer data exchange between nodes in an organized and, if necessary, deterministic manner.

CANopen Protocol

The CANopen protocol is based on the CAN 2.B passive specification (identifier coded on 11 bits).

The LTMR CANopen controller interface conforms to the CANopen specifications (DS301 V4.02).

The controllers are described in EDS (electronic data sheet) files that must be embedded into the configuration tools.

NOTE: For more information about CANopen, visit the Can In Automation website: http://www.can-cia.de.

CANopen Message Frame

Below is the description of a standard CANopen message frame:

SOF

COB-ID

RTR

CTRL

Data Segment

CRC

ACK

EOF

1 bit

11 bits

1 bit

5 bits

0-8 bytes

16 bits

2 bits

7 bits

SOF

Start of frame

COB-ID

CAN message identification field, composed of a Function code (4 bits) and a Module ID (7 bits).

The Function code determines the object priority. This allows communication between a Network manager and 127 stations. The Function code is determined with an Object Dictionary in the Device Profile. Broadcasting is indicated by a Module ID of zero.

RTR

Remote transmission request

CTRL

Control field (i.e. data length)

CRC

Cyclic redundancy check

ACK

Acknowledge

OEF

End of frame

CANopen Services

CANopen communication objects transmitted via the CAN network are described by services:

  • NETWORK MANAGEMENT

    Starting the bus, parameters setting, monitoring.

  • HIGH SPEED TRANSMISSION OF PROCESS DATA

    PDOs (Process Data Objects) for real time control command.

  • LOW SPEED TRANSMISSION OF SERVICE DATA.

    SDOs (Service Data Objects) for configuration, setting and diagnostics.

Network Management (NMT)

The CANopen network management is node-oriented and follows a client/server structure. It requires one device in the network, which fulfils the function of the NMT client. The other nodes are NMT servers.

The CANopen NMT server devices implement a state machine, described below:

(1)

At power-up, the device enters the initialization state.

(2)

Once initialization is finished, the Pre-Operational state is automatically entered (it is possible to send parameters).

Note: In the Pre-Operational state, you can write some parameters selected by configuration.

(3) (6)

Start_Remote_Node

(4) (7)

Enter_Pre-Operational_State and apply fallback.

(5) (8)

Stop_Remote_Node

(9) (10) (11)

Reset_Node

(12) (13) (14)

Reset_Communication

Process Data Objects (PDOs)

The real time data transfer is performed by means of Process Data Object (PDO) telegrams. Process Data is time-critical data used to monitor and control the device.

The CANopen controller communication module features:

PDOs

Description

Status

Transmit PDO1

To monitor (data transmitted by the server)

Pre-configured and activated

Received PDO1

To control (data transmitted by the client)

Transmit PDO2

To exchange data (defined at configuration)

To be configured and activated

Received PDO2

Transmit PDO3

Received PDO3

Transmit PDO4

To access (read or write) to any register by programming

Pre-configured and activated

Received PDO4

The RPDO (Received PDO) and TPDO (Transmit PDO) objects can be configured to include 8 bytes of data (for example, organized as four 16-bit registers or one 64-bit object).

The RPDO objects have write access.

Depending on the application, set the PDO communication mode to asynchronous, cyclic, or acyclic synchronous.

In synchronous mode, the PDO transmission is related to the SYNC object, which is cyclically emitted by the CANopen client. It does not include any data. Its factory setting is 0x080.

Transmission mode is:

Transmission Type

PDO Transmission

 

Cyclic

Acyclic

Synchronous

Asynchronous

0

PDO sent synchronously with the SYNC object, triggered by a change of data value

 

 

1-240

PDO sent by the communication module once every 1 to 240 receptions of the SYNC object

 

 

255

Factory setting of communication mode

 

 

For more information on PDOs, refer to Using PDOs.

Service Data Objects (SDOs)

Service Data Objects (SDOs) are used to configure the device and to define the type and format of information communicated via the PDOs.

SDOs let you access any object of the device Object Dictionary.

CANopen clients perform acyclic messaging through SDOs. They are also used for asynchronous, aperiodic requests. For example, an SDO can be used to read a control unit identification.

The CANopen communication module manages one SDO server, which receives two COB-IDs:

  • One for requests (telegrams issued by the client to the CANopen LTMR)

  • One for responses (telegrams sent back to the client by the CANopen LTMR)

For more information on SDOs, refer to Using SDOs.

Configuration of the LTMR CANopen Network Port

Communication Parameters

Use the TeSys T DTM or the HMI to configure the CANopen communication parameters:

  • Network port address setting

  • Network port baud rate setting

  • Configuration channel setting

Setting the Node-ID

The Node-ID is the address of the module on the CANopen bus. With CANopen class S20, you can assign an address from 1 to 127.

You must set the Node-ID before any communication can begin. Use the TeSys T DTM or the HMI to configure the communication parameter Network Port Address Setting.

NOTE: A return to factory settings command sets the Node-ID to the invalid value 0.

Setting the Baud Rate

Set the baud rate to one of the following speeds:

  • 10 kBaud

  • 20 kBaud

  • 50 kBaud

  • 250 kBaud

  • 500 kBaud

  • 800 kBaud

  • 1000 kBaud

To set the baud rate, use the TeSys T DTM or the HMI to configure the communication parameter Network Port Baud Rate Setting.

The parameter has the following possible settings:

Network Port Baud Rate Setting

Baud Rate

0

10 kBaud

1

20 kBaud

2

50 kBaud

3

125 kBaud

4

250 kBaud

5

500 kBaud

6

800 kBaud

7

1000 kBaud

8

Autobaud

9

Factory setting (250 kBaud)

The factory setting for the Network Port Baud Rate Setting parameter is 250 kBaud. Using Autobaud, the LTMR Controller adapts its baud rate to that of the client.

NOTE: The Autobaud functionality can only be used if at least one client and one server are already communicating on the network.

Setting the Configuration Channel

The LTMR configuration can be managed:

  • Locally through the HMI port using the TeSys T DTM or the HMI

  • Remotely through the network.

To manage the configuration locally, the Config via Network Port Enable parameter must be disabled to prevent an overwrite of the configuration through the network.

To manage the configuration remotely, the Config via Network Port Enable parameter must be enabled (factory setting).

Importing the EDS File into the CANopen Configuration Software

EDS File

The different LTMR controller variants are described in EDS (electronic data sheet) files.

If the LTMR controllers do not show up in your CANopen configuration tool, the corresponding EDS files must be imported.

The EDS and icon files associated with the LTMR can be downloaded from www.se.com website ( Products and Services > Automation and Control > Product offers > Motor Control > TeSys T > Downloads > Software/Firmware > EDS&GSD ). EDS files and icons are grouped in a single compressed Zip file that you must unzip to a single directory on your hard disk drive.

The following table gives the associations between the four LTMR variants and the associated EDS files names.

Variants

Description

EDS File Name

TeSys T MMC L

Motor Management Controller, local configuration mode

TE_TESYST_MMC_L••••E.eds

TeSys T MMC L EV40

Motor Management Controller, LTMEV40, local configuration mode

TE_TESYST_MMC_L_EV40••••E.eds

TeSys T MMC R

Motor Management Controller, remote configuration mode

TE_TESYST_MMC_R••••E.eds

TeSys T MMC R EV40

Motor Management Controller, LTMEV40, remote configuration mode

TE_TESYST_MMC_R_EV40••••E.eds

Selection Criteria for TeSys T LTMR Controller Variants

There are four EDS files corresponding to the four possible configurations of the TeSys T Motor Management Controller system:

Choose...

When You Want to Use...

TeSys T MMC L

A TeSys T Motor Management Controller system without an expansion module, configurable via the HMI port. This variant enables you to preserve your local configuration.

TeSys T MMC L EV40

A TeSys T Motor Management Controller system with expansion module, configurable via the HMI port. This variant enables you to preserve your local configuration.

TeSys T MMC R

A TeSys T Motor Management Controller system without expansion module configurable via the network.

TeSys T MMC R EV40

A TeSys T Motor Management Controller system with expansion module configurable via the network.

In local configuration mode, the parameter Config via Network Port Enable must be disabled. This mode preserves the local configuration made using the Magelis XBT or TeSys T DTM through the HMI port and prevents PLC configuration via the network.

In remote configuration mode, the parameter Config via Network Port Enable must be enabled. This enables the PLC to remotely configure the LTMR controller.

NOTE: In remote mode, the parameters overwritten by the PLC will be lost. This mode is useful when replacing inoperable devices.

The Config via Network Port Enable parameter is set by default.

Using PDOs

Introduction

PDO telegrams are used to exchange periodic I/O data between the PLC and the LTMR Controller.

The LTMR Controller has four PDO sets:

  • PDO1 set is predefined for control and monitoring. It is activated by default.

  • PDO2 set is not predefined and is available to use. It is not activated by default.

  • PDO3 set is not predefined and is available to use. It is not activated by default.

  • PDO4 set is predefined to access any register (read or write) by programming using PKW objects. It is activated by default.

The four PDO sets support the following transmission modes:

  • Cyclic synchronous (synchronization is related to SYNC object)

  • Acyclic synchronous

The factory setting mode of transmission of LTMR Controller is acyclic synchronous. Data is sent at network startup, on network reconnection and during normal operation of data exchange.

The factory setting mode of transmission of CANopen is acyclic asynchronous. Data is sent from the client at network startup, on network reconnection and during normal operation of data exchange.

The mapping of the four PDO sets can be modified by the user.

Transmit PDOs can transport the following read-only variables:

Monitoring objects

CANopen index 2004

Receive PDOs can transport the following read/write variables:

Setting objects:

CANopen index 2007

Command objects:

CANopen index 2008

PDO1 Set Description

The first PDO set (PDO1) is dedicated to control and monitoring. The predefined mapping is described below and can be modified by the user.

Receive PDO1 Mapping Description

Receive PDO1 is dedicated to commanding the Controller from the PLC. This table describes the predefined mapping.

COB-ID

Word 1

Word 2

Word 3

Word 4

0x200 + Node-ID

Register

704

706

700

Empty

CANopen Index

2008:5

2008:7

2008:1

Description

Control Register

Analog output 1 command

Boolean output command register

Transmit PDO1 Mapping Description

Transmit PDO1 is dedicated to monitoring the Controller from the PLC. This table describes the predefined mapping.

COB-ID

Word 1

Word 2

Word 3

Word 4

0x180 + Node-ID

Register

455

456

457

458

CANopen Index

2004:6

2004:7

2004:8

2004:9

Description

System status register 1

System status register 2

Boolean inputs status

Boolean outputs status

PDO2 and PDO3 Set Description

PDO2 and PDO3 sets are not predefined (PDO is empty) and not activated. The user can map inside any mappable object.

PDO4 Set Description

PDO4 set is predefined to access to any register (read or write) by programming using PKW objects, which enable acyclical read or write access to any TeSys T register.

  • Four words are reserved in Receive PDO4 to receive a request telegram.

  • Four words are reserved in the Transmit PDO4 to provide a response telegram.

For TeSys T MMC L and TeSys T MMC L EV40, PKW use is restricted to read access.

Receive PDO4 Mapping Description

Receive PDO4 is dedicated to receiving PKW request telegrams.

CANopen Index

3000:01

3000:02

Word number

Word 1

Word 2

Word 3

Word 4

MSB

LSB

Description

Address Register

Toggle bit (bit 15)

Function code (bit 8 to 14)

0x00 or Address register

Value to write: 1st word MSW

Value to write: 2nd word LSW

Transmit PDO4 Mapping Description

Transmit PDO4 is dedicated to providing responses to PKW request telegrams.

CANopen Index

3000:03

3000:04

Word number

Word 1

Word 2

Word 3

Word 4

MSB

LSB

Description

Same as request

Toggle bit (bit 15)

Function code (bit 8 to 14)

0x00 or Address register

Read data: 1st word MSW

Read data: 2nd word LSW

NOTE: In the tables above:
  • MSB = Most Significant Byte

  • LSB = Least Significant Byte

  • MSW = Most Significant Word

  • LSW = Least Significant Word

PKW Objects

Overview

The CANopen Controller supports PKW (Periodically Kept in acyclic Words). The PKW feature consists of 4 manufacturer-specific objects: 0x3000:0x01 to 0x3000:0x04.

These objects enable a CANopen client to read or write any register using PDOs. They are mapped, by default, in Transmit and Receive PDO4.

You can choose to address a register by its number or by CANopen Index and sub-index, depending on the function code.

PKW OUT Data Register Number Addressing

PKW OUT Data request ( CANopen Client > LTMR ) is mapped by default in Receive PDO4.

To access a register using number addressing, you must select one of the following function codes:

  • R_REG_16 = 0x25 to read 1 register

  • R_REG_32 = 0x26 to read 2 registers

  • W_REG_16 = 0x2A to write 1 register

  • W_REG_32 = 0x2B to write 2 registers.

0x3000:0x01

0x3000:0x02

Word 1

Word 2

Word 3

Word 4

MSB

LSB

Register address

Toggle bit

(bit 15)

Function bits

(bits 8 to 14)

Not used

(bits 0 to 7)

Data to write

Register number

0/1

R_REG_16

Code 0x25

0x00

_

_

R_REG_32

Code 0x26

_

_

W_REG_16

Code 0x2A

Data to write in register

_

W_REG_32

Code 0x2B

Data to write in register 1

Data to write in register 2

PKW OUT Data CANopen Addressing

To access a register using CANopen addressing, you must select one of the following function codes:

  • R_CO_16 = 0x35 to read 1 register

  • R_CO_32 = 0x36 to read 2 registers

  • W_CO_16 = 0x3A to write 1 register

  • W_CO_32 = 0x3B to write 2 registers.

0x3000:0x01

0x3000:0x02

Word 1

Word 2

Word 3

Word 4

MSB

LSB

Register address

Toggle bit

(bit 15)

Function bits

(bits 8 to 14)

Register address

Data to write

CANopen index

0/1

R_CO_16

Code 0x35

CANopen sub-index

_

_

R_CO_32

Code 0x36

_

_

W_CO_16

Code 0x3A

Data to write in register

_

W_CO_32

Code 0x3B

Data to write in register 1

Data to write in register 2

Any changes in the function code will trigger the handling of the request (unless function code [b8...b14] = 0x00).

NOTE: The highest bit of function code (bit 15) is a toggle bit. It is changed for each consecutive request.

This mechanism enables the request initiator to detect that a response is ready by polling bit 15 of the function code in object 30000x:03. When this bit in the OUT project becomes equal to the response emitted toggle bit in the IN data (when starting the request), then the response is ready.

PKW IN Data Register Number Addressing

PKW IN Data Response ( LTMR > CANopen Client ) is mapped by default in Transmit PDO4. The LTMR echoes the same register address and function code or eventually a detected error code:

0x3000:0x03

0x3000:0x04

Word 1

Word 2

Word 3

Word 4

MSB

LSB

Register address

Toggle bit

(bit 15)

Function bits

(bits 8 to 14)

Not used

(bits 0 to 7)

Data to write

Same register number as in request

Same as request

DETECTED ERROR

Code 0x4E

0x00

Detected error code

R_REG_16

Code 0x25

Data read in register

_

R_REG_32

Code 0x26

Data read in register 1

Data read in register 2

W_REG_16

Code 0x2A

_

_

W_REG_32

Code 0x2B

_

_

PKW IN Data CANopen Addressing

The LTMR echoes the same register address and function code or eventually a detected error code:

0x3000:0x03

0x3000:0x04

Word 1

Word 2

Word 3

Word 4

MSB

LSB

Register address

Toggle bit

(bit 15)

Function bits

(bits 8 to 14)

Register address

Data to write

Same CANopen index as in request

Same as request

DETECTED ERROR

Code 0x4E

CANopen sub-index

Detected error code

R_REG_16

Code 0x55

Data read in register

_

R_REG_32

Code 0x36

Data read in register 1

Data read in register 2

W_REG_16

Code 0x3A

_

_

W_REG_32

Code 0x3B

_

_

If the initiator tries to write a TeSys T object or register to an unauthorized value, or tries to access an inaccessible register, a detected error code is returned (function code = toggle bit + 0x4E). The exact code can be found in words 3 and 4.

These codes are the same as SDO Abort codes SDO Abort Codes.

The request is not accepted and the object/register remains at the original value.

To re-trigger exactly the same command:

  1. Reset the function code to 0x00,

  2. Wait for the response frame with the function code equal to 0x00,

  3. Reset it to its previous value.

This is useful for a limited client like an HMI.

Another way of re-triggering exactly the same command is to invert the toggle bit in the function code byte.

The response is valid when the toggle bit of the response is equal to the toggle bit written in the answer (this is a more efficient method, but it requires higher programming capabilities).

Using SDOs

Introduction

SDO telegrams are used to aperiodically access any CANopen object by request programming. The SDO service consists of a request telegram and a response telegram.

Request SDO Telegram

Request information from the client to the LTMR Controller:

COB-ID

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

0x600 + Node-ID

Request code

Object index

Object sub-index

Request data

LSB

MSB

Bits 7-0

Bits 15-8

Bits 23-16

Bits 31-24

Response SDO Telegram

Request information from the client to the LTMR Controller:

COB-ID

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

0x580 + Node-ID

Response code

Object index

Object sub-index

Response data

LSB

MSB

Bits 7-0

Bits 15-8

Bits 23-16

Bits 31-24

Request and Response Codes

Depending on the request code and the response code, the contents of the request data and response data may vary. The following table shows the request data for each of the different request codes:

Response Code

Command Description

Byte 4

Byte 5

Byte 6

Byte 7

0x23

Write 4-byte data

Bits 7-0

Bits 15-8

Bits 23-16

Bits 31-24

0x2B

Write 2-byte data

Bits 7-0

Bits 15-8

0x00

0x00

0x2F

Write 1-byte data

Bits 7-0

0x00

0x00

0x00

0x40

Read data

0x00

0x00

0x00

0x00

0x80

Abort the current SDO command* 1

Bits 7-0

Bits 15-8

Bits 23-16

Bits 31-24

The following table shows the response data for each of the different response codes:

Request Code

Command Description

Byte 4

Byte 5

Byte 6

Byte 7

0x23

Read data: 4-byte data

Bits 7-0

Bits 15-8

Bits 23-16

Bits 31-24

0x2B

Read data: 2-byte data

Bits 7-0

Bits 15-8

0x00

0x00

0x2F

Read data: 1-byte data

Bits 7-0

0x00

0x00

0x00

0x40

Write a 1/2/4-byte data response

0x00

0x00

0x00

0x00

0x80

Detected error response: abort code returned*

0x00

0x00

0x00

0x00

SDO Abort Codes

The following abort codes are supported:

Abort Code

Description

0x 0503 0000

Segmented transfer: the toggle bit has not been alternated

0x 0504 0000

The SDO protocol timed out

0x 0504 0001

The request code is not valid or is unknown

0x 0601 0000

An access trip has occurred during access to the parameter (for example, a write request on a read-only parameter)

0x 0601 0001

Tried to perform a read request on a parameter with write-only access rights

0x 0601 0002

Tried to perform a write request on a parameter with read-only access rights

0x 0602 0000

The index sent in the request refers to an object that does not exist in the object dictionary

0x 0604 0041

PDO object mapping: the parameter cannot be mapped to the PDO; this detected error occurs when writing to the 0x1600, 0x1A00, 0x1605, and 0x1A05 parameters (PDO mappings)

0x 0604 0042

PDO object mapping: the number or length of the parameters to be mapped would exceed the maximum PDO length.

0x 0609 0011

The sub-index sent in the request does not exist

0x 0609 0030

Value range of parameter exceeded (only for write access)

0x 0609 0031

Value of parameter written too high

0x 0609 0032

Value of parameter written too low

0x 0609 0036

The parameter maximum value is less than its minimum value

0x 0800 0000

A general detected error occurred

Write SDO Example

Here is an example of write SDO programming for Premium PLC in structured text language.

Read SDO Example

Here is an example of read SDO programming for Premium PLC in structured text language.

Communication Profile Parameters

Overview

The CANopen Communication profile contains the following communication-specific parameters for the CANopen network:

  • Device type

  • Diagnostic

  • CANopen communication objects description

  • SDO

  • Received PDO

  • Transmit PDO

These parameters are used to configure and communicate with the LTMR controller. They are described in detail in the following pages.

Device Type

The following tables give the specifications for Device type parameter:

Index

Sub Index

Access

Object Type

Data Type

Factory Setting

Description

0x1000

0x00

RO

VAR

Unsigned 32

0x00000000

Device type:

Bits 16-23 = Device type mode

Bits 00-15 = Device profile number (I/O module profile)

Diagnostic

The following tables give the specifications for Diagnostic parameters:

Index

Sub Index

Access

Object Type

Data Type

Factory Setting

Description

0x1001

0x00

RO

VAR

Unsigned 8

0x00

Detected error register: Detected error (1) or no detected error (0)

Bitfield: could be detailed

What does this mean? Is it correct?

0x1003

0x00

RW

ARRAY

Unsigned 8

0

Number of detected errors: No detected error (0) or one or more detected errors (>0) in object 0x1003; Only the value 0 can be written

0x1003

0x01

RO

VAR

Unsigned 32

0x00000000

Standard Detected Error Field 1:

Bits 16-23 = Additional information (all 0s)

Bits 00-15 = Detected error code

0x1003

0x02

RO

VAR

Unsigned 32

0x00000000

Standard Detected Error Field 2:

Bits 16-23 = Additional information (all 0s)

Bits 00-15 = Detected error code

0x1003

0x03

RO

VAR

Unsigned 32

0x00000000

Standard Detected Error Field 3:

Bits 16-23 = Additional information (all 0s)

Bits 00-15 = Detected error code

0x1003

0x04

RO

VAR

Unsigned 32

0x00000000

Standard Detected Error Field 4:

Bits 16-23 = Additional information (all 0s)

Bits 00-15 = Detected error code

0x1003

0x05

RO

VAR

Unsigned 32

0x00000000

Standard Detected Error Field 5:

Bits 16-23 = Additional information (all 0s)

Bits 00-15 = Detected error code

CANopen Communication Objects Description

The following tables give the specifications for CANopen Communication Objects parameters:

Index

Sub Index

Access

Object Type

Data Type

Factory Setting

Description

0x1004

0x00

RO

ARRAY

Unsigned 32

0x00040004

Number of PDOs supported

0x1004

0x01

RO

VAR

Unsigned 32

0x00000000

Number of synchronous PDOs

Bits 16-31 = Number of received PDOs supported

Bits 00-15 = Number of transmit PDOs supported

0x1004

0x01

RO

VAR

Unsigned 32

0x00000000

Number of asynchronous PDOs

Bits 16-31 = Number of received PDOs supported

Bits 00-15 = Number of transmit PDOs supported

0x1005

0x00

RW

VAR

Unsigned 32

0x80

COB-ID SYNC message

0x1006

0x00

RW

VAR

Unsigned 32

0x00

Communication cycle period in microseconds

0x1007

0x00

RW

VAR

Unsigned 32

0x00

Synchronous window length in microseconds

0x1008

0x00

Const

VAR

VISIBLE_STRING

LTM

Manufacturer device name

0x1009

0x00

Const

VAR

VISIBLE_STRING

M1.0-ES1.0

Manufacturer hardware version

0x100A

0x00

Const

VAR

VISIBLE_STRING

V01.01

Manufacturer software version: The value given here is only an example.

0x100C

0x00

RW

VAR

Unsigned 16

0x0000

Guard time: By default, the Node Guarding Protocol is inhibited; the unit for this object is 1 ms.

0x100D

0x00

RW

VAR

Unsigned 8

0x00

Life time factor: Multiplier applied to the "Guard Time" to obtain a "Life Time"

0x1014

0x00

RW

VAR

Unsigned 32

$NODEID+

0x80

COB-ID Emergency message: COB-ID used for the EMCY service

0x1016

0x00

RO

ARRAY

Unsigned 8

1

Consumer Heartbeat Time - Number of entries

0x1016

0x01

RW

VAR

Unsigned 32

0x00000000

Consumer Heartbeat Time:

Bits 16-23 = Node-ID of the producer

Bits 00-15 = Heartbeat time (unit = 1 ms)

Note: Only one heartbeat producer can be configured here. By default, no producer is watched.

0x1017

0x00

RW

VAR

Unsigned 16

0x0000

Producer Heartbeat Time: The unit of this object is 1 ms. By default, the controller sends no Heartbeat messages.

0x1018

0x00

RO

ARRAY

Unsigned 8

4

Identity object - Number of entries

0x1018

0x01

RO

VAR

Unsigned 32

0x0300005A

Identity object - Vendor ID: This value is unique for each manufacturer. ("Power Control and Protection Activity")

0x1018

0x02

RO

VAR

Unsigned 32

See table below

Product code -To determine the product family and product number

0x1018

0x03

RO

VAR

Unsigned 32

0x00010001

Major and minor Product revision number

0x1018

0x04

RO

VAR

Unsigned 32

0x00000000

Serial number

0x1020

0x00

RO

ARRAY

Unsigned 32

2

Verify configuration

0x1020

0x01

RW

VAR

Unsigned 32

0x00000000

Configuration date

0x1020

0x02

RW

VAR

Unsigned 32

0x00000000

Configuration time

0x1029

0x00

RO

ARRAY

Unsigned 8

1

Detected Error Behavior - No. of Detected Error Classes

0x1029

0x01

RW

VAR

Unsigned 8

0x00

Detected communication error

0:pre-operational / 1:no state change / 2:stopped

Register 0x1018 : 0x02 is the product code. This register is used by configuration tools to identity the product on the network. Possible values are:

Object 1018sub2

With/without Expansion Module

Configuration Mode

0x 0000 0030

Without

Remote mode

0x 0000 0031

With

0x 0000 0130

Without

Local mode

0x 0000 0131

With

SDO Definition

SDO Specifications

The following table gives the specifications for SDOs.

Index

Sub Index

Access

Object Type

Data Type

Factory Setting

Description

0x1200

0x00

RO

RECORD

Unsigned 8

2

Server SDO - Number of entries

0x1200

0x01

RO

VAR

Unsigned 32

$NODEID+0x600

Server SDO - COB-ID: FBC -> K7 (receive)

0x1200

0x02

RO

VAR

Unsigned 32

$NODEID+0x580

Server SDO - COB-ID: FBC <- K7 (transmit)

Receive PDO Definition

Receive PDO specifications

The following tables give the specifications for Receive PDO.

Index

Sub Index

Access

Object Type

Data Type

Factory Setting

Description

0x1400

0x00

RO

RECORD

Unsigned 8

2

Receive PDO1 - Number of entries

0x1400

0x01

RW

VAR

Unsigned 32

$NODEID+0x00000200

Receive PDO1 - COB-ID

0x1400

0x02

RW

VAR

Unsigned 8

0xFF

Receive PDO1 - Transmission type: three modes are available for this PDO: asynchronous (255), synchronously cyclic (1-240), and synchronously acyclic (0)

0x1401

0x00

RO

RECORD

Unsigned 8

2

Receive PDO2 - Number of entries

0x1401

0x01

RW

VAR

Unsigned 32

$NODEID+0x80000300

Receive PDO2 - COB-ID

0x1401

0x02

RW

VAR

Unsigned 8

0xFF

Receive PDO2 - Transmission type: three modes are available for this PDO: asynchronous (255), synchronously cyclic (1-240), and synchronously acyclic (0)

0x1402

0x00

RO

RECORD

Unsigned 8

2

Receive PDO3 - Number of entries

0x1402

0x01

RW

VAR

Unsigned 32

$NODEID+0x80000400

Receive PDO3 - COB-ID

0x1402

0x02

RW

VAR

Unsigned 8

0xFF

Receive PDO3 - Transmission type: three modes are available for this PDO: asynchronous (255), synchronously cyclic (1-240), and synchronously acyclic (0)

0x1403

0x00

RO

RECORD

Unsigned 8

2

Receive PDO4 - Number of entries

0x1403

0x01

RW

VAR

Unsigned 32

$NODEID+0x00000500

Receive PDO4 - COB-ID

0x1403

0x02

RW

VAR

Unsigned 8

0xFF

Receive PDO4 - Transmission type: three modes are available for this PDO: asynchronous (255), synchronously cyclic (1-240), and synchronously acyclic (0)

.

Index

Sub Index

Access

Object Type

Data Type

Factory Setting

Description

0x1600

0x00

RW

ARRAY

Unsigned 8

3

Receive PDO1 mapping - Number of mapped objects

0x1600

0x01

RW

VAR

Unsigned 32

0x20080510

Receive PDO1 mapping 1 - mapped object: Reg [704]

0x1600

0x02

RW

VAR

Unsigned 32

0x20080410

Receive PDO1 mapping 2 - mapped object: Reg [706]

0x1600

0x03

RW

VAR

Unsigned 32

0x20080110

Receive PDO1 mapping 3 - mapped object: Reg [700]

0x1600

0x04

RW

VAR

Unsigned 32

0x00000000

Receive PDO1 mapping 4 - mapped object: None by default

0x1601

0x00

RW

ARRAY

Unsigned 8

0

Receive PDO2 mapping - Number of mapped objects

0x1601

0x01

RW

VAR

Unsigned 32

0x00000000

Receive PDO2 mapping 1 - mapped object: None by default

0x1601

0x02

RW

VAR

Unsigned 32

0x00000000

Receive PDO2 mapping 2 - mapped object: None by default

0x1601

0x03

RW

VAR

Unsigned 32

0x00000000

Receive PDO2 mapping 3 - mapped object: None by default

0x1601

0x04

RW

VAR

Unsigned 32

0x00000000

Receive PDO2 mapping 4 - mapped object: None by default

0x1602

0x00

RW

ARRAY

Unsigned 8

0

Receive PDO3 mapping - Number of mapped objects

0x1602

0x01

RW

VAR

Unsigned 32

0x00000000

Receive PDO3 mapping 1 - mapped object: None by default

0x1602

0x02

RW

VAR

Unsigned 32

0x00000000

Receive PDO3 mapping 2 - mapped object: None by default

0x1602

0x03

RW

VAR

Unsigned 32

0x00000000

Receive PDO3 mapping 3 - mapped object: None by default

0x1602

0x04

RW

VAR

Unsigned 32

0x00000000

Receive PDO3 mapping 4 - mapped object: None by default

0x1603

0x00

RW

ARRAY

Unsigned 8

2

Receive PDO4 mapping - Number of mapped objects

0x1603

0x01

RW

VAR

Unsigned 32

0x30000120

Receive PDO4 mapping 1 - mapped object: PKW request

0x1603

0x02

RW

VAR

Unsigned 32

0x30000220

Receive PDO4 mapping 2 - mapped object: None by default

0x1603

0x03

RW

VAR

Unsigned 32

0x00000000

Receive PDO4 mapping 3 - mapped object: None by default

0x1603

0x04

RW

VAR

Unsigned 32

0x00000000

Receive PDO4 mapping 4 - mapped object: None by default

Transmit PDO Definition

Transmit PDO Specifications

The following tables give the specifications for Transmit PDO.

Index

Sub Index

Access

Object Type

Data Type

Factory Setting

Description

0x1800

0x00

RO

RECORD

Unsigned 8

5

Transmit PDO1 - Number of entries

0x1800

0x01

RW

VAR

Unsigned 32

$NODEID+0x00000180

Transmit PDO1 - COB-ID

0x1800

0x02

RW

VAR

Unsigned 8

0xFF

Transmit PDO1 - Transmission type: three modes are available for this PDO: "asynchronous" (255), "synchronously cyclic" (1-240), and "synchronously acyclic" (0)

0x1800

0x03

RW

VAR

Unsigned 16

0

Transmit PDO1 - Inhibit time: Minimum time between two transmissions; unit = 0.1 ms

0x1800

0x04

RW

VAR

Unsigned 8

0

Transmit PDO1 - Reserved

0x1800

0x05

RW

VAR

Unsigned 16

0

Transmit PDO1 - Event timer: In "asynchronous" mode, this object sets a minimum rate of transmission for this PDO; unit = 0.1 ms

0x1801

0x00

RO

RECORD

Unsigned 8

5

Transmit PDO2 - Number of entries

0x1801

0x01

RW

VAR

Unsigned 32

$NODEID+0x80000280

Transmit PDO2 - COB-ID

0x1801

0x02

RW

VAR

Unsigned 8

0xFF

Transmit PDO2 - Transmission type: three modes are available for this PDO: "asynchronous" (255), "synchronously cyclic" (1-240), and "synchronously acyclic" (0)

0x1801

0x03

RW

VAR

Unsigned 16

0

Transmit PDO2 - Inhibit time: Minimum time between two transmissions; unit = 0.1 ms

0x1801

0x04

RW

VAR

Unsigned 8

0

Transmit PDO2 - Reserved

0x1801

0x05

RW

VAR

Unsigned 16

0

Transmit PDO2 - Event timer: In "asynchronous" mode, this object sets a minimum rate of transmission for this PDO; unit = 0.1 ms

0x1802

0x00

RO

RECORD

Unsigned 8

5

Transmit PDO3 - Number of entries

0x1802

0x01

RW

VAR

Unsigned 32

$NODEID+0x80000380

Transmit PDO3 - COB-ID

0x1802

0x02

RW

VAR

Unsigned 8

0xFF

Transmit PDO3 - Transmission type: three modes are available for this PDO: "asynchronous" (255), "synchronously cyclic" (1-240), and "synchronously acyclic" (0)

0x1802

0x03

RW

VAR

Unsigned 16

0

Transmit PDO3 - Inhibit time: Minimum time between two transmissions; unit = 0.1 ms

0x1802

0x04

RW

VAR

Unsigned 8

0

Transmit PDO3 - Reserved

0x1802

0x05

RW

VAR

Unsigned 16

0

Transmit PDO3 - Event timer: In "asynchronous" mode, this object sets a minimum rate of transmission for this PDO; unit = 0.1 ms

0x1803

0x00

RO

RECORD

Unsigned 8

5

Transmit PDO4 - Number of entries

0x1803

0x01

RW

VAR

Unsigned 32

$NODEID+0x00000480

Transmit PDO4 - COB-ID

0x1803

0x02

RW

VAR

Unsigned 8

0xFF

Transmit PDO4 - Transmission type: three modes are available for this PDO: "asynchronous" (255), "synchronously cyclic" (1-240), and "synchronously acyclic" (0)

0x1803

0x03

RW

VAR

Unsigned 16

0

Transmit PDO4 - Inhibit time: Minimum time between two transmissions; unit = 0.1 ms

0x1803

0x04

RW

VAR

Unsigned 8

0

Transmit PDO4 - Reserved

0x1803

0x05

RW

VAR

Unsigned 16

0

Transmit PDO4 - Event timer: In "asynchronous" mode, this object sets a minimum rate of transmission for this PDO; unit = 0.1 ms

Index

Sub Index

Access

Object Type

Data Type

Factory Setting

Description

0x1A00

0x00

RW

ARRAY

Unsigned 8

4

Transmit PDO1 mapping - Number of mapped objects

0x1A00

0x01

RW

VAR

Unsigned 32

0x20040610

Transmit PDO1 mapping 1 - mapped object: Reg [455]

0x1A00

0x02

RW

VAR

Unsigned 32

0x20040710

Transmit PDO1 mapping 2 - mapped object: Reg [456]

0x1A00

0x03

RW

VAR

Unsigned 32

0x20040810

Transmit PDO1 mapping 3 - mapped object: Reg [457]

0x1A00

0x04

RW

VAR

Unsigned 32

0x20040A10

Transmit PDO1 mapping 4 - mapped object: Reg [459]

0x1A01

0x00

RW

ARRAY

Unsigned 8

0

Transmit PDO2 mapping - Number of mapped objects

0x1A01

0x01

RW

VAR

Unsigned 32

0x00000000

Transmit PDO2 mapping 1 - mapped object: None by default

0x1A01

0x02

RW

VAR

Unsigned 32

0x00000000

Transmit PDO2 mapping 2 - mapped object: None by default

0x1A01

0x03

RW

VAR

Unsigned 32

0x00000000

Transmit PDO2 mapping 3 - mapped object: None by default

0x1A01

0x04

RW

VAR

Unsigned 32

0x00000000

Transmit PDO2 mapping 4 - mapped object: None by default

0x1A02

0x00

RW

ARRAY

Unsigned 8

0

Transmit PDO3 mapping - Number of mapped objects

0x1A02

0x01

RW

VAR

Unsigned 32

0x00000000

Transmit PDO3 mapping 1 - mapped object: None by default

0x1A02

0x02

RW

VAR

Unsigned 32

0x00000000

Transmit PDO3 mapping 2 - mapped object: None by default

0x1A02

0x03

RW

VAR

Unsigned 32

0x00000000

Transmit PDO3 mapping 3 - mapped object: None by default

0x1A02

0x04

RW

VAR

Unsigned 32

0x00000000

Transmit PDO3 mapping 4 - mapped object: None by default

0x1A03

0x00

RW

ARRAY

Unsigned 8

2

Transmit PDO4 mapping - Number of mapped objects

0x1A03

0x01

RW

VAR

Unsigned 32

0x30000320

Transmit PDO4 mapping 1 - mapped object: None by default

0x1A03

0x02

RW

VAR

Unsigned 32

0x30000420

Transmit PDO4 mapping 2 - mapped object: None by default

0x1A03

0x03

RW

VAR

Unsigned 32

0x00000000

Transmit PDO4 mapping 3 - mapped object: None by default

0x1A03

0x04

RW

VAR

Unsigned 32

0x00000000

Transmit PDO4 mapping 4 - mapped object: None by default

Register Map - Organization of Communication Variables

Introduction

Communication variables are listed in tables according to the group (such as identification, statistics, or monitoring). to which they belong. They are associated with an LTMR controller, which may or may not have an LTME expansion module attached.

Communication Variable Groups

Communication variables are grouped according to the following criteria:

Variable Groups

Registers

CANopen Addresses

Identification variables

00 to 99

2000 : 32 to 2000 : 61

Statistics variables

100 to 449

2001 : 01 to 2003 : 82

Monitoring variables

450 to 539

2004 : 01 to 2004 : 46

Configuration variables

540 to 699

2005 : 01 to 2007 : 32

Command variables

700 to 799

2008 : 01 to 2008 : 64

Custom Logic variables

1200 to 1399

200C : 01 to 200D : 64

Table Structure

Communication variables are listed in 5-column tables:

Column 1

Register (in decimal format)

Column 2

CANopen address (index : sub-index)

Column 3

Variable type Data Formats

Column 4

Variable name and access via Read-only or Read/Write requests

Column 5

Note: code for additional information

Note

The Note column gives a code for additional information.

Variables without a code are available for all hardware configurations, and without functional restrictions.

The code can be:

  • numerical (1 to 9), for specific hardware combinations

  • alphabetical (A to Z), for specific system behaviors.

If the Note is...

Then the Variable is...

1

available for the LTMR + LTMEV40 combination

2

always available but with a value equal to 0 if no LTMEV40 is connected

3-9

Not used

If the Note is...

Then...

A

the variable can be written only when the motor is OFF

B

the variable can be written only in configuration mode

C

the variable can be written only with no trip

D-Z

the variable is available for future exceptions

Unused Addresses

Unused addresses fall into three categories:

  • Not significant, in Read only tables, means that you should ignore the value read, whether equal to 0 or not.

  • Reserved, in Read/Write tables, means that you must write 0 in these variables.

  • Forbidden, means that read or write requests are rejected, that these addresses are not accessible.

Data Formats

Overview

The data format of a communication variable can be integer, Word, or Word[n], as described below. For more information about a variable size and format, refer to the Data Types.

Integer (Int, UInt, DInt, IDInt)

Integers fall into the following categories:

  • Int: signed integer using one register (16 bits)

  • UInt: unsigned integer using one register (16 bits)

  • DInt: signed double integer using 2 registers (32 bits)

  • UDInt: unsigned double integer using 2 registers (32 bits)

For all integer-type variables, the variable name is completed with its unit or format, if necessary.

Example:

Address 474, UInt, Frequency (x 0.01 Hz).

Word

Word: Set of 16 bits, where each bit or group of bits represents command, monitoring or configuration data.

Example:

Address 455, Word, System Status Register 1.

bit 0

System ready

bit 1

System ON

bit 2

System trip

bit 3

System alarm

bit 4

System tripped

bit 5

Trip reset authorized

bit 6

(Not significant)

bit 7

Motor running

bits 8-13

Motor average current ratio

bit 14

In remote

bit 15

Motor starting (in progress)

Word[n]

Word[n]: Data encoded on contiguous registers.

Examples:

Addresses 64 to 69, Word[6], Controller Commercial Reference (DT_CommercialReference).

Addresses 655 to 658, Word[4], (DT_DateTime).

Data Types

Overview

Data types are specific variable formats which are used to complement the description of internal formats (for instance, in case of a structure or of an enumeration). The generic format of data types is DT_xxx.

List of Data Types

Here is the list of the most commonly used data types:

  • DT_ACInputSetting

  • DT_CommercialReference

  • DT_DateTime

  • DT_ExtBaudRate

  • DT_ExtParity

  • DT_FaultCode

    Change this to DT_TripCode?
  • DT_FirmwareVersion

  • DT_Language5

  • DT_OutputFallbackStrategy

  • DT_PhaseNumber

  • DT_ResetMode

  • DT_WarningCode

    Change this to DT_AlarmCode?

These data types are described in the following tables.

DT_ACInputSetting

DT_ACInputSetting format is an enumeration that improves AC input detection:

Value

Description

0

None (factory setting)

1

< 170 V 50 Hz

2

< 170 V 60 Hz

3

> 170 V 50 Hz

4

> 170 V 60 Hz

DT_CommercialReference

DT_CommercialReference format is Word[6] and indicates a Commercial Reference:

Register

MSB

LSB

Register N

character 1

Character 2

Register N+1

character 3

Character 4

Register N+2

character 5

Character 6

Register N+3

character 7

Character 8

Register N+4

character 9

Character 10

Register N+5

character 11

Character 12

Example:

Addresses 64 to 69, Word[6], Controller Commercial Reference.

If Controller Commercial Reference = LTMR:

Register

MSB

LSB

64

L

T

65

M

(space)

66

R

67

68

69

DT_DateTime

DT_DateTime format is Word[4] and indicates Date and Time:

Register

Bits 12-15

Bits 8-11

Bits 4-7

Bits 0-3

Register N

S

S

0

0

Register N+1

H

H

m

m

Register N+2

M

M

D

D

Register N+3

Y

Y

Y

Y

Where:

  • S = second

    The format is two BCD digits.

    The value range is [00-59] in BCD.

  • 0 = unused

  • H = hour

    The format is two BCD digits.

    The value range is [00-23] in BCD.

  • m = minute

    The format is two BCD digits.

    The value range is [00-59] in BCD.

  • M = month

    The format is two BCD digits.

    The value range is [01-12] in BCD.

  • D = day

    The format is two BCD digits.

    The value range is (in BCD):

    [01-31] for months 01, 03, 05, 07, 08, 10, 12

    [01-30] for months 04, 06, 09, 11

    [01-29] for month 02 in a leap year

    [01-28] for month 02 in a non-leap year.

  • Y = year

    The format is four Binary Coded Decimal (BCD) digits.

    The value range is [2006-2099] in BCD.

Data entry format and value range are:

Data Entry Format

DT#YYYY-MM-DD-HH:mm:ss

Minimum value

DT#2006-01-01:00:00:00

January 1, 2006

Maximum value

DT#2099-12-31-23:59:59

December 31, 2099

Note: If you give values outside the limits, the system will return a detected error.

Example:

Addresses 655 to 658, Word[4], Date and Time setting.

If date is September 4, 2008 at 7 a.m., 50 minutes and 32 seconds:

Register

15 12

11 8

7 4

3 0

655

3

2

0

0

656

0

7

5

0

657

0

9

0

4

658

2

0

0

8

With data entry format: DT#2008-09-04-07:50:32.

DT_ExtBaudRate

DT_ExtbaudRate depends on the bus used:

DT_ModbusExtBaudRate format is an enumeration of possible baud rates with Modbus network:

Value

Description

1200

1200 Baud

2400

2400 Baud

4800

4800 Baud

9600

9600 Baud

19200

19,200 Baud

65535

Autodetection (factory setting)

DT_ProfibusExtBaudRate format is an enumeration of possible baud rates with PROFIBUS DP network:

Value

Description

65535

Autobaud (factory setting)

DT_DeviceNetExtBaudRate format is an enumeration of possible baud rates with DeviceNet network:

Value

Description

0

125 kBaud

1

250 kBaud

2

500 kBaud

3

Autobaud (factory setting)

DT_CANopenExtBaudRate format is an enumeration of possible baud rates with CANopen network:

Value

Description

0

10 kBaud

1

20 kBaud

2

50 kBaud

3

125 kBaud

4

250 kBaud (factory setting)

5

500 kBaud

6

800 kBaud

7

1000 kBaud

8

Autobaud

9

Factory setting

DT_ExtParity

DT_ExtParity depends on the bus used:

DT_ModbusExtParity format is an enumeration of possible parities with Modbus network:

Value

Description

0

None

1

Even

2

Odd

DT_FaultCode
Change this to DT_TripCode?

DT_FaultCode

Change this to DT_TripCode?
format is an enumeration of trip codes:

Trip Code

Description

0

No detected error

3

Ground current

4

Thermal overload

5

Long start

6

Jam

7

Current phase imbalance

8

Undercurrent

10

Test

11

HMI port detected error

12

HMI port communication loss

13

Network port internal detected error

16

External trip

18

ON-OFF diagnostic

19

Wiring diagnostic

20

Overcurrent

21

Current phase loss

22

Current phase reversal

23

Motor temp sensor

24

Voltage phase imbalance

25

Voltage phase loss

26

Voltage phase reversal

27

Undervoltage

28

Overvoltage

29

Underpower

30

Overpower

31

Under power factor

32

Over power factor

33

LTME configuration

34

Temperature sensor short-circuit

35

Temperature sensor open-circuit

36

CT reversal

37

Out of boundary CT ratio

46

Start check

47

Run checkback

48

Stop check

49

Stop checkback

51

Controller internal temperature detected error

55

Controller internal detected error (Stack overflow)

56

Controller internal detected error (RAM detected error)

57

Controller internal detected error (RAM checksum detected error)

58

Controller internal detected error (Hardware watchdog trip)

60

L2 current detected in single-phase mode

64

Non-volatile memory detected error

65

Expansion module communication detected error

66

Stuck reset button

67

Logic function detected error

100-104

Network port internal detected error

109

Network port comm detected error

111

Fast device replacement trip

555

Network port configuration detected error

DT_FirmwareVersion

DT_FirmwareVersion format is an XY000 array that describes a firmware revision:

  • X = major revision

  • Y = minor revision.

Example:

Address 76, UInt, Controller firmware version.

DT_Language5

DT_Language5 format is an enumeration used for language display:

Language Code

Description

1

English (factory setting)

2

Français

4

Español

8

Deutsch

16

Italiano

Example:

Address 650, Word, HMI language.

DT_OutputFallbackStrategy

DT_OutputFallbackStrategy format is an enumeration of motor output states when loosing communication.

Value

Description

Motor Modes

0

Hold LO1 LO2

For all modes

1

Run

For 2-step mode only

2

LO1, LO2 Off

For all modes

3

LO1, LO2 On

Only for overload, independent and custom operating modes

4

LO1 On

For all modes except 2-step

5

LO2 On

For all modes except 2-step

DT_PhaseNumber

DT_PhaseNumber format is an enumeration, with only 1 bit activated:

Value

Description

1

1 phase

2

3 phases

DT_ResetMode

DT_ResetMode format is an enumeration of possible modes for thermal trip reset:

Value

Description

1

Manual or HMI

2

Remote by network

4

Automatic

DT_WarningCode
Change this to DT_AlarmCode?

DT_WarningCode

Change this to DT_AlarmCode?
format is an enumeration of alarm codes:

Alarm Code

Description

0

No alarm

3

Ground current

4

Thermal overload

5

Long start

6

Jam

7

Current phase imbalance

8

Undercurrent

10

HMI port

11

LTMR internal temperature

18

Diagnostic

19

Wiring

20

Overcurrent

21

Current phase loss

23

Motor temp sensor

24

Voltage phase imbalance

25

Voltage phase loss

27

Undervoltage

28

Overvoltage

29

Underpower

30

Overpower

31

Under power factor

32

Over power factor

33

LTME configuration

46

Start check

47

Run checkback

48

Stop check

49

Stop checkback

109

Network port comm loss

555

Network port configuration

Identification Variables

Identification Variables

Identification variables are described in the following table:

Register

CANopen Address

Variable Type

Read-only Variables

Note

0-34

2000 : 03 - 2000 : 28

(Not significant)

 

35-40

2000 : 23 - 2000 : 29

Word[6]

Expansion commercial reference DT_CommercialReference

1

41-45

2000 :2A - 2000 : 2E

Word[5]

Expansion serial number

1

46

2000 : 2F

UInt

Expansion ID code

1

47

2000 : 30

UInt

Expansion firmware version DT_FirmwareVersion

1

48

2000 : 31

UInt

Expansion compatibility code

1

49-60

2000 : 32 - 2000 : 3D

(Not significant)

 

61

2000 : 3E

Ulnt

Network port ID code

 

62

2000 : 3F

Ulnt

Network port firmware version DT_FirmwareVersion

 

63

2000 : 40

Ulnt

Network port compatibility code

 

64-69

2000 : 41 - 2000 : 46

Word[6]

Controller commercial reference DT_CommercialReference

 

70-74

2000 : 47 - 2000 : 4B

Word[5]

Controller serial number

 

75

2000 : 4C

Ulnt

Controller ID code

 

76

2000 : 4D

Ulnt

Controller firmware version DT_FirmwareVersion

 

77

2000 : 4E

Ulnt

Controller compatibility code

 

78

2000 : 4F

Ulnt

Current scale ratio (0.1 %)

 

79

2000 : 50

Ulnt

Current sensor max

 

80

2000 : 51

 

(Not significant)

 

81

2000 : 52

Ulnt

Current range max (x 0.1 A)

 

82-94

2000 : 53 - 2000 : 58

 

(Not significant)

 

95

2000 : 60

Ulnt

Load CT ratio (x 0.1 A)

 

96

2000 : 61

Ulnt

Full load current max (maximum FLC range, FLC = Full Load Current) (x 0.1 A)

 

97-99

2000 : 62 - 2000 : 64

Ulnt

(Forbidden)

 

Statistics Variables

Statistics Overview

Statistics variables are grouped according to the following criteria. Trip statistics are described in a main table and in an extension table.

Statistics Variable Groups

Register

CANopen Addresses

Global statistics

100 to 121

2001 : 01 to 2001 : 16

LTM monitoring statistics

122 to 149

2001 : 17 to 2001 : 32

Last trip statistics

and extension

150 to 179

300 to 309

2002 : 01 to 2002 : 1E

2003 : 01 to 2003 : 0A

Trip n-1 statistics

and extension

180 to 209

330 to 339

2002 : 1F to 2002 : 3C

2003 : 1F to 2003 : 28

Trip n-2 statistics

and extension

210 to 239

360 to 369

2002 : 3D to 2002 : 5A

2003 : 3D to 2003 : 46

Trip n-3 statistics

and extension

240 to 269

390 to 399

2002 : 5B to 2002 : 78

2003 : 5B to 2003 : 64

Trip n-4 statistics

and extension

270 to 299

420 to 429

2002 : 79 to 2002 : 96

2003 : 79 to 2003 : 82

Global Statistics

The global statistics are described in the following table:

Register

CANopen Address

Variable Type

Read-only Variables

Note

100-101

2001 : 01 - 2001 : 02

(Not significant)

 

102

2001 : 03

Ulnt

Ground current trips count

 

103

2001 : 04

Ulnt

Thermal overload trips count

 

104

2001 : 05

Ulnt

Long start trips count

 

105

2001 : 06

Ulnt

Jam trips count

 

106

2001 : 07

Ulnt

Current phase imbalance trips count

 

107

2001 : 08

Ulnt

Undercurrent trips count

 

109

2001 : 0A

Ulnt

HMI port trips count

 

110

2001 : 0B

Ulnt

Controller internal trips count

 

111

2001 : 0C

Ulnt

Internal port trips count

 

112

2001 : 0D

 

(Not significant)

 

113

2001 : 0E

Ulnt

Network port config trips count

 

114

2001 : 0F

Ulnt

Network port trips count

 

115

2001 : 10

Ulnt

Auto-resets count

 

116

2001 : 11

Ulnt

Thermal overload alarms count

 

117-118

2001 : 12 - 2001 : 13

UDlnt

Motor starts count

 

119-120

2001 : 14 - 2001 : 15

UDlnt

Operating time (s)

 

121

2001 : 16

lnt

Controller internal temperature max (°C)

 

LTM Monitoring Statistics

The LTM monitoring statistics are described in the following table:

Register

CANopen Address

Variable Type

Read-only Variables

Note

122

2001 : 17

Ulnt

Trips count

 

123

2001 : 18

Ulnt

Alarms count

 

124-125

2001 : 19 - 2001 : 1A

UDlnt

Motor LO1 closings count

 

126-127

2001 : 1B - 2001 : 1C

UDlnt

Motor LO2 closings count

 

128

2001 : 1D

Ulnt

Diagnostic trips count

 

129

2001 : 1E

 

(Reserved)

 

130

2001 : 1F

Ulnt

Overcurrent trips count

 

131

2001 : 20

Ulnt

Current phase loss trips count

 

132

2001 : 21

Ulnt

Motor temperature sensor trips count

 

133

2001 : 22

Ulnt

Voltage phase imbalance trips count

1

134

2001 : 23

Ulnt

Voltage phase loss trips count

1

135

2001 : 24

Ulnt

Wiring trips count

1

136

2001 : 25

Ulnt

Undervoltage trips count

1

137

2001 : 26

Ulnt

Overvoltage trips count

1

138

2001 : 27

Ulnt

Underpower trips count

1

139

2001 : 28

Ulnt

Overpower trips count

1

140

2001 : 29

Ulnt

Under power factor trips count

1

141

2001 : 2A

Ulnt

Over power factor trips count

1

142

2001 : 2B

Ulnt

Load sheddings count

1

143-144

2001 : 2C - 2001 : 2D

UDlnt

Active power consumption (kWh)

1

145-146

2001 : 2E - 2001 : 2F

UDlnt

Reactive power consumption (kVARh)

1

147

2001 : 30

Ulnt

Auto restart immediate count

148

2001 : 31

Ulnt

Auto restart delayed count

149

2001 : 32

Ulnt

Auto restart manual count

 

Last Trip (n-0) Statistics

The last trip statistics are completed by variables at addresses 300 to 309.

Register

CANopen Address

Variable Type

Read-only Variables

Note

150

2002 : 01

Ulnt

trip code n-0

 

151

2002 : 02

Ulnt

Motor full load current ratio n-0 (% FLC max)

 

152

2002 : 03

Ulnt

Thermal capacity level n-0 (% trip level)

 

153

2002 : 04

Ulnt

Average current ratio n-0 (% FLC)

 

154

2002 : 05

Ulnt

L1 current ratio n-0 (% FLC)

 

155

2002 : 06

Ulnt

L2 current ratio n-0 (% FLC)

 

156

2002 : 07

Ulnt

L3 current ratio n-0 (% FLC)

 

157

2002 : 08

Ulnt

Ground current ratio n-0 (x 0.1 % FLC min)

 

158

2002 : 09

Ulnt

Full load current max n-0 (x 0.1 A)

 

159

2002 : 0A

Ulnt

Current phase imbalance n-0 (%)

 

160

2002 : 0B

Ulnt

Frequency n-0 (x 0.1 Hz)

2

161

2002 : 0C

Ulnt

Motor temperature sensor n-0 (x 0.1 Ω)

 

162-165

2002 : 0D - 2002 : 10

Word[4]

Date and time n-0 DT_DateTime

 

166

2002 : 11

Ulnt

Average voltage n-0 (V)

1

167

2002 : 12

Ulnt

L3-L1 voltage n-0 (V)

1

168

2002 : 13

Ulnt

L1-L2 voltage n-0 (V)

1

169

2002 : 14

Ulnt

L2-L3 voltage n-0 (V)

1

170

2002 : 15

Ulnt

Voltage phase imbalance n-0 (%)

1

171

2002 : 16

Ulnt

Active power n-0 (x 0.1 kWh)

1

172

2002 : 17

Ulnt

Power factor n-0 (x 0.01)

1

173-179

2002 : 18 - 2002 : 1E

 

(Not significant)

 

N-1 Trip Statistics

The n-1 trip statistics are completed by variables at addresses 330 to 339.

Register

CANopen Address

Variable Type

Read-only Variables

Note

180

2002 : 1F

Ulnt

Trip code n-1

 

181

2002 : 20

Ulnt

Motor full load current ratio n-1 (% FLC max)

 

182

2002 : 21

Ulnt

Thermal capacity level n-1 (% trip level)

 

183

2002 : 22

Ulnt

Average current ratio n-1 (% FLC)

 

184

2002 : 23

Ulnt

L1 current ratio n-1 (% FLC)

 

185

2002 : 24

Ulnt

L2 current ratio n-1 (% FLC)

 

186

2002 : 25

Ulnt

L3 current ratio n-1 (% FLC)

 

187

2002 : 26

Ulnt

Ground current ratio n-1 (x 0.1 % FLC min)

 

188

2002 : 27

Ulnt

Full load current max n-1 (x 0.1 A)

 

189

2002 : 28

Ulnt

Current phase imbalance n-1 (%)

 

190

2002 : 29

Ulnt

Frequency n-1 (x 0.1 Hz)

2

191

2002 : 2A

Ulnt

Motor temperature sensor n-1 (x 0.1 Ω)

 

192-195

2002 : 2B - 2002 : 2E

Word[4]

Date and time n-1 DT_DateTime

 

196

2002 : 2F

Ulnt

Average voltage n-1 (V)

1

197

2002 : 30

Ulnt

L3-L1 voltage n-1 (V)

1

198

2002 : 31

Ulnt

L1-L2 voltage n-1 (V)

1

199

2002 : 32

Ulnt

L2-L3 voltage n-1 (V)

1

200

2002 : 33

Ulnt

Voltage phase imbalance n-1 (%)

1

201

2002 : 34

Ulnt

Active power n-1 (x 0.1 kWh)

1

202

2002 : 35

Ulnt

Power factor n-1 (x 0.01)

1

203-209

2002 : 36 - 2002 : 3C

 

(Not significant)

 

N-2 Trip Statistics

The n-2 trip statistics are completed by variables at addresses 360 to 369.

Register

CANopen Address

Variable Type

Read-only Variables

Note

210

2002 : 3D

Ulnt

Trip code n-2

 

211

2002 : 3E

Ulnt

Motor full load current ratio n-2 (% FLC max)

 

212

2002 : 3F

Ulnt

Thermal capacity level n-2 (% trip level)

 

213

2002 : 40

Ulnt

Average current ratio n-2 (% FLC)

 

214

2002 : 41

Ulnt

L1 current ratio n-2 (% FLC)

 

215

2002 : 42

Ulnt

L2 current ratio n-2 (% FLC)

 

216

2002 : 43

Ulnt

L3 current ratio n-2 (% FLC)

 

217

2002 : 44

Ulnt

Ground current ratio n-2 (x 0.1 % FLC min)

 

218

2002 : 45

Ulnt

Full load current max n-2 (x 0.1 A)

 

219

2002 : 46

Ulnt

Current phase imbalance n-2 (%)

 

220

2002 : 47

Ulnt

Frequency n-2 (x 0.1 Hz)

2

221

2002 : 48

Ulnt

Motor temperature sensor n-2 (x 0.1 Ω)

 

222-225

2002 : 49 - 2002 : 4C

Word[4]

Date and time n-2 DT_DateTime

 

226

2002 : 4D

Ulnt

Average voltage n-2 (V)

1

227

2002 : 4E

Ulnt

L3-L1 voltage n-2 (V)

1

228

2002 : 4F

Ulnt

L1-L2 voltage n-2 (V)

1

229

2002 : 50

Ulnt

L2-L3 voltage n-2 (V)

1

230

2002 : 51

Ulnt

Voltage phase imbalance n-2 (%)

1

231

2002 : 52

Ulnt

Active power n-2 (x 0.1 kWh)

1

232

2002 : 53

Ulnt

Power factor n-2 (x 0.01)

1

233-239

2002 : 54 - 2002 : 5A

 

(Not significant)

 

N-3 Trip Statistics

The n-3 trip statistics are completed by variables at addresses 390 to 399.

Register

CANopen Address

Variable Type

Read-only Variables

Note

240

2002 : 5B

Ulnt

Trip code n-3

 

241

2002 : 5C

Ulnt

Motor full load current ratio n-3 (% FLC max)

 

242

2002 : 5D

Ulnt

Thermal capacity level n-3 (% trip level)

 

243

2002 : 5E

Ulnt

Average current ratio n-3 (% FLC)

 

244

2002 : 5F

Ulnt

L1 current ratio n-3 (% FLC)

 

245

2002 : 60

Ulnt

L2 current ratio n-3 (% FLC)

 

246

2002 : 61

Ulnt

L3 current ratio n-3 (% FLC)

 

247

2002 : 62

Ulnt

Ground current ratio n-3 (x 0.1 % FLC min)

 

248

2002 : 63

Ulnt

Full load current max n-3 (0.1 A)

 

249

2002 : 64

Ulnt

Current phase imbalance n-3 (%)

 

250

2002 : 65

Ulnt

Frequency n-3 (x 0.1 Hz)

2

251

2002 : 66

Ulnt

Motor temperature sensor n-3 (x 0.1 Ω)

 

252-255

2002 : 67 - 2002 : 6A

Word[4]

Date and time n-3 DT_DateTime

 

256

2002 : 6B

Ulnt

Average voltage n-3 (V)

1

257

2002 : 6C

Ulnt

L3-L1 voltage n-3 (V)

1

258

2002 : 6D

Ulnt

L1-L2 voltage n-3 (V)

1

259

2002 : 6E

Ulnt

L2-L3 voltage n-3 (V)

1

260

2002 : 6F

Ulnt

Voltage phase imbalance n-3 (%)

1

261

2002 : 70

Ulnt

Active power n-3 (x 0.1 kWh)

1

262

2002 : 71

Ulnt

Power factor n-3 (x 0.01)

1

263-269

2002 : 72 - 2002 : 78

 

(Not significant)

 

N-4 Trip Statistics

The n-4 trip statistics are completed by variables at addresses 420 to 429.

Register

CANopen Address

Variable Type

Read-only Variables

Note

270

2002 : 79

Ulnt

Trip code n-4

 

271

2002 : 7A

Ulnt

Motor full load current ratio n-4 (% FLC max)

 

272

2002 : 7B

Ulnt

Thermal capacity level n-4 (% trip level)

 

273

2002 : 7C

Ulnt

Average current ratio n-4 (% FLC)

 

274

2002 : 7D

Ulnt

L1 current ratio n-4 (% FLC)

 

275

2002 : 7E

Ulnt

L2 current ratio n-4 (% FLC))

 

276

2002 : 7F

Ulnt

L3 current ratio n-4 (% FLC)

 

277

2002 : 80

Ulnt

Ground current ratio n-4 (x 0.1 % FLC min)

 

278

2002 : 81

Ulnt

Full load current max n-4 (x 0.1 A)

 

279

2002 : 82

Ulnt

Current phase imbalance n-4 (%)

 

280

2002 : 83

Ulnt

Frequency n-4 (x 0.1 Hz)

2

281

2002 : 84

Ulnt

Motor temperature sensor n-4 (x 0.1 Ω)

 

282-285

2002 : 85 - 2002 : 88

Word[4]

Date and time n-4 DT_DateTime

 

286

2002 : 89

Ulnt

Average voltage n-4 (V)

1

287

2002 : 8A

Ulnt

L3-L1 voltage n-4 (V)

1

288

2002 : 8B

Ulnt

L1-L2 voltage n-4 (V)

1

289

2002 : 8C

Ulnt

L2-L3 voltage n-4 (V)

1

290

2002 : 8D

Ulnt

Voltage phase imbalance n-4 (x 1%)

1

291

2002 : 8E

Ulnt

Active power n-4 (x 0.1 kWh)

1

292

2002 : 8F

Ulnt

Power factor n-4 (x 0.01)

1

293-299

2002 : 90 - 2002 : 96

 

(Not significant)

 

Last Trip (n-0) Statistics Extension

The last trip main statistics are listed at addresses 150-179.

Register

CANopen Address

Variable Type

Read-only Variables

Note

300-301

2003 : 01 - 2003 : 02

UDlnt

Average current n-0 (x 0.01 A)

 

302-303

2003 : 03 - 2003 : 04

UDlnt

L1 current n-0 (x 0.01 A)

 

304-305

2003 : 05 - 2003 : 06

UDlnt

L2 current n-0 (x 0.01 A)

 

306-307

2003 : 07 - 2003 : 08

UDlnt

L3 current n-0 (x 0.01 A)

 

308-309

2003 : 09 - 2003 : 0A

UDlnt

Ground current n-0 (mA)

 

310

2003 : 0B

Ulnt

Motor temperature sensor degree n-0 (°C)

 

N-1 Trip Statistics Extension

The n-1 trip main statistics are listed at addresses 180-209.

Register

CANopen Address

Variable Type

Read-only Variables

Note

330-331

2003 : 1F - 2003 : 20

UDlnt

Average current n-1 (x 0.01 A)

 

332-333

2003 : 21 - 2003 : 22

UDlnt

L1 current n-1 (x 0.01 A)

 

334-335

2003 : 23 - 2003 : 24

UDlnt

L2 current n-1 (x 0.01 A)

 

336-337

2003 : 25 - 2003 : 26

UDlnt

L3 current n-1 (x 0.01 A)

 

338-339

2003 : 27 - 2003 : 28

UDlnt

Ground current n-1 (mA)

 

340

2003 : 29

Ulnt

Motor temperature sensor degree n-1 (°C)

 

N-2 Trip Statistics Extension

The n-2 trip main statistics are listed at addresses 210-239.

Register

CANopen Address

Variable Type

Read-only Variables

Note

360-361

2003 : 3D - 2003 : 3E

UDlnt

Average current n-2 (x 0.01 A)

 

362-363

2003 : 3F - 2003 : 40

UDlnt

L1 current n-2 (x 0.01 A)

 

364-365

2003 : 41 - 2003 : 42

UDlnt

L2 current n-2 (x 0.01 A)

 

366-367

2003 : 43 - 2003 : 44

UDlnt

L3 current n-2 (x 0.01 A)

 

368-369

2003 : 45 - 2003 : 46

UDlnt

Ground current n-2 (mA)

 

370

2003 : 47

Ulnt

Motor temperature sensor degree n-2 (°C)

 

N-3 Trip Statistics Extension

The n-3 trip main statistics are listed at addresses 240-269.

Register

CANopen Address

Variable Type

Read-only Variables

Note

390-391

2003 : 5B - 2003 : 5C

UDlnt

Average current n-3 (x 0.01 A)

 

392-393

2003 : 5D - 2003 : 5E

UDlnt

L1 current n-3 (x 0.01 A)

 

394-395

2003 : 5F - 2003 : 60

UDlnt

L2 current n-3 (x 0.01 A)

 

396-397

2003 : 61 - 2003 : 62

UDlnt

L3 current n-3 (x 0.01 A)

 

398-399

2003 : 63 - 2003 : 64

UDlnt

Ground current n-3 (mA)

 

400

2003 : 65

Ulnt

Motor temperature sensor degree n-3 (°C)

 

N-4 Trip Statistics Extension

The n-4 trip main statistics are listed at addresses 270-299.

Register

CANopen Address

Variable Type

Read-only Variables

Note

420-421

2003 : 79 - 2003 : 7A

UDlnt

Average current n-4 (x 0.01 A)

 

422-423

2003 : 7B9 - 2003 : 7C

UDlnt

L1 current n-4 (x 0.01 A)

 

424-425

2003 : 7D - 2003 : 7E

UDlnt

L2 current n-4 (x 0.01 A)

 

426-427

2003 : 7F - 2003 : 80

UDlnt

L3 current n-4 (x 0.01 A)

 

428-429

2003 : 81 - 2003 : 82

UDlnt

Ground current n-4 (mA)

 

430

2003 : 83

Ulnt

Motor temperature sensor degree n-4 (°C)

 

Monitoring Variables

Monitoring Variables

Monitoring variables are described in the following table:

Monitoring Variable Groups

Modbus Addresses

CANopen Addresses

Monitoring of trips

450 to 454

2004 : 01 to 2004 : 05

Monitoring of status

455 to 459

2004 : 06 to 2004 : 0A

Monitoring of alarms

460 to 464

2004 : 0B to 2004 : 0F

Monitoring of measurements

465 to 539

2004 : 10 to 2004 : 5A

Register

CANopen Address

Variable Type

Read-only Variables

Note

450

2004 : 01

Ulnt

Minimum wait time (s)

 

451

2004 : 02

Ulnt

Trip code (code of the last trip, or of the trip that takes priority) DT_FaultCode

 

452

2004 : 03

Word

Trip register 1

 

bits 0-1 (Reserved)

 

bit 2 Ground current trip

 

bit 3 Thermal overload trip

 

bit 4 Long start trip

 

bit 5 Jam trip

 

bit 6 Current phase imbalance trip

 

bit 7 Undercurrent trip

 

bit 8 (Reserved)

 

bit 9 Test trip

 

bit 10 HMI port trip

 

bit 11 Controller internal trip

 

bit 12 Internal port trip

 

bit 13 (Not significant)

 

bit 14 Network port config trip

 

bit 15 Network port trip

 

453

2004 : 04

Word

Trip register 2

 

bit 0 External system trip

 

bit 1 Diagnostic trip

 

bit 2 Wiring trip

 

bit 3 Overcurrent trip

 

bit 4 Current phase loss trip

 

bit 5 Current phase reversal trip

 

bit 6 Motor temperature sensor trip

1

bit 7 Voltage phase imbalance trip

1

bit 8 Voltage phase loss trip

1

bit 9 Voltage phase reversal trip

1

bit 10 Undervoltage trip

1

bit 11 Overvoltage trip

1

bit 12 Underpower trip

1

bit 13 Overpower trip

1

bit 14 Under power factor trip

1

bit 15 Over power factor trip

1

454

2004 : 05

Word

Trip register 3

 

bit 0 LTME configuration trip

 

bits 1-15 (Reserved)

 

455

2004 : 06

Word

System status register 1

 

bit 0 System ready

 

bit 1 System on

 

bit 2 System trip

 

bit 3 System alarm

 

bit 4 System tripped

 

bit 5 Trip reset authorized

 

bit 6 Controller power

 

bit 7 Motor running (with detection of a current if greater than 10% FLC)

 

bits 8-13 Motor average current ratio

32 = 100% FLC - 63 = 200% FLC

 

bit 14 In remote

 

bit 15 Motor starting (start in progress)

0 = descending current is less than 150% FLC

1 = ascending current is greater than 10% FLC

 

456

2004 : 07

Word

System status register 2

 

bit 0 Auto-reset active

 

bit 1 (Not significant)

 

bit 2 Trip power cycle requested

 

bit 3 Motor restart time undefined

 

bit 4 Rapid cycle lockout

 

bit 5 Load shedding

1

bit 6 Motor speed

0 = FLC1 setting is use

1 = FLC2 setting is used

 

bit 7 HMI port comm loss

 

bit 8 Network port comm loss

 

bit 9 Motor transition lockout

 

bits 10-15 (Not significant)

 

457

2004 : 08

Word

Logic inputs status

 

bit 0 Logic input 1

 

bit 1 Logic input 2

 

bit 2 Logic input 3

 

bit 3 Logic input 4

 

bit 4 Logic input 5

 

bit 5 Logic input 6

 

bit 6 Logic input 7

 

bit 7 Logic input 8

1

bit 8 Logic input 9

1

bit 9 Logic input 10

1

bit 10 Logic input 11

1

bit 11 Logic input 12

1

bit 12 Logic input 13

1

bit 13 Logic input 14

1

bit 14 Logic input 15

1

bit 15 Logic input 16

1

458

2004 : 09

Word

Logic outputs status

 

bit 0 Logic output 1

 

bit 1 Logic output 2

 

bit 2 Logic output 3

 

bit 3 Logic output 4

 

bit 4 Logic output 5

1

bit 5 Logic output 6

1

bit 6 Logic output 7

1

bit 7 Logic output 8

1

bits 8-15 (Reserved)

 

459

2004 : 0A

Word

I/O status

 

bit 0 Input 1

 

bit 1 Input 2

 

bit 2 Input 3

 

bit 3 Input 4

 

bit 4 Input 5

 

bit 5 Input 6

 

bit 6 Input 7

 

bit 7 Input 8

 

bit 8 Input 9

 

bit 9 Input 10

 

bit 10 Input 11

 

bit 11 Input 12

 

bit 12 Output 1 (13-14)

 

bit 13 Output 2 (23-24)

 

bit 14 Output 3 (33-34)

 

bit 15 Output 4 (95-96, 97-98)

 

460

2004 : 0B

UInt

Alarm code DT_WarningCode

 

461

2004 : 0C

Word

Alarm register 1

 

bits 0-1 (Not significant)

 

bit 2 Ground current alarm

 

bit 3 Thermal overload alarm

 

bit 4 (Not significant)

 

bit 5 Jam alarm

 

bit 6 Current phase imbalance alarm

 

bit 7 Undercurrent alarm

 

bits 8-9 (Not significant)

 

bit 10 HMI port alarm

 

bit 11 Controller internal temperature alarm

 

bits 12-14 (Not significant)

 

bit 15 Network port alarm

 

462

2004 : 0D

Word

Alarm register 2

 

bit 0 (Not significant)

 

bit 1 Diagnostic alarm

 

bit 2 (Reserved)

 

bit 3 Overcurrent alarm

 

bit 4 Current phase loss alarm

 

bit 5 Current phase reversal alarm

 

bit 6 Motor temperature sensor alarm

 

bit 7 Voltage phase imbalance alarm

1

bit 8 Voltage phase loss alarm

1

bit 9 (Not significant)

bit 10 Undervoltage alarm

1

bit 11 Overvoltage alarm

1

bit 12 Underpower alarm

1

bit 13 Overpower alarm

1

bit 14 Under power factor alarm

1

bit 15 Over power factor alarm

1

463

2004 : 0E

Word

Alarm register 3

 

bit 0 LTME configuration alarm

 

bits 1-15 (Reserved)

 

464

2004 : 0F

 

Motor temperature sensor degree (°C)

 

465

2004 : 10

UInt

Thermal capacity level (% trip level)

 

466

2004 : 11

UInt

Average current ratio (% FLC)

 

467

2004 : 12

UInt

L1 current ratio (% FLC)

 

468

2004 : 13

UInt

L2 current ratio (% FLC)

 

469

2004 : 14

UInt

L3 current ratio (% FLC)

 

470

2004 : 15

UInt

Ground current ratio (x 0.1 % FLC min)

 

471

2004 : 16

UInt

Current phase imbalance (%)

 

472

2004 : 17

Int

Controller internal temperature (°C)

 

473

2004 : 18

UInt

Controller config checksum

 

474

2004 : 19

UInt

Frequency (x 0.01 Hz)

2

475

2004 : 1A

UInt

Motor temperature sensor (x 0.1 Ω)

 

476

2004 : 1B

UInt

Average voltage (V)

1

477

2004 : 1C

UInt

L3-L1 voltage (V)

1

478

2004 : 1D

UInt

L1-L2 voltage (V)

1

479

2004 : 1E

UInt

L2-L3 voltage (V)

1

480

2004 : 1F

UInt

Voltage phase imbalance (%)

1

481

2004 : 20

UInt

Power factor (x 0.01)

1

482

2004 : 21

UInt

Active power (x 0.1 kW)

1

483

2004 : 22

UInt

Reactive power (x 0.1 kVAR)

1

484

2004 : 23

Word

Auto restart status register

bit 0 Voltage dip occurred

 

bit 1 Voltage dip detection

 

bit 2 Auto restart immediate condition

 

bit 3 Auto restart delayed condition

 

bit 4 Auto restart manual condition

 

bits 5-15 (Not significant)

 

485-489

2004 : 24 - 2004 : 28

 

(Not significant)

 

490

2004 : 29

Word

Network port status

 

bit 0 Network port communicating

 

bit 1 Network port connected

 

bit 2 Network port self-testing

 

bit 3 Network port self-detecting

 

bit 4 Network port bad config

 

bits 5-15 (Not significant)

 

491

2004 : 2A

UInt

network port baud rate DT_ExtBaudRate

 

492

2004 : 2B

 

(Not significant)

 

493

2004 : 2C

UInt

Network port parity DT_ExtParity

 

494-499

2004 : 2D - 2004 : 32

 

(Not significant)

 

500-501

2004 : 33 - 2004 : 34

UDInt

Average current (x 0.01 A)

 

502-503

2004 : 35 - 2004 : 36

UDInt

L1 current (x 0.01 A)

 

504-505

2004 : 37 - 2004 : 38

UDInt

L2 current (x 0.01 A)

 

506-507

2004 : 39 - 2004 : 3A

UDInt

L3 current (x 0.01 A)

 

508-509

2004 : 3B - 2004 : 3C

UDInt

Ground current (mA)

 

510

2004 : 3D

UInt

Controller port ID

 

511

2004 : 3E

UInt

Time to trip (x 1 s)

 

512

2004 : 3F

UInt

Motor last start current ratio (% FLC)

 

513

2004 : 40

UInt

Motor last start duration (s)

 

514

2004 : 41

UInt

Motor starts per hour count

 

515

2004 : 42

Word

Phase imbalances register

 

bit 0 L1 current highest imbalance

 

bit 1 L2 current highest imbalance

 

bit 2 L3 current highest imbalance

 

bit 3 L1-L2 voltage highest imbalance

1

bit 4 L2-L3 voltage highest imbalance

1

bit 5 L3-L1 voltage highest imbalance

1

bits 6-15 (Not significant)

 

516-523

2004 : 43 - 2004 : 4A

UInt

(Reserved)

1

524-539

2004 : 4B - 2004 : 5A

UInt

(Forbidden)

1

Configuration Variables

Configuration Variables

Configuration variables are described in the following table:

Configuration Variable Groups

Modbus Addresses

CANopen Addresses

Configuration

540 to 649

2005 : 01 to 2006 : 32

Setting

650 to 699

2007 : 01 to 2007 : 32

Register

CANopen Address

Variable Type

Read/Write Variables

Note

540

2005 : 01

UInt

Motor operating mode:

2 = 2-wire overload

3 = 3-wire overload

4 = 2-wire independent

5 = 3-wire independent

6 = 2-wire reverser

7 = 3-wire reverser

8 = 2-wire 2-step

9 = 3-wire 2-step

10 = 2-wire 2-speed

11 = 3-wire 2-speed

256-511 = Custom logic program (0-255)

B

541

2005 : 02

UInt

Motor transition timeout (s)

 

542-544

2005 : 03 -

2005 : 05

 

(Reserved)

 

545

2005 : 06

Word

Controller AC inputs setting register

 

bits 0-3 Controller AC logic inputs configuration DT_ACInputSetting

 

bits 4-15 (Reserved)

 

546

2005 : 07

UInt

Thermal overload setting

B

bits 0-2 Motor temperature sensor type:

0 = None

1 = PTC binary

2 = PT100

3 = PTC analog

4 = NTC analog

bits 3-4 Thermal overload mode:

0 = Definite

2 = Inverse thermal

bits 5-15 (Reserved)

547

2005 : 08

UInt

Thermal overload trip definite timeout (s)

 

548

2005 : 09

(Reserved)

 

549

2005 : 0A

UInt

Motor temperature sensor trip threshold (x 0.1 Ω)

 

550

2005 : 0B

UInt

Motor temperature sensor alarm threshold (x 0.1 Ω)

 

551

2005 : 0C

Ulnt

Motor temperature sensor trip threshold degree (°C)

 

552

2005 : 0D

Ulnt

Motor temperature sensor alarm threshold degree (°C)

 

553

2005 : 0E

UInt

Rapid cycle lockout timeout (s)

 

554

2005 : 0F

UInt

(Reserved)

 

555

2005 : 10

UInt

Current phase loss timeout (x 0.1 s)

 

556

2005 : 11

UInt

Overcurrent trip timeout (s)

 

557

2005 : 12

UInt

Overcurrent trip threshold (% FLC)

 

558

2005 : 13

UInt

Overcurrent alarm threshold (% FLC)

 

559

2005 : 14

Word

Ground current trip configuration

B

bit 0 Ground current mode

bits 1-15 (Reserved)

560

2005 : 15

UInt

Ground current sensor client

 

561

2005 : 16

UInt

Ground current sensor server

 

562

2005 : 17

UInt

External ground current trip timeout (x 0.01 s)

 

563

2005 : 18

UInt

External ground current trip threshold (x 0.01 A)

 

564

2005 : 19

UInt

External ground current alarm threshold (x 0.01 A)

 

565

2005 : 1A

UInt

Motor nominal voltage (V)

1

566

2005 : 1B

UInt

Voltage phase imbalance trip timeout starting (x 0.1 s)

1

567

2005 : 1C

UInt

Voltage phase imbalance trip timeout running (x 0.1 s)

1

568

2005 : 1D

UInt

Voltage phase imbalance trip threshold (% imb)

1

569

2005 : 1E

UInt

Voltage phase imbalance alarm threshold (% imb)

1

570

2005 : 1F

UInt

Overvoltage trip timeout (x 0.1 s)

1

571

2005 : 20

UInt

Overvoltage trip threshold (x Vnom)

1

572

2005 : 21

UInt

Overvoltage alarm threshold (x Vnom)

1

573

2005 : 22

UInt

Undervoltage trip timeout (x 0.1 s)

1

574

2005 : 23

UInt

Undervoltage trip threshold (x Vnom)

1

575

2005 : 24

UInt

Undervoltage alarm threshold (x Vnom)

1

576

2005 : 25

UInt

Voltage phase loss trip timeout (x 0.1 s)

1

577

2005 : 26

Word

Voltage dip setting

1

bit 0 Load shedding enable

bit 1 Auto-restart enable

bits 2-15 (Reserved)

578

2005 : 27

UInt

Load shedding timeout (s)

1

579

2005 : 28

UInt

Voltage dip threshold (% Vnom)

1

580

2005 : 29

UInt

Voltage dip restart timeout (s)

1

581

2005 : 2A

UInt

Voltage dip restart threshold (% Vnom)

1

582

2005 : 2B

UInt

Auto restart immediate timeout (x 0.1 s)

 

583

2005 : 2C

UInt

Motor nominal power (x 0.1 kW)

1

584

2005 : 2D

UInt

Overpower trip timeout (s)

1

585

2005 : 2E

UInt

Overpower trip threshold (% Pnom)

1

586

2005 : 2F

UInt

Overpower alarm threshold (% Pnom)

1

587

2005 : 30

UInt

Underpower trip timeout (s)

1

588

2005 : 31

UInt

Underpower trip threshold (% Pnom)

1

589

2005 : 32

UInt

Underpower alarm threshold (% Pnom)

1

590

2005 : 33

UInt

Under power factor trip timeout (x 0.1 s)

1

591

2005 : 34

UInt

Under power factor trip threshold (x 0.01 PF)

1

592

2005 : 35

UInt

Under power factor alarm threshold (x 0.01 PF)

1

593

2005 : 36

UInt

Over power factor trip timeout (x 0.1 s)

1

594

2005 : 37

UInt

Over power factor trip threshold (x 0.01 PF)

1

595

2005 : 38

UInt

Over power factor alarm threshold (x 0.01 PF)

1

596

2005 : 39

 

Auto restart delayed timeout (s)

 

597-599

2005 : 3A - 2005 : 3C

 

(Reserved)

 

600

2006 : 01

(Not significant)

 

601

2006 : 02

Word

General configuration register 1

 

bit 0 Controller system config required:

0 = exit the configuration menu

1 = go to the configuration menu

A

bits 1-7 (Reserved)

 

Control mode configuration, bits 8-10 (one bit is set to 1):

 

bit 8 Config via HMI keypad enable

 

bit 9 Config via HMI engineering tool enable

 

bit 10 Config via network port enable

 

bit 11 Motor star-delta

B

bit 12 Motor phases sequence:

0 = A B C

1 = A C B

 

bits 13-14 Motor phases DT_PhaseNumber

B

bit 15 Motor auxiliary fan cooled (factory setting = 0)

 

602

2006 : 03

Word

General configuration register 2

 

bits 0-2 Trip reset mode DT_ResetMode

C

bit 3 HMI port parity setting:

0 = none

1 = even (factory setting)

 

bits 4-8 (Reserved)

 

bit 9 HMI port endian setting

 

bit 10 Network port endian setting

 

bits 11 HMI motor status LED color

 

bits 12-15 (Reserved)

 

603

2006 : 04

Ulnt

HMI port address setting

 

604

2006 : 05

Ulnt

HMI port baud rate setting (Baud)

 

605

2006 : 06

(Reserved)

 

606

2006 : 07

Ulnt

Motor trip class (s)

 

607

2006 : 08

 

(Reserved)

 

608

2006 : 09

Ulnt

Thermal overload trip reset threshold (% trip level)

 

609

2006 : 0A

Ulnt

Thermal overload alarm threshold (% trip level)

 

610

2006 : 0B

UInt

Internal ground current trip timeout (x 0.1 s)

 

611

2006 : 0C

UInt

Internal ground current trip threshold (% FLCmin)

 

612

2006 : 0D

UInt

Internal ground current alarm threshold (% FLCmin)

 

613

2006 : 0E

UInt

Current phase imbalance trip timeout starting (x 0.1 s)

 

614

2006 : 0F

UInt

Current phase imbalance trip timeout running (x 0.1 s)

 

615

2006 : 10

UInt

Current phase imbalance trip threshold (% imb)

 

616

2006 : 11

UInt

Current phase imbalance alarm threshold (% imb)

 

617

2006 : 12

UInt

Jam trip timeout (s)

 

618

2006 : 13

UInt

Jam trip threshold (% FLC)

 

619

2006 : 14

UInt

Jam alarm threshold (% FLC)

 

620

2006 : 15

UInt

Undercurrent trip timeout (s)

 

621

2006 : 16

UInt

Undercurrent trip threshold (% FLC)

 

622

2006 : 17

UInt

Undercurrent alarm threshold (% FLC)

 

623

2006 : 18

UInt

Long start trip timeout (s)

 

624

2006 : 19

UInt

Long start trip threshold (% FLC)

 

625

2006 : 1A

 

(Reserved)

 

626

2006 : 1B

UInt

HMI display contrast setting

 

bits 0-7 HMI display contrast setting

 

bits 8-15 HMI display brightness setting

 

627

2006 : 1C

UInt

Contactor rating (0.1 A)

 

628

2006 : 1D

UInt

Load CT client

B

629

2006 : 1E

UInt

Load CT server

B

630

2006 : 1F

UInt

Load CT multiple passes (passes)

B

631

2006 : 20

Word

Trip enable register 1

 

bits 0-1 (Reserved)

 

bit 2 Ground current trip enable

 

bit 3 Thermal overload trip enable

 

bit 4 Long start trip enable

 

bit 5 Jam trip enable

 

bit 6 Current phase imbalance trip enable

 

bit 7 Undercurrent trip enable

 

bit 8 (Reserved)

 

bit 9 Self test enable

0 = disable

1 = enable (factory setting)

 

bit 10 HMI port trip enable

 

bits 11-14 (Reserved)

 

bit 15 Network port trip enable

 

632

2006 : 21

Word

Alarm enable register 1

 

bit 0 (Not significant)

 

bit 1 (Reserved)

 

bit 2 Ground current alarm enable

 

bit 3 Thermal overload alarm enable

 

bit 4 (Reserved)

 

bit 5 Jam alarm enable

 

bit 6 Current phase imbalance alarm enable

 

bit 7 Undercurrent alarm enable

 

bits 8- 9 (Reserved)

 

bit 10 HMI port alarm enable

 

bit 11 Controller internal temperature alarm enable

 

bits 12-14 (Reserved)

 

bit 15 Network port alarm enable

 

633

2006 : 22

Word

Trip enable register 2

 

bit 0 (Reserved)

 

bit 1 Diagnostic trip enable

 

bit 2 Wiring trip enable

 

bit 3 Overcurrent trip enable

 

bit 4 Current phase loss trip enable

 

bit 5 Current phase reversal trip enable

 

bit 6 Motor temperature sensor trip enable

 

bit 7 Voltage phase imbalance trip enable

1

bit 8 Voltage phase loss trip enable

1

bit 9 Voltage phase reversal trip enable

1

bit 10 Undervoltage trip enable

1

bit 11 Overvoltage trip enable

1

bit 12 Underpower trip enable

1

bit 13 Overpower trip enable

1

bit 14 Under power factor trip enable

1

bit 15 Over power factor trip enable

1

634

2006 : 23

Word

Alarm enable register 2

 

bit 0 (Reserved)

 

bit 1 Diagnostic alarm enable

 

bit 2 (Reserved)

 

bit 3 Overcurrent alarm enable

 

bit 4 Current phase loss alarm enable

 

bit 5 (Reserved)

 

bit 6 Motor temperature sensor alarm enable

 

bit 7 Voltage phase imbalance alarm enable

1

bit 8 Voltage phase loss alarm enable

1

bit 9 (Reserved)

1

bit 10 Undervoltage alarm enable

1

bit 11 Overvoltage alarm enable

1

bit 12 Underpower alarm enable

1

bit 13 Overpower alarm enable

1

bit 14 Under power factor alarm enable

1

bit 15 Over power factor alarm enable

1

635-636

2006 : 24 - 2006 : 25

(Reserved)

 

637

2006 : 26

UInt

Auto-reset attempts group 1 setting

 

638

2006 : 27

UInt

Auto-reset group 1 timeout

 

639

2006 : 28

UInt

Auto-reset attempts group 2 setting

 

640

2006 : 29

UInt

Auto-reset group 2 timeout

 

641

2006 : 2A

UInt

Auto-reset attempts group 3 setting

 

642

2006 : 2B

UInt

Auto-reset group 3 timeout

 

643

2006 : 2C

UInt

Motor step 1 to 2 timeout

 

644

2006 : 2D

UInt

Motor step 1 to 2 threshold

 

645

2006 : 2E

UInt

HMI port fallback setting DT_OutputFallbackStrategy

 

646-649

2006 : 2F -

2006 : 32

(Reserved)

 

650

2007 : 01

Word

HMI language setting register:

 

bit 0-4 HMI language setting DT_Language5

 

bits 5-15 (Not significant)

 

651

2007 : 02

Word

HMI display items register 1

 

bit 0 HMI display average current enable

 

bit 1 HMI display thermal capacity level enable

 

bit 2 HMI display L1 current enable

 

bit 3 HMI display L2 current enable

 

bit 4 HMI display L3 current enable

 

bit 5 HMI display ground current enable

 

bit 6 HMI display motor status enable

 

bit 7 HMI display current phase imbalance enable

 

bit 8 HMI display operating time enable

 

bit 9 HMI display I/O status enable

 

bit 10 HMI display reactive power enable

 

bit 11 HMI display frequency enable

 

bit 12 HMI display starts per hour enable

 

bit 13 HMI display control mode enable

 

bit 14 HMI display start statistics enable

 

bit 15 HMI motor temperature sensor enable

 

652

2007 : 03

Ulnt

Motor full load current ratio, FLC1 (% FLCmax)

 

653

2007 : 04

Ulnt

Motor high speed full load current ratio, FLC2 (% FLCmax)

 

654

2007 : 05

Word

HMI display items register 2

 

bit 0 HMI display L1-L2 voltage enable

1

bit 1 HMI display L2-L3 voltage enable

1

bit 2 HMI display L3-L1 voltage enable

1

bit 3 HMI display average voltage enable

1

bit 4 HMI display active power enable

1

bit 5 HMI display power consumption enable

1

bit 6 HMI display power factor enable

1

bit 7 HMI display average current ratio enable

 

bit 8 HMI display L1 current ratio enable

1

bit 9 HMI display L2 current ratio enable

1

bit 10 HMI display L3 current ratio enable

1

bit 11 HMI display thermal capacity remaining enable

 

bit 12 HMI display time to trip enable

 

bit 13 HMI display voltage phase imbalance enable

1

bit 14 HMI display date enable

 

bit 15 HMI display time enable

 

655-658

2007 : 06 - 2007 : 09

Word[4]

Date and time setting DT_DateTime

 

659

2007 : 0A

Word

HMI display items register 3

 

bit 0 HMI display temperature sensor degree CF

bits 1-15 (Reserved)

 

660-681

2007 : 0B - 2007 : 20

 

(Reserved)

 

682

2007 : 21

Ulnt

Network port fallback setting DT_OutputFallbackStrategy

 

683

2007 : 22

Word

Control setting register

 

bits 0-1 (Reserved)

 

bit 2 Control remote local default mode (with LTMCU)

0 = remote

1 = local

 

bit 3 (Reserved)

 

bit 4 Control remote local buttons enable (with LTMCU)

0 = disable

1 = enable

 

bits 5-6 Control remote channel setting (with LTMCU)

0 = network

1 = terminal strip

2 = HMI

 

bit 7 (Reserved)

 

bit 8 Control local channel setting

0 = terminal strip

1 = HMI

 

bit 9 Control direct transition

0 = stop required during transition

1 = stop not required during transition

 

bit 10 Control transfer mode

0 = bump

1 = bumpless

 

bit 11 Stop terminal strip disable

0 = enable

1 = disable

 

bit 12 Stop HMI disable

0 = enable

1 = disable

 

bits 13-15 (Reserved)

 

684-692

2007 : 23 - 2007 : 2D

Word

(Reserved

 

695

2007 : 2E

Ulnt

Network port baud rate setting (Baud) DT_ExtBaudRate

 

696

2007 : 2F

Ulnt

Network port address setting

 

697-699

2007 : 30 - 2007 : 32

Word

(Not significant)

 

Command Variables

Command Variables

Command variables are described in the following table:

Register

CANopen Address

Variable Type

Read/Write Variables

Note

700

2008 : 01

Word

Register available to remotely write commands that can be processed in a specific custom logic

 

701-703

2008 : 02 - 2008 : 04

(Reserved)

 

704

2008 : 05

Word

Control register 1

 

bit 0 Motor run forward command*

 

bit 1 Motor run reverse command (1)

 

bit 2 (Reserved)

 

bit 3 Trip reset command

 

bit 4 (Reserved)

 

bit 5 Self test command

 

bit 6 Motor low speed command

 

bits 7-15 (Reserved)

 

705

2008 : 06

Word

Control register 2

 

bit 0 Clear all command

Clear all parameters, except:

  • Motor LO1 closings count

  • Motor LO2 closings count

  • Controller internal temperature max

  • Thermal capacity level

 

bit 1 Clear statistics command

 

bit 2 Clear thermal capacity level command

 

bit 3 Clear controller settings command

 

bit 4 Clear network port settings command

 

bits 5-15 (Reserved)

 

706-709

2008 : 07 - 2008 : 0A

 

(Reserved)

 

707-799

2008 : 0B - 2008 : 64

(Forbidden)

 

Custom Logic Variables

Custom Logic Variables

Custom logic variables are described in the following tables:

Modbus Address

CANopen Address

Variable Type

Read-only Variables

Note

1200

200D : 01

Word

Custom logic status register

 

bit 0 Custom logic run

 

bit 1 Custom logic stop

 

bit 2 Custom logic reset

 

bit 3 Custom logic second step

 

bit 4 Custom logic transition

 

bit 5 Custom logic phase reverse

 

bit 6 Custom logic network control

 

bit 7 Custom logic FLC selection

 

bit 8 (Reserved)

 

bit 9 Custom logic auxiliary 1 LED

 

bit 10 Custom logic auxiliary 2 LED

 

bit 11 Custom logic stop LED

 

bit 12 Custom logic LO1

 

bit 13 Custom logic LO2

 

bit 14 Custom logic LO3

 

bit 15 Custom logic LO4

 

1201

200D : 02

Word

Custom logic version

 

1202

200D : 03

Word

Custom logic memory space

 

1203

200D : 04

Word

Custom logic memory used

 

1204

200D : 05

Word

Custom logic temporary space

 

1205

200D : 06

Word

Custom logic non volatile space

 

1206-1249

200D : 07 - 200D : 32

 

(Reserved)

 

Modbus Address

CANopen Address

Variable Type

Read-only Variables

Note

1250

200D : 33

Word

Custom logic setting register 1

 

bit 0 (Reserved)

 

bit 1 Logic input 3 external ready enable

 

bits 2-15 (Reserved)

 

1251-1269

200D : 34 - 200D : 46

 

(Reserved)

 

1270

200D : 47

Word

Custom logic command register 1

 

bit 0 Custom logic external trip command

 

bits 1-15 (Reserved)

 

1271-1279

200D : 48 - 200D : 50

 

(Reserved)

 

Modbus Address

CANopen Address

Variable Type

Read-only Variables

Note

1280

200D : 51

Word

Custom logic monitoring register 1

 

bit 0 Custom logic monitoring external trip

 

bit 1 Custom logic system ready

 

bits 2-15 (Reserved)

 

1281-1300

200D : 52 - 200D : 65

 

(Reserved)

 

Modbus Address

CANopen Address

Variable Type

Read-only Variables

Note

1301-1399

200D : 66 - 200D : C8

Word[99]

General purpose registers for logic functions

 
QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?