Homeline Load Centers
Homeline Product Description
This section provides an overview of the Homeline Load Center features, an overview of the catalog number guide, and general information about the product.
Introduction to Homeline Load Centers
Homeline Load Centers are built on Square D reputation for reliability, innovation, and leadership in circuit protection.
Homeline Load Centers from Square D are UL Listed panelboards. Then are designed to meet residential requirements to help protect electrical systems, equipment, and people.
Other Features:
UL Listed Only for Square D Breakers: 1-in. format breakers trip to center position.
Standard 22 kA /10 kA AIR SCCR: Standard 22/10 kA AIR series rating on main circuit breaker panels increases application capability (branch circuit breakers 10 kA / main circuit breaker 22 kA).
Hinges and ground bars: Side hinge doors on outdoor convertible main panels. Equipment grounding bar included with main lug load centers.
Screws: Single captive screw interior mounting on indoor panels to ease removal. Combination slot/square drive neutral, ground, and cover screws for positive drive and improved torque.
Accepts Plug-on Neutral (PoN) CAFI and Dual Function Breakers, and circuit breakers with pigtails
Catalog Number Guide — Homeline Load Centers
General Information
Type:
Circuit breaker load centers for use on AC systems. They are UL Listed under file E-6294 (panelboards) and meet Federal Specifications W-P-115b NEMA Type 1, Class 2.
Service:
120 Vac, 1Ø2W
120 / 240 Vac, 1Ø3W
Ratings:
Main lugs: 70–225 A
Main circuit breaker: 50–225 A
UL Listed:
-
File E-6294 (panelboards)
-
UL 67 Standard for Panelboards establishes requirements for electrical distribution panels
-
Suitable for use as service equipment
-
75°C wire rating
Class CTL:
UL Listed Class CTL load centers
Meets the 2020 National Electrical Code (NEC) article for Lighting and Appliance Branch Circuit panelboards
Main Circuit Breaker Kits:
50–225 A main circuit breaker kit is 22,000 AIR series rated with 10,000 AIR branch circuit breakers.
Branch Circuit Breakers
10,000 AIR | |
HOM |
1-pole, 15–50 A |
2-pole, 15–125 A |
|
HOMT |
1-pole, 15–30 A |
2-pole, 15–50 A |
|
HOM-GFI |
1-pole, 15–20 A |
2-pole, 15–50 A |
|
HOM-AFI |
1-pole, 15–20 A |
HOM-CAFI |
1-pole, 15–20 A |
2-pole, 15–20 A |
|
HOM-P |
1-pole, 15–20 A |
HOM-BB |
2-pole, 150–200 A |
HOM-DF |
1-pole, 15–20 A |
HOM-HM |
1-pole, 15–20 A |
HOM-EPD |
1-pole, 15–20 A |
2-pole, 15–50 A |
Homeline Indoor and Outdoor Load Centers
NEMA Type 1 – Indoor
NEMA Type 1 enclosures are typically used to help protect controls and terminations from objects and personnel. This style of enclosure, while offering a latching door, does not have a gasket sealing surface. NEMA 1 enclosures are used in applications where sealing out dust, oil, and water is not required.
NEMA Type 3R – Rainproof
NEMA Type 3R enclosures are typically used in outdoor applications for wiring and junction boxes. This style of enclosure help provide protection against falling rain, sleet, snow, and external ice formation. In an indoor application, this can help protect against dripping water. This style of enclosure does not have a gasket sealing surface. Some models have hasps for padlocking.
Indoor Enclosures (NEMA Type 1)
|
Homeline Plug-on Neutral Load Centers Homeline plug-on neutral load centers offer time-savings for plug-on neutral combination arc fault (CAFI) and dual function circuit breaker installation. Our innovative, split neutrals are designed to save you time and wire, allowing plug-on neutral circuit breakers to connect directly to the neutral bar without the pigtail. |
|
Qwik-Grip wire management system available Save time and simplify your work by eliminating knockouts, installing wire connectors and help prevent pulling wire into the load center. |
|
Material, Finish, and Knockouts The enclosures are sheet steel with knockouts at the top, bottom, back, and sides. Homeline finish consists of gray baked enamel electrodeposited over cleaned, phosphatized steel. Most indoor enclosures are 14.25 in. (362 mm) wide. Homeline enclosures can be rotated to allow top or bottom feed. Homeline load center interiors have tin and copper plated aluminum bus bars. |
|
Flush and surface covers Indoor Homeline covers with latch are available in surface or flush mount and are included with our load centers. Doors to cover circuit breaker handles, except on 2-4, 4-8, and 6-12 circuit models. Triple lead covers crews for fast cover installation. |
|
Filter plates Snap-in style filler plates are accessories purchased separately available to cover unused spaces. HOMFP and QOFP filler plates available for branch circuit breaker spaces in all covers. QOM1FP filler plates available for 100-125 A convertible load center covers. QOM2FP filler plates available for 150-225 A convertible load center covers. |
|
Different colors and styles Homeline covers are available in gray and white colors. Mono-Flat covers, a high-end alternative with aesthetically pleasing design and low profile surface with concealed mounting screws and door hinges are an alternative to the standard covers. |
Outdoor Enclosures (NEMA Type 3R)
Fixed Mains vs. Convertible Mains — Single Phase
Single-Phase — Homeline Load Centers, Fixed Mains (70–125 A)
Indoor NEMA 1 |
Rainproof NEMA 3R |
||||
---|---|---|---|---|---|
|
|
||||
Standards |
|||||
UL 67 Listed
|
|||||
Short Circuit Current Rating |
|||||
Main lugs: up to 10,000 AIR | |||||
Interior |
|||||
Tin plated aluminum bus | |||||
Mains |
|||||
|
|||||
Covers |
|||||
Flush and surface cover |
Single-Phase — Homeline Load Centers, Convertible Mains
(100–225 A)
Technical Information
Indoor, HOM Fixed Mains (70-125 A) — Main Lugs
HOM Standard Load Center Main Lugs, Fixed Mains (1Ø3W—120/240 Vac Indoor—UL Listed)
Mains Rating |
Spaces |
Max. Single Pole Circuits * |
Max. Tandem Circuit Breakers |
Load Center Box, Interior * |
Main Wire Size AWG/kcmil |
Equipment Ground Bar Kit (Order Separately) |
Box No. * |
|
---|---|---|---|---|---|---|---|---|
Al |
Cu |
|||||||
Main Lugs—10 kA Short Circuit Current Rating Order HOM Circuit Breakers |
||||||||
70 A |
2 |
4 |
2 |
HOM24L70F/S * , * |
12–3 |
14–4 |
2 |
|
100 A |
6 |
12 |
6 |
HOM612L100F/S * , * |
6–2/0 |
8–1 |
4 |
|
125 A |
4 |
8 |
4 |
12–2/0 |
14–2/0 |
PK7GTA
|
21 |
Indoor, HOM Convertible Mains (125–225 A) — Main Lugs
HOM Plug-on Neutral Load Center Main Lugs, Convertible Mains
(1Ø3W–120/240 Vac Indoor—UL Listed)
Mains Rating |
Spaces |
Max. Single Pole Circuits * |
Max. Tandam Circuit Breakers |
Load Center Box, Interior and Cover * |
Main Wire Size AWG/kcmil |
Equipment Ground Bar Kit (Order Separately |
Box No. * |
|
---|---|---|---|---|---|---|---|---|
Al |
Cu |
|||||||
Convertible
Mains—Factory-installed Main Lugs |
||||||||
125 A |
8 |
16 |
8 |
6–2/0 |
6–1 |
6 |
||
12 |
24 |
12 |
||||||
16 |
32 |
16 |
6–1/0 |
8 |
||||
20 |
40 |
20 |
||||||
30 |
60 |
30 |
6–2/0 |
10 |
||||
Convertible
Mains—Factory-installed Main Lugs |
||||||||
225 A |
30 |
60 |
30 |
4–300 |
4–250 |
10 |
||
40 |
80 |
40 |
12 |
|||||
42 |
84 |
42 |
||||||
60 |
120 |
60 |
25 |
|||||
Convertible
Mains—Factory-installed Main Lugs—Ground Bar Included |
||||||||
125 A |
8 |
16 |
8 |
6–2/0 |
6–1 |
PKGTALP1
|
6 |
|
12 |
24 |
12 |
||||||
20 |
40 |
20 |
6–1/0 |
8 |
||||
24 |
80 |
24 |
||||||
Convertible
Mains—Factory-installed Main Lugs—Ground Bar Included |
||||||||
225 A |
30 |
60 |
30 |
4–300 |
4–250 |
PKGTALP2
|
10 |
|
16 |
32 |
16 |
PKGTALP1
|
9 |
||||
20 |
40 |
20 |
||||||
40 |
80 |
40 |
PKGTALP3
|
12 |
||||
42 |
84 |
42 |
Indoor, HOM Convertible Mains (100–200 A) — Main Breaker
HOM Plug-on Neutral Load Center Main Breaker, Convertible Mains
(1Ø3W–120/240 Vac Indoor—UL Listed)
Mains Rating |
Spaces |
Max. Single Pole Circuits * |
Max. Tandam Circuit Breakers |
Load Center Box, Interior and Cover * |
Main Wire Size AWG/kcmil |
Equipment Ground Bar Kit (Order Separately |
Box No. * |
|
---|---|---|---|---|---|---|---|---|
Al |
Cu |
|||||||
Main
Circuit Breaker—22 kA Short Circuit Current Rating |
||||||||
100 A |
8 |
16 |
8 |
6–1 |
6–3 |
5 |
||
12 |
24 |
12 |
6–2/0 |
6 |
||||
20 |
40 |
20 |
6–3 |
7 |
||||
24 |
48 |
24 |
6–2/0 |
8 |
||||
30 |
60 |
30 |
6–2/0 |
10 |
||||
125 A |
24 |
48 |
24 |
6–2/0 |
6–1/0 |
8 |
||
30 |
60 |
30 |
6–2/0 |
10 |
||||
Convertible
Mains—Factory-installed Main Circuit Breaker |
||||||||
150 A |
30 |
60 |
30 |
4–250 |
10 |
|||
200 A |
20 |
40 |
20 |
4–250 |
9 | |||
30 |
60 |
30 |
10 | |||||
40 |
80 |
40 |
12 |
|||||
42 |
84 |
42 |
12 |
|||||
60 |
120 |
60 |
25 |
|||||
225 A |
42 |
84 |
42 |
4–300 |
4–250 |
12 |
Indoor, HOM Convertible Mains (125–200 A with Qwik-Grip)
HOM Plug-on Neutral Load Centers with Qwik-Grip (1Ø3W–120 / 240 Vac Indoor— UL Listed)
Mains Rating |
Spaces |
Max. 1P Circuit |
Max. Tandam Circuit Breakers |
Load Center Box, Interior and Cover |
Main Wire Size |
Equipment Ground Bar Kit |
Box No. |
|
---|---|---|---|---|---|---|---|---|
Al |
Cu |
|||||||
125 A |
34 |
48 |
24 |
6–2/0 |
6–1/0 |
PKGTALP2
|
8Q |
|
40 |
60 |
30 |
6–2/0 |
10Q |
||||
Convertible Mains—Factory-Installed Main Lugs, 10 kA Short Circuit Current Rating— QOM2 Main Frame Size, Convertible |
||||||||
225 A |
30 |
60 |
30 |
4–300 |
4–250 |
PKGTALP2
|
10Q |
|
40 |
80 |
40 |
PKGTALP3
|
12Q |
||||
42 |
84 |
42 |
||||||
Convertible Mains—Factory-Installed Main Circuit Breaker, 22 kA Short Circuit Current Rating— QOM2 Main Circuit Breaker Frame Size, Convertible to Main Lugs or Main Circuit Breaker |
||||||||
200 A |
30 |
60 |
30 |
4–250 |
10Q |
|||
40 |
80 |
40 |
12Q |
|||||
42 |
84 |
42 |
4–300 |
4–250 |
Homeline Service Upgrades Load Centers (1Ø3W—120/240 Vac Special Applications—UL Listed)
Mains Rating |
Spaces |
Max. IP Circuits * |
Max. Tandem Circuit Breakers |
Load Center Box and Interior |
Extra Long Cover with Door (Order Separately) |
Main Wire Size AWG/Kcmil |
Equipment Ground Bar Kit (Order Separately) |
Box No. * |
||
---|---|---|---|---|---|---|---|---|---|---|
Flush |
Surface |
Al |
Cu |
|||||||
Convertible
Mains—Factory-Installed Main Circuit Breaker—22 KA |
||||||||||
200 A |
30 |
60 |
30 |
— |
4–250 |
26 |
1Ø, Field-Installed Mains Kits
Field-Installed Main Circuit Breaker Kits, 1Ø
QOM1 Frame Size — (Use with Convertible Main Load Centers
only)
Main Circuit Breaker Rating* |
Convertible Load Center Mains Rating |
22 k AIR * |
Lug Wire |
---|---|---|---|
Main Circuit Breaker |
|||
50 A |
100–125 |
12–2/0 Al or Cu |
|
60 A |
|||
70 A |
|||
80 A |
|||
90 A |
|||
100 A |
|||
110 A |
125 |
||
125 A |
Field-Installed Main Circuit Breaker Kits, 1Ø
QOM2 Frame Size — (Use with Convertible Main Load Centers
only)
Main Circuit Breaker Rating * |
Convertible Load Center Mains Rating |
22 k AIR * |
Lug Wire Size |
---|---|---|---|
Main Circuit Breaker * |
|||
100 A |
150–225 |
4–300 Al or Cu |
|
125 A |
|||
150 A |
|||
175 A |
200–225 |
||
200 A |
|||
225 A |
225 |
Rainproof, HOM Fixed and Convertible Mains (70–225 A) Main Lugs
HOM Standard Load Center Main Lugs, Fixed Mains
(1Ø3W–120/240 Vac Rainproof UL—Listed)
Mains Rating |
Spaces |
Max. Single Pole Circuits * |
Max. Tandam Circuit Breakers |
Load Center Box, Interior and Cover |
Main Wire Size AWG/kcmil |
Equipment Ground Bar Kit (Order Separately |
Box No. |
|
---|---|---|---|---|---|---|---|---|
Cat. No. (DE3C) |
Al |
Cu |
Cat. No. (DE3A) |
|||||
Main
Lugs—10 kA Short Circuit Current Rating |
||||||||
70 A |
2 |
4 |
2 |
12–3 |
14–4 |
1R |
||
100 A |
6 |
12 |
6 |
8–1 |
2R |
|||
125 A |
4 |
8 |
4 |
12–2/0 |
14–2/0 |
PK7GTA
|
15R |
HOM Plug-on Neutral Load Center Main Lugs, Convertible Mains
(1Ø3W–120/240 Vac Rainproof UL—Listed)
Mains Rating |
Spaces |
Max. Single Pole Circuits * |
Max. Tandam Circuit Breakers |
Load Center Box, Interior and Cover |
Main Wire Size AWG/kcmil |
Equipment Ground Bar Kit (Order Separately |
Box No. |
|
---|---|---|---|---|---|---|---|---|
Cat. No. (DE3C) |
Al |
Cu |
Cat. No. (DE3A) |
|||||
Convertible Mains with Factory-installed Main Lugs * , QOM1 Main Frame Size—Convertible to Main Circuit Breaker |
||||||||
125 A |
8 |
16 |
8 |
6–2/0 |
6–1 |
3R |
||
12 |
24 |
12 |
||||||
20 |
40 |
20 |
4R |
|||||
24 |
48 |
24 |
6R |
|||||
Convertible Mains with Factory-installed Main Lugs * , QOM2 Main Frame Size—Convertible to Main Circuit Breaker |
||||||||
225 A |
12 |
12 |
0 |
4–300 |
4–250 |
5R |
||
16 |
32 |
16 |
6R |
|||||
20 |
40 |
20 |
||||||
30 |
60 |
30 |
7R |
|||||
40 |
80 |
40 |
14R |
|||||
42 |
84 |
42 |
Rainproof, HOM Convertible Mains (100–200 A) — Main Breaker
HOM Plug-on Neutral Load Center Main Breaker, Convertible Mains (1Ø3W–120/240 Vac Rainproof—UL Listed)
Mains Rating |
Spaces |
Max. Single Pole Circuits * |
Max. Tandam Circuit Breakers |
Load Center Box, Interior and Cover |
Main Wire Size AWG/kcmil |
Equipment Ground Bar Kit (Order Separately |
Box No. |
|
---|---|---|---|---|---|---|---|---|
Cat. No. (DE3C) |
Al |
Cu |
Cat. No. (DE3A) |
|||||
Main
Circuit Breaker—22 kA Short Circuit Current Rating Convertible
Mains with Factory-Installed Main Circuit Breaker, |
||||||||
100 A |
8 |
16 |
8 |
6–2/0 |
6–1 |
3R |
||
12 |
24 |
12 |
||||||
20 |
40 |
20 |
4R |
|||||
125 A |
8 |
16 |
8 |
3R |
||||
24 |
48 |
24 |
6R |
|||||
Convertible
Mains with Factory-installed Main Circuit Breaker, |
||||||||
150 A |
30 |
60 |
30 |
4–250 |
7R |
|||
200 A |
12 |
12 |
0 |
5R |
||||
20 |
40 |
20 |
6R |
|||||
30 |
60 |
30 |
7R |
|||||
40 |
80 |
40 |
14R |
|||||
Convertible
Mains with Factory-installed Main Circuit Breaker with Feed-thru Lugs, |
||||||||
150 A |
8 |
16 |
8 |
4–250 |
6R |
|||
200 A |
Homeline Label Samples
Homeline Box Label Sample
|
Wire range for lug torque data table |
Short circuit ratings |
Short circuit ratings and additional or replacement circuit breakers |
|
Homeline Wiring Diagram Sample
Alternate wiring diagram for main circuit breaker or main lug |
|
Load center accessories |
Square D circuit breakers that may be used in this load center |
Homeline Wiring Diagrams
Homeline Load Centers — Main Lugs
Homeline Load Centers — Main Breaker
Homeline Load Centers – Main Breaker
Homeline Value Packs and Covers
Value Pack Offer
Different value pack combinations offer an affordable mix of products for load center customers. Value packs are ideal for new construction, upgrades and remodels. Designed to meet various needs, special packs are combined for Homeline products.
We’ve got you covered, the covers are included.
Indoor Homeline covers are available in gray or white colors; these can be purchased separately and limit loss or damage if stored at the job site.
Mono-Flat covers, a high-end alternative with aesthetically pleasing design and low profile surface with concealed mounting screws and door hinges, are an alternative to our standard covers.
Plug-on Neutral Load Center Value Packs
Plug-on Neutral Indoor Load Center Value Packs (compatible with Plug-on Circuit Breakers and Plug-on Neutral Circuit Breakers)
Mains Rating |
Spaces |
Max. 1P Circuits * |
Max. Tandem Circuit Breakers |
Load Center Box, Interior, Cover and Branch Circuit Breakers |
Equipment Ground Bar Kit (Order Separately) |
Main Wire Size |
Box No. * |
||
---|---|---|---|---|---|---|---|---|---|
Cat. No. |
Included Load Center/Circuit Breakers |
Cat. No. |
AI |
Cu |
|||||
Homeline
Convertible Mains—Factory-Installed Main Lugs (accepts only
HOM Plug-On Circuit Breakers) |
|||||||||
125 A |
12 |
24 |
12 |
(1)
HOM1224L125PGC
|
PKGTALP1
|
6–2/0 |
6–1 |
6 |
|
225 A |
30 |
60 |
30 |
(1)
HOM3060L225PGC
|
PKGTALP2
|
4–300 |
4–250 |
10 |
|
100 A |
20 |
40 |
20 |
(1)
HOM2040M100PC
|
PK9-27GTA(L)
|
6–1 |
6–3 |
7 |
|
(1)
HOM2040M100PC
|
|||||||||
24 |
48 |
24 |
(1)
HOM2448M100PC
|
6–2/0 |
6–1/0 |
8 |
|||
150 A |
30 |
30 |
30 |
(1)
HOM3060M150PC
|
PK9-27GTA(L)
|
4–250 |
10 |
||
20 |
40 |
20 |
(1)
HOM2040M200PC
|
9 |
|||||
30 |
60 |
30 |
(1)
HOM3060M200PC
|
10 |
|||||
(1)
HOM3060M200PC
|
|||||||||
200 A |
30 |
60 |
30 |
(1)
HOM3060M200PC
|
PK9-27GTA(L)
|
||||
40 |
80 |
40 |
(1)
HOM4080M200PC
|
12 |
|||||
(1)
HOM4080M200PC
|
|||||||||
(1)
HOM4080M200PC
|
Plug-on Neutral with Qwik-Grip Indoor Load Center Value Packs — (compatible with Plug-on Circuit Breakers and Plug-on Neutral Circuit Breakers)
Mains Rating |
Spaces |
Max. 1P Circuits |
Max. Tandem Circuit Breakers |
Load Center Box, Interior, Cover and Branch Circuit Breakers |
Equipment Ground Bar Kit (Order Separately) |
Main Wire Size |
Box No. * |
||
---|---|---|---|---|---|---|---|---|---|
Cat. No. |
Included Load Center/Circuit Breakers |
Cat. No. |
AI |
Cu |
|||||
Homeline
Convertible Mains—Factory-Installed Main Circuit breaker, 22
kA Short Circuit Current Rating—Copper Bus, |
|||||||||
100 A |
20 |
40 |
20 |
(1)
HOM2040M100PQC
|
6–1 |
6–3 |
7Q |
||
200 A |
30 |
60 |
30 |
(1)
HOM3060M200PQC
|
4–250 |
10Q |
|||
200 A |
40 |
80 |
40 |
(1)
HOM4080M200PQC
|
4–250 |
12Q |
Plug-on Neutral Rainproof Load Center Value Packs (compatible with Plug-on Circuit Breakers and Plug-on Neutral Circuit Breakers)
Mains Rating |
Spaces |
Max. 1P Circuits |
Max. Tandem Circuit Breakers |
Load Center Box, Interior, Cover and Branch Circuit Breakers |
Equipment Ground Bar Kit (Order Separately) |
Main Wire Size |
Box No. * |
||
---|---|---|---|---|---|---|---|---|---|
Cat. No. |
Included Load Center/Circuit Breakers |
Cat. No. |
AI |
Cu |
|||||
Homeline
(Accepts Only HOM Plug-On Circuit Breakers) Convertible Mains—Factory-Installed
Main Circuit Breaker, |
|||||||||
125 A |
12 |
24 |
12 |
(1)
HOM1224M125PRB
|
6–2/0 |
6–1 |
3R |
||
200 A |
30 |
60 |
30 |
(1)
HOM3060M200PRB
|
4–250 |
7R |
Plug-on Neutral Load Center Value Packs with Surge Protective Device (compatible with Plug-on Circuit Breakers and Plug-on Neutral Circuit Breakers)
Mains Rating |
Spaces |
Max. 1P Circuits |
Max. Tandem Circuit Breakers |
Load Center Box, Interior, Cover and Branch Circuit Breakers |
Equipment Ground Bars |
Main Wire Size |
Box No. |
||
---|---|---|---|---|---|---|---|---|---|
Cat. No. |
Included Load Center/Circuit Breakers/SPD |
Cat. No. |
Al |
Cu |
|||||
225 A |
30 |
60 |
30 |
(1)
HOM3060l225PGC
|
PKGTALP2
|
4-300 |
4-250 |
10 |
|
200 A |
8 |
16 |
8 |
(1)
HOM816M200PFTRB
|
PK15GTA
|
4-250 |
6R |