990-1000015-001

Connect the Power Cables

  1. Route the power cables through the top or bottom of the maintenance bypass cabinet.
  2. Connect the input cables/bypass cables, UPS input cables/UPS bypass cables and load cables.

    Single Mains – Rear View

    Dual Mains – Rear View

    NOTE: If there is no room available for removing the right side panel from the maintenance bypass cabinet, follow the sequence on the label on the maintenance bypass cabinet to connect the input and output cables.
  3. Check the fastening of the cable lugs.
    CAUTION
    Risk of equipment damage
    Check the fastening of the cable lugs. If the cable lugs move due to pulling on the cables, the bolt can become loose.
    Failure to follow these instructions can result in injury or equipment damage.
  4. Only for single mains system: Route the UPS input cables and the UPS output cables through the top of the maintenance bypass and into the UPS. Follow the UPS installation manual to connect the UPS input cables and the UPS output cables in the UPS.
  5. Only for dual mains system: Route the UPS bypass cables and the UPS output cables through the top of the maintenance bypass cabinet and into the UPS. Follow the UPS installation manual to connect the input cables, the UPS bypass cables and the UPS output cables in the UPS.
  6. Clean/vacuum the maintenance bypass cabinet of any debris and foreign objects.