Energy and energy by tariff
Energy values – 64-bit integer
Address | Register | Action | Size | Type | Units | Description |
---|---|---|---|---|---|---|
Total energy (cannot be rest) |
||||||
0x0C84 |
3205 |
R |
4 |
Int64 |
Wh |
Forward active energy |
0x0C88 |
3209 |
R |
4 |
Int64 |
Wh |
Reverse active energy |
0x0C8C |
3213 |
R |
4 |
Int64 |
Wh |
Total active energy |
0x0C94 |
3221 |
R |
4 |
Int64 |
VARh |
Forward reactive energy |
0x0C98 |
3225 |
R |
4 |
Int64 |
VARh |
Reverse reactive energy |
0x0C9C |
3229 |
R |
4 |
Int64 |
VARh |
Total reactive energy |
Partial energy |
||||||
0x0CB8 |
3257 |
R |
4 |
Int64 |
Wh |
Forward partial active energy |
Energy by tariff |
||||||
0x105F |
4192 |
R/WC |
1 |
UInt16 |
- |
Tariff (01 - T1, 02 - T2) |
0x1064 |
4197 |
R |
4 |
Int64 |
Wh |
T1 Forward active energy |
0x1068 |
4201 |
R |
4 |
Int64 |
Wh |
T2 Forward active energy |
0x106C |
4205 |
R |
4 |
Int64 |
Wh |
T1 Reverse active energy |
0x1070 |
4209 |
R |
4 |
Int64 |
Wh |
T2 Reverse active energy |
0x1074 |
4213 |
R |
4 |
Int64 |
Wh |
T1 Total active energy |
0x1078 |
4217 |
R |
4 |
Int64 |
Wh |
T2 Total active energy |
0x107C |
4221 |
R |
4 |
Int64 |
VARh |
T1 Forward reactive energy |
0x1080 |
4225 |
R |
4 |
Int64 |
VARh |
T2 Forward reactive energy |
0x1084 |
4229 |
R |
4 |
Int64 |
VARh |
T1 Reverse reactive energy |
0x1088 |
4233 |
R |
4 |
Int64 |
VARh |
T2 Reverse reactive energy |
0x108C |
4237 |
R |
4 |
Int64 |
VARh |
T1 Total reactive energy |
0x1090 |
4241 |
R |
4 |
Int64 |
VARh |
T2 Total reactive energy |
Energy values – 32-bit floating point
Address | Register | Action | Size | Type | Units | Description |
---|---|---|---|---|---|---|
Total energy (cannot be rest) |
||||||
0xB02C |
45101 |
R |
2 |
Float32 |
Wh |
Forward active energy |
0xB02E |
45103 |
R |
2 |
Float32 |
Wh |
Reverse active energy |
0xB030 |
45105 |
R |
2 |
Float32 |
VARh |
Forward reactive energy |
0xB032 |
45107 |
R |
2 |
Float32 |
VARh |
Reverse reactive energy |
0xB038 |
45113 |
R |
2 |
Float32 |
Wh |
Total active energy |
0xB03A |
45115 |
R |
2 |
Float32 |
VARh |
Total reactive energy |
Partial energy |
||||||
0xB034 |
45109 |
R |
2 |
Float32 |
Wh |
Forward partial active energy |
Energy by tariff |
||||||
0xB040 |
45121 |
R |
4 |
Float32 |
Wh |
T1 Forward active energy |
0xB042 |
45123 |
R |
4 |
Float32 |
Wh |
T2 Forward active energy |
0xB044 |
45125 |
R |
4 |
Float32 |
Wh |
T1 Reverse active energy |
0xB046 |
45127 |
R |
4 |
Float32 |
Wh |
T2 Reverse active energy |
0xB048 |
45129 |
R |
4 |
Float32 |
Wh |
T1 Total active energy |
0xB04A |
45131 |
R |
4 |
Float32 |
Wh |
T2 Total active energy |
0xB04C |
45133 |
R |
4 |
Float32 |
VARh |
T1 Forward reactive energy |
0xB04E |
45135 |
R |
4 |
Float32 |
VARh |
T2 Forward reactive energy |
0xB050 |
45137 |
R |
4 |
Float32 |
VARh |
T1 Reverse reactive energy |
0xB052 |
45139 |
R |
4 |
Float32 |
VARh |
T2 Reverse reactive energy |
0xB054 |
45141 |
R |
4 |
Float32 |
VARh |
T1 Total reactive energy |
0xB056 |
45143 |
R |
4 |
Float32 |
VARh |
T2 Total reactive energy |