48049-137-06EN

Appendix C—Network/Com Access

Remotely Readable Values

The communication option can be used to remotely access the MicroLogic trip unit, using System Manager Software (SMS) (version 3.3 or later) or other network system management software. See the product catalog for more information on the SMS software.

Remotely Readable Values

Item Description Symbol
Current Instantaneous current in A phase Ia
Instantaneous current in B phase Ib
Instantaneous current in C phase Ic
Instantaneous current in neutral In
Instantaneous current in ground
Average instantaneous current in A phase Iaavg
Average instantaneous current in B phase Ibavg
Average instantaneous current in C phase Icavg
Average instantaneous current in neutral Inavg
Average instantaneous current in ground
Maximum instantaneous current in A phase Iamax
Maximum instantaneous current in B phase Ibmax
Maximum instantaneous current in C phase Icmax
Maximum instantaneous current in neutral Inmax
Maximum instantaneous current in ground
Instantaneous current unbalance in A phase Iaunbal
Instantaneous current unbalance in B phase Ibunbal
Instantaneous current unbalance in C phase Icunbal
Instantaneous current unbalance in neutral Inunbal
Instantaneous current unbalance in ground
Max. instantaneous current unbalance in A phase Iaunbal max
Max. instantaneous current unbalance in B phase Ibunbal max
Max. instantaneous current unbalance in C phase Icunbal max
Max. instantaneous current unbalance in neutral Inunbal max
Max. instantaneous current unbalance in ground
Demand Currents Demand current in A phase Ia
Demand current in B phase Ib
Demand current in C phase Ic
Demand current in neutral In
Max. demand current since last reset in A phase Iamax
Max. demand current since last reset in B phase Ibmax
Max. demand current since last reset in C phase Icmax
Max. demand current since last reset in neutral Inmax
Recommended demand current in A phase
Recommended demand current in B phase
Recommended demand current in C phase
Recommended demand current in neutral
Time stamping of demand current max.
Voltage Instantaneous voltage between A and B phase V inst Vab
Instantaneous voltage between B and C phase V inst Vbc
Instantaneous voltage between C and A phase V inst Vca
Instantaneous voltage between A and neutral phase V inst Van
Instantaneous voltage between B and neutral phase V inst Vbn
Instantaneous voltage between C and neutral phase V inst Vcn
Average phase-to-phase voltage between A and B phase V avg Vab
Average phase-to-phase voltage between B and C phase V avg Vbc
Average phase-to-phase voltage between C and A phase V avg Vca
Average phase-to-phase voltage between A phase and neutral V avg Van
Average phase-to-phase voltage between B phase and neutral V avg Vbn
Average phase-to-phase voltage between C phase and neutral V avg Vcn
Voltage unbalance between Vab and mean V unbal Vab
Voltage unbalance between Vbc and mean V unbal Vbc
Voltage unbalance between Vca and mean V unbal Vca
Voltage unbalance between Van and mean V unbal Van
Voltage unbalance between Vbn and mean V unbal Vbn
Voltage unbalance between Vcn and mean V unbal Vcn
Max. voltage unbalance between Vab and mean
Max. voltage unbalance between Vbc and mean
Max. voltage unbalance between Vca and mean
Max. voltage unbalance between Van and mean
Max. voltage unbalance between Vbn and mean
Max. voltage unbalance between Vcn and mean
Active Power Instantaneous active power per phase P
Demand Power Active demand power P
Reactive demand power Q
Apparent demand power S
Max. active demand power since last reset
Max. reactive demand power since last reset
Max. apparent demand power since last reset
Max. predicted active demand power
Max. predicted reactive demand power
Max. predicted apparent demand power
Time stamping of demand power max.
Energy Total active energy E
Active energy in
Active energy out
Fault values Fault type
Interrupted current values
Frequency System frequency F
Update dates Interval between last update of real-time values and the current table
Update date of demand currents, demand power and energy
History Trip history
Alarm history
Event history
Counters Contact wear
Operation counter since last reset
Date/time of last operation counter reset
Operation counter total (lifetime)
Setup Setting of date and time
Password
Trip unit ID code
Trip unit ID name
Measurement calculation algorithm
Sign convention
Total-energy measurement mode
Scale factors
Demand-current calculation window interval
Power quality indication
Demand-power calculation mode
Demand-power calculation window interval
Battery-charge indication
Programmable contact assignments
Programmable contact setup
Waveform capture
Protection Circuit breaker rated current
Type of neutral protection
Long-time protection settings
Short-time protection settings
Instantanaeous protection settings
Ground-fault protection settings
Current-unbalance protection settings
Maximum-current protection settings
Voltage protection settings
Other protective functions settings

List of Registers

The quantities are listed in alphabetical order according to the SMS topic name.

NOTE: A system scan rate of 500 ms or greater is recommended to minimize communications timeout issues.

To access available registers, the following address scheme applies

Module Module Name Equation Address Range
BCM Circuit Breaker Communication Module 1–47
CCM Cradle Communication Module BCM + 50 51–97
PM Protection Module (Internal to trip unit) BCM + 100 101–147
MM Meter Module (Internal to trip unit) BCM + 200 201–247

List of Registers

SMS Topic Name User Description Number of Registers* Register* Module* Units* Scale*
810D_LDPU Circuit breaker LDPU in Progress 1 8862 PM   Scaling N/A
810DBrkrStatus Circuit breaker Status 1 661 BCM   Bit 0; ON = closed; OFF = open
810DBrkrTripStat Circuit breaker Trip Unit Status 1 661 BCM   Bit 2; ON = tripped; OFF = not tripped
BCM_SN BCM Serial Number 4 516 BCM   ASCII text
BkrPos Circuit breaker Position 1 661 CCM   Bit 8 = disconnected
Bit 9 = connected
Bit 10 = test position
CFVAB Crest Factor Voltage A-B 1 1119 MM No Units Hundredths
CFVAN Crest Factor Voltage A-N 1 1122 MM No Units Hundredths
CFVBC Crest Factor Voltage B-C 1 1120 MM No Units Hundredths
CFVBN Crest Factor Voltage B-N 1 1123 MM No Units Hundredths
CFVCA Crest Factor Voltage C-A 1 1121 MM No Units Hundredths
CFVCN Crest Factor Voltage C-N 1 1124 MM No Units Hundredths
DT_3Regs Device Clock Date/Time 4 679 BCM   3-register date/time format*
DTLastTrip D/T of Last Trip 3 693 BCM   3-register date/time format*
DTPkIAD D/T Peak Demand Current A 3 3005 MM   3-register date/time format*
DTPkIBD D/T Peak Demand Current B 3 3008 MM   3-register date/time format*
DTPkICD D/T Peak Demand Current C 3 3011 MM   3-register date/time format*
DTPkIND D/T Peak Demand Current N 3 3014 MM   3-register date/time format*
DTPkKFDA D/T K-Factor Dmd Peak A 3 3041 MM No Units 3-register date/time format*
DTPkKFDB D/T K-Factor Dmd Peak B 3 3044 MM No Units 3-register date/time format*
DTPkKFDC D/T K-Factor Dmd Peak C 3 3047 MM No Units 3-register date/time format*
DTPkKFDN D/T K-Factor Dmd Peak N 3 3050 MM No Units 3-register date/time format*
DTPkkVAD D/T Peak Demand Apparent Power 3 3023 MM   3-register date/time format*
DTPkkVARD D/T Peak Demand Reactive Power 3 3020 MM   3-register date/time format*
DTPkkWD D/T Peak Demand Active Power 3 3017 MM   3-register date/time format*
DTResetEnergy D/T Last Reset Accum. Energies 3 3038 MM   3-register date/time format*
DTResetMinMax D/T Last Reset Min/Max 3 3032 MM   3-register date/time format*
DTResetPkID D/T Last Reset Peak Dmd Currents 3 3026 MM   3-register date/time format*
DTResetPkkWD D/T Last Reset Peak Dmd Power 3 3029 MM   3-register date/time format*
EnableCloseBkr Remote Closing Enabled 1 669 BCM   Bit 2; ON = enabled, OFF = not enabled
EnableOpenBkr Remote Opening Enabled 1 669 BCM   Bit 1; ON = enabled; OFF = not enabled
EnableRemCtrl Remote Control Enabled 1 669 BCM   Bit 3; ON = auto (enabled); OFF = manual (not enabled)
fkVAA Fundamental Apparent Power A 1 1084 MM kVA Scale E
fkVAB Fundamental Apparent Power B 1 1085 MM kVA Scale E
fkVAC Fundamental Apparent Power C 1 1086 MM kVA Scale E
fkVATtl Fundamental Apparent Power Total 1 1087 MM kVA Scale E
fVAngA Fundamental Voltage Ang A-B/A-N 1 1133 MM Deg Tenths
fVAngB Fundamental Voltage Ang B-C/B-N 1 1134 MM Deg Tenths
fVAngC Fundamental Voltage Ang C-A/C-N 1 1135 MM Deg Tenths
GFAlarmStatus GF Alarm Status 1 8860 PM   Bit 0; ON = active; OFF = inactive
GFPreAlarmStatus GF Alarm Pre-Alarm Status 1 8864 PM   Bit 0; ON = active; OFF = inactive
Hz Frequency 1 1054 MM Hz Scale F
IA Current A 1 1016 MM A Scale A - Phase Current
IA_PCT Current A % Load 1 8837 PM % Unity
IAD Demand Current A 1 2200 MM A Scale A
IAppA Current Apparent A 1 1023 MM A Scale A
IAppB Current Apparent B 1 1024 MM A Scale A
IAppC Current Apparent C 1 1025 MM A Scale A
IAppN Current Apparent N 1 1026 MM A Scale B
IAvg Current Avg 1 1027 MM A Scale A - Phase Current
IB Current B 1 1017 MM A Scale A - Phase Current
IB_PCT Current B % Load 1 8838 PM % Unity
IBD Demand Current B 1 2201 MM A Scale A
IC Current C 1 1018 MM A Scale A - Phase Current
IC_PCT Current C % Load 1 8839 PM % Unity
ICD Demand Current C 1 2202 MM A Scale A
IDatPkKFD_A Current Demand at Peak K-Factor Demand A 1 2270 MM A Scale A
IDatPkKFD_B Current Demand at Peak K-Factor Demand B 1 2271 MM A Scale A
IDatPkKFD_C Current Demand at Peak K-Factor Demand C 1 2272 MM A Scale A
IDatPkKFD_N Current Demand at Peak K-Factor Demand N 1 2273 MM A Scale B
IG Current G 1 1021 MM A Scale C
IG_PCT Current G % Load 1 8841 PM % Unity
IG_PCT_VIGI Current G (VIGI) % Load 1 8842 PM % Hundredths
IG_VIGI Current G (VIGI) 1 8826 PM A Thousandths
IMax Current Max Present 1 1020 MM A Scale A - Phase Current
IN Current N 1 1019 MM A Scale B - Neutral Current
IN_PCT Current N % Load 1 8840 PM % Unity
IND Demand Current N 1 2203 MM A Scale B
IUnbalA Current Unbalance A 1 1028 MM % Tenths
IUnbalAlrm Current Unbalance Alarm Status 1 8859 PM   Bit 0; ON = active; OFF = inactive
IUnbalB Current Unbalance B 1 1029 MM % Tenths
IUnbalC Current Unbalance C 1 1030 MM % Tenths
IUnbalPreAlrm Current Unbalance Pre-Alarm Status 1 8863 PM   Bit 0; ON = active, OFF = inactive
IUnbalW Current Unbalance Worst 1 1032 MM % Tenths
KFDatPkID_A K-Factor Demand at Peak Demand Current A 1 2254 MM No Units Tenths
KFDatPkID_B K-Factor Demand at Peak Demand Current B 1 2255 MM No Units Tenths
KFDatPkID_C K-Factor Demand at Peak Demand Current C 1 2256 MM No Units Tenths
KFDatPkID_N K-Factor Demand at Peak Demand Current N 1 2257 MM No Units Tenths
KFDN K-Factor Demand N 1 2215 MM No Units Tenths
KFN K-Factor N 1 1118 MM No Units Tenths
kVAA Apparent Power A 1 1042 MM kVA Scale E
kVAB Apparent Power B 1 1043 MM kVA Scale E
kVAC Apparent Power C 1 1044 MM kVA Scale E
kVAD Demand Apparent Power 1 2236 MM kVA Scale D
kVAD_PkkVARD KVA Dmd Coincident w/Peak KVAR Dmd 1 2235 MM kVA Scale D
kVAD_PkkWD KVA Dmd Coincident w/Peak KW Dmd 1 2229 MM kVA Scale D
kVAHr Apparent Energy 4 2024 MM kVAH Unity
kVARA Reactive Power A 1 1038 MM kVAR Scale E
kVARB Reactive Power B 1 1039 MM kVAR Scale E
kVARC Reactive Power C 1 1040 MM kVAR Scale E
kVARD Demand Reactive Power 1 2230 MM kVAR Scale D
kVARD_PkkVAD KVAR Dmd Coincident w/Peak KVA Dmd 1 2241 MM kVAR Scale D
kVARD_PkkWD KVAR Dmd Coincident w/Peak KW Dmd 1 2228 MM kVAR Scale D
kVARHr Reactive Energy 4 2004 MM kVARH Unity
kVARHr_I Reactive Energy Into the Load 4 2016 MM kVARH Unity
kVARHr_O Reactive Energy Out of the Load 4 2020 MM kVARH Unity
kVARTtl Reactive Power Total 1 1041 MM kVAR Scale E
kVATtl Apparent Power Total 1 1045 MM kVA Scale E
kWA Active Power A 1 1034 MM kW Scale E
kWB Active Power B 1 1035 MM kW Scale E
kWC Active Power C 1 1036 MM kW Scale E
kWD Demand Active Power 1 2224 MM kW Scale D
kWD_PkkVAD KW Dmd Coincident w/Peak KVA Dmd 1 2240 MM kW Scale D
kWD_PkkVARD KW Dmd Coincident w/Peak KVAR Dmd 1 2234 MM kW Scale D
kWHr Real Energy 4 2000 MM kWH Unity
kWHr_I Real Energy Into the Load 4 2008 MM kWH Unity
kWHr_O Real Energy Out of the Load 4 2012 MM kWH Unity
kWTtl Active Power Total 1 1037 MM kW Scale E
LDPUValue Long Delay Pickup Value 2 8756 PM A Unity
LSCurrAlrm Load Shed Current Alarm Status 1 8859 PM   Bit 13; ON = active; OFF = inactive
LSCurrPreAlrm Load Shed Current Pre-Alarm Status 1 8863 PM   Bit 13; ON = active; OFF = inactive
LSPwrAlrm Load Shed Power Alarm Status 1 8859 PM   Bit 14; ON = active; OFF = inactive
LSPwrPreAlrm Load Shed Power Pre-Alarm Status 1 8863 PM   Bit 14; ON = active; OFF = inactive
M2C_M6CR1Status Relay Module R1 Status 1 8857 PM   Bit 0; ON = on; OFF = off
M2C_M6CR2Status Relay Module R2 Status 1 8857 PM   Bit 1; ON = on; OFF = off
M2C_M6CR3Status Relay Module R3 Status 1 8857 PM   Bit 2; ON = on; OFF = off
M2C_M6CR4Status Relay Module R4 Status 1 8857 PM   Bit 3; ON = on; OFF = off
M2C_M6CR5Status Relay Module R5 Status 1 8857 PM   Bit 4; ON = on; OFF = off
M2C_M6CR6Status Relay Module R6 Status 1 8857 PM   Bit 5; ON = on; OFF = off
MaxCFVAB Maximum Crest Factor Voltage A-B 1 1719 MM No Units Hundredths
MaxCFVAN Maximum Crest Factor Voltage A-N 1 1722 MM No Units Hundredths
MaxCFVBC Maximum Crest Factor Voltage B-C 1 1720 MM No Units Hundredths
MaxCFVBN Maximum Crest Factor Voltage B-N 1 1723 MM No Units Hundredths
MaxCFVCA Maximum Crest Factor Voltage C-A 1 1721 MM No Units Hundredths
MaxCFVCN Maximum Crest Factor Voltage C-N 1 1724 MM No Units Hundredths
MaxfkVAA Maximum Fundamental Apparent Power A 1 1684 MM kVA Scale E
MaxfkVAB Maximum Fundamental Apparent Power B 1 1685 MM kVA Scale E
MaxfkVAC Maximum Fundamental Apparent Power C 1 1686 MM kVA Scale E
MaxfkVATtl Maximum Fundamental Apparent Power Total 1 1687 MM kVA Scale E
MaxfVMagAB Maximum Fundamental Voltage Mag A-B 1 1656 MM V Scale D
MaxfVMagAN Maximum Fundamental Voltage Mag A-N 1 1659 MM V Scale D
MaxfVMagBC Maximum Fundamental Voltage Mag B-C 1 1657 MM V Scale D
MaxfVMagBN Maximum Fundamental Voltage Mag B-N 1 1660 MM V Scale D
MaxfVMagCA Maximum Fundamental Voltage Mag C-A 1 1658 MM V Scale D
MaxfVMagCN Maximum Fundamental Voltage Mag C-N 1 1661 MM V Scale D
MaxHz Max Frequency 1 1654 MM Hz Scale F
MaxIA Max Current A 1 1616 MM A Scale A - Phase Current
MaxIAppA Maximum Current Apparent A 1 1623 MM A Scale A
MaxIAppB Maximum Current Apparent B 1 1624 MM A Scale A
MaxIAppC Maximum Current Apparent C 1 1625 MM A Scale A
MaxIAppN Maximum Current Apparent N 1 1626 MM A Scale B
MaxIAvg Max Current Avg 1 1627 MM A Scale A - Phase Current
MaxIB Max Current B 1 1617 MM A Scale A - Phase Current
MaxIC Max Current C 1 1618 MM A Scale A - Phase Current
MaxIG Max Current G 1 1621 MM A Scale C
MaxIG_VIGI Max Current G (VIGI) 1 8832 PM A Thousandths
MaxIN Max Current N 1 1619 MM A Scale B - Neutral Current
MaxIUnbalA Max Current Unbalance A 1 1628 MM % Tenths
MaxIUnbalB Max Current Unbalance B 1 1629 MM % Tenths
MaxIUnbalC Max Current Unbalance C 1 1630 MM % Tenths
MaxIUnbalW Max Current Unbalance Worst 1 1632 MM % Tenths
MaxKFN Maximum K-Factor N 1 1718 MM No Units Tenths
MaxkVAA Max Apparent Power A 1 1642 MM kVA Scale E
MaxkVAB Max Apparent Power B 1 1643 MM kVA Scale E
MaxkVAC Max Apparent Power C 1 1644 MM kVA Scale E
MaxkVARA Max Reactive Power A 1 1638 MM kVAR Scale E
MaxkVARB Max Reactive Power B 1 1639 MM kVAR Scale E
MaxkVARC Max Reactive Power C 1 1640 MM kVAR Scale E
MaxkVARTtl Max Reactive Power Total 1 1641 MM kVAR Scale E
MaxkVATtl Max Apparent Power Total 1 1645 MM kVA Scale E
MaxkWA Max Active Power A 1 1634 MM kW Scale E
MaxkWB Max Active Power B 1 1635 MM kW Scale E
MaxkWC Max Active Power C 1 1636 MM kW Scale E
MaxkWTtl Max Active Power Total 1 1637 MM kW Scale E
MaxPFA Max Power Factor A 3 1646 MM   PF format*
MaxPFB Max Power Factor B 3 1647 MM   PF format*
MaxPFC Max Power Factor C 3 1648 MM   PF format*
MaxPFTtl Max Power Factor Total 3 1649 MM   PF format*
MaxVAB Max Voltage A-B 1 1600 MM V Scale D - Voltage
MaxVAN Max Voltage A-N 1 1603 MM V Scale D - Voltage
MaxVBC Max Voltage B-C 1 1601 MM V Scale D - Voltage
MaxVBN Max Voltage B-N 1 1604 MM V Scale D - Voltage
MaxVCA Max Voltage C-A 1 1602 MM V Scale D - Voltage
MaxVCN Max Voltage C-N 1 1605 MM V Scale D - Voltage
MaxVLLAvg Max Voltage L-L Avg 1 1606 MM V Scale D - Voltage
MaxVLNAvg Max Voltage L-N Avg 1 1607 MM V Scale D - Voltage
MaxVUnbalAB Max Voltage Unbalance A-B 1 1608 MM % Tenths
MaxVUnbalAN Max Voltage Unbalance A-N 1 1611 MM % Tenths
MaxVUnbalBC Max Voltage Unbalance B-C 1 1609 MM % Tenths
MaxVUnbalBN Max Voltage Unbalance B-N 1 1612 MM % Tenths
MaxVUnbalCA Max Voltage Unbalance C-A 1 1610 MM % Tenths
MaxVUnbalCN Max Voltage Unbalance C-N 1 1613 MM % Tenths
MaxVUnbalLLW Max Voltage Unbalance L-L Worst 1 1614 MM % Tenths
MaxVUnbalLNW Max Voltage Unbalance L-N Worst 1 1615 MM % Tenths
MinCFVAB Minimum Crest Factor Voltage A-B 1 1419 MM No Units Hundredths
MinCFVAN Minimum Crest Factor Voltage A-N 1 1422 MM No Units Hundredths
MinCFVBC Minimum Crest Factor Voltage B-C 1 1420 MM No Units Hundredths
MinCFVBN Minimum Crest Factor Voltage B-N 1 1423 MM No Units Hundredths
MinCFVCA Minimum Crest Factor Voltage C-A 1 1421 MM No Units Hundredths
MinCFVCN Minimum Crest Factor Voltage C-N 1 1424 MM No Units Hundredths
MinfkVAA Minimum Fundamental Apparent Power A 1 1384 MM kVA Scale E
MinfkVAB Minimum Fundamental Apparent Power B 1 1385 MM kVA Scale E
MinfkVAC Minimum Fundamental Apparent Power C 1 1386 MM kVA Scale E
MinfkVATtl Minimum Fundamental Apparent Power Total 1 1387 MM kVA Scale E
MinfVMagAB Minimum Fundamental Voltage Mag A-B 1 1356 MM V Scale D
MinfVMagAN Minimum Fundamental Voltage Mag A-N 1 1359 MM V Scale D
MinfVMagBC Minimum Fundamental Voltage Mag B-C 1 1357 MM V Scale D
MinfVMagBN Minimum Fundamental Voltage Mag B-N 1 1360 MM V Scale D
MinfVMagCA Minimum Fundamental Voltage Mag C-A 1 1358 MM V Scale D
MinfVMagCN Minimum Fundamental Voltage Mag C-N 1 1361 MM V Scale D
MinHz Min Frequency 1 1354 MM Hz Scale F
MinIA Min Current A 1 1316 MM A Scale A - Phase Current
MinIAppA Minimum Current Apparent A 1 1323 MM A Scale A
MinIAppB Minimum Current Apparent B 1 1324 MM A Scale A
MinIAppC Minimum Current Apparent C 1 1325 MM A Scale A
MinIAppN Minimum Current Apparent N 1 1326 MM A Scale B
MinIAvg Min Current Avg 1 1327 MM A Scale A - Phase Current
MinIB Min Current B 1 1317 MM A Scale A - Phase Current
MinIC Min Current C 1 1318 MM A Scale A - Phase Current
MinIN Min Current N 1 1319 MM A Scale B - Neutral Current
MinIUnbalA Min Current Unbalance A 1 1328 MM % Tenths
MinIUnbalB Min Current Unbalance B 1 1329 MM % Tenths
MinIUnbalC Min Current Unbalance C 1 1330 MM % Tenths
MinIUnbalW Min Current Unbalance Worst 1 1332 MM % Tenths
MinKFN Minimum K-Factor N 1 1418 MM No Units Tenths
MinkVAA Min Apparent Power A 1 1342 MM kVA Scale E
MinkVAB Min Apparent Power B 1 1343 MM kVA Scale E
MinkVAC Min Apparent Power C 1 1344 MM kVA Scale E
MinkVARA Min Reactive Power A 1 1338 MM kVAR Scale E
MinkVARB Min Reactive Power B 1 1339 MM kVAR Scale E
MinkVARC Min Reactive Power C 1 1340 MM kVAR Scale E
MinkVARTtl Min Reactive Power Total 1 1341 MM kVAR Scale E
MinkVATtl Min Apparent Power Total 1 1345 MM kVA Scale E
MinkWA Min Active Power A 1 1334 MM kW Scale E
MinkWB Min Active Power B 1 1335 MM kW Scale E
MinkWC Min Active Power C 1 1336 MM kW Scale E
MinkWTtl Min Active Power Total 1 1337 MM kW Scale E
MinPFA Min Power Factor A 3 1346 MM   PF format*
MinPFB Min Power Factor B 3 1347 MM   PF format*
MinPFC Min Power Factor C 3 1348 MM   PF format*
MinPFTtl Min Power Factor Total 3 1349 MM   PF format*
MinVAB Min Voltage A-B 1 1300 MM V Scale D - Voltage
MinVAN Min Voltage A-N 1 1303 MM V Scale D - Voltage
MinVBC Min Voltage B-C 1 1301 MM V Scale D - Voltage
MinVBN Min Voltage B-N 1 1304 MM V Scale D - Voltage
MinVCA Min Voltage C-A 1 1302 MM V Scale D - Voltage
MinVCN Min Voltage C-N 1 1305 MM V Scale D - Voltage
MinVLLAvg Min Voltage L-L Avg 1 1306 MM V Scale D - Voltage
MinVLNAvg Min Voltage L-N Avg 1 1307 MM V Scale D - Voltage
MinVUnbalAB Min Voltage Unbalance A-B 1 1308 MM % Tenths
MinVUnbalAN Min Voltage Unbalance A-N 1 1311 MM % Tenths
MinVUnbalBC Min Voltage Unbalance B-C 1 1309 MM % Tenths
MinVUnbalBN Min Voltage Unbalance B-N 1 1312 MM % Tenths
MinVUnbalCA Min Voltage Unbalance C-A 1 1310 MM % Tenths
MinVUnbalCN Min Voltage Unbalance C-N 1 1313 MM % Tenths
MinVUnbalLLW Min Voltage Unbalance L-L Worst 1 1314 MM % Tenths
MinVUnbalLNW Min Voltage Unbalance L-N Worst 1 1315 MM % Tenths
NominalCurrent Circuit breaker Nominal Current 1 8750 PM A Unity
OverFreqAlrm Over Frequency Alarm Status 1 8859 PM   Bit 11; ON = active, OFF = inactive
OverFreqPreAlrm Over Frequency Pre-Alarm Status 1 8863 PM   Bit 11; ON = active, OFF = inactive
OverIAAlrm Over IA Demand Alarm Status 1 8859 PM   Bit 1; ON = active, OFF = inactive
OverIAPreAlrm Over IA Demand Pre-Alarm Status 1 8863 PM   Bit 1; ON = active, OFF = inactive
OverIBAlrm Over IB Demand Alarm Status 1 8859 PM   Bit 2; ON = active, OFF = inactive
OverIBPreAlrm Over IB Demand Pre-Alarm Status 1 8863 PM   Bit 2; ON = active, OFF = inactive
OverICAlrm Over IC Demand Alarm Status 1 8859 PM   Bit 3; ON = active, OFF = inactive
OverICPreAlrm Over IC Demand Pre-Alarm Status 1 8863 PM   Bit 3; ON = active, OFF = inactive
OverINAlrm Over IN Demand Alarm Status 1 8859 PM   Bit 4; ON = active, OFF = inactive
OverINPreAlrm Over IN Demand Pre-Alarm Status 1 8863 PM   Bit 4; ON = active, OFF = inactive
OverVoltAlrm Over Voltage Alarm Status 1 8859 PM   Bit 6; ON = active, OFF = inactive
OverVoltPreAlrm Over Voltage Pre-Alarm Status 1 8863 PM   Bit 6; ON = active, OFF = inactive
PF_PkkVAD PF Coincident w/Peak KVA Demand 3 2239 MM   Thousandths
PF_PkkVARD PF Coincident w/Peak KVAR Demand 3 2233 MM   Thousandths
PF_PkkWD PF Coincident w/Peak KW Demand 3 2227 MM   Thousandths
PFA Power Factor A 3 1046 MM   PF format*
PFB Power Factor B 3 1047 MM   PF format*
PFC Power Factor C 3 1048 MM   PF format*
PFTtl Power Factor Total 3 1049 MM   PF format*
PhaRotAlrm Phase Rotation Alarm Status 1 8859 PM   Bit 12; ON = active, OFF = inactive
PkIAD Peak Demand Current A 1 2204 MM A Scale A
PkIBD Peak Demand Current B 1 2205 MM A Scale A
PkICD Peak Demand Current C 1 2206 MM A Scale A
PkIND Peak Demand Current N 1 2207 MM A Scale A
PkKFDA Peak K-Factor Demand A 1 2216 MM No Units Tenths
PkKFDB Peak K-Factor Demand B 1 2217 MM No Units Tenths
PkKFDC Peak K-Factor Demand C 1 2218 MM No Units Tenths
PkKFDN Peak K-Factor Demand N 1 2219 MM No Units Tenths
PkkVAD Peak Demand Apparent Power 1 2237 MM kVA Scale A
PkkVARD Peak Demand Reactive Power 1 2231 MM kVAR Scale A
PkkWD Peak Demand Active Power 1 2225 MM kW Scale A
PredIAD Predicted Demand Current A 1 2208 MM A Scale A
PredIBD Predicted Demand Current B 1 2209 MM A Scale A
PredICD Predicted Demand Current C 1 2210 MM A Scale A
PredIND Predicted Demand Current N 1 2211 MM A Scale A
PredKFDA Predicted K-Factor Demand A 1 2220 MM No Units Tenths
PredKFDB Predicted K-Factor Demand B 1 2221 MM No Units Tenths
PredKFDC Predicted K-Factor Demand C 1 2222 MM No Units Tenths
PredKFDN Predicted K-Factor Demand N 1 2223 MM No Units Tenths
PredkVAD Predicted KVA Demand 1 2238 MM kVA Scale A
PredkVARD Predicted KVAR Demand 1 2232 MM kVAR Scale A
PredkWD Predicted KW Demand 1 2226 MM kW Scale A
R1OpsCounter Relay 1 Operations Counter 1 9081 PM   Unity
R2OpsCounter Relay 2 Operations Counter 1 9082 PM   Unity
R3OpsCounter Relay 3 Operations Counter 1 9083 PM   Unity
R4OpsCounter Relay 4 Operations Counter 1 9084 PM   Unity
R5OpsCounter Relay 5 Operations Counter 1 9085 PM   Unity
R6OpsCounter Relay 6 Operations Counter 1 9086 PM   Unity
ReadyToClose Breaker Ready to Close 1 661 BCM   Bit 5; ON = yes, OFF = no
RevPwrAlrm Reverse Power Alarm Status 1 8859 PM   Bit 9; ON = active; OFF = inactive
RevPwrPreAlrm Reverse Power Pre-Alarm Status 1 8863 PM   Bit 9; ON = active; OFF = inactive
TimeToTrip Time Remaining to LT Trip 2 8865 PM   Tenths
TU_BATT_PCT Trip Unit % Battery 1 8843 PM % Unity
TU_SN Trip Unit Serial Number 4 8700 PM   ASCII text
TUCommStatus Trip Unit Internal Comms Status 1 552 BCM   Bit 11; ON = not responding; OFF = OK
UnderFreqAlrm Under Frequency Alarm Status 1 8859 PM   Bit 10; ON = active; OFF = inactive
UnderFreqPreAlrm Under Frequency Pre-Alarm Status 1 8863 PM   Bit 10; ON = active; OFF = inactive
UnderVoltAlrm Under Voltage Alarm Status 1 8859 PM   Bit 5; ON = active; OFF = inactive
UnderVoltPreAlrm Under Voltage Pre-Alarm Status 1 8863 PM   Bit 5; ON = active; OFF = inactive
VAB Voltage A-B 1 1000 MM V Scale D - Voltage
VAN Voltage A-N 1 1003 MM V Scale D - Voltage
VBC Voltage B-C 1 1001 MM V Scale D - Voltage
VBN Voltage B-N 1 1004 MM V Scale D - Voltage
VCA Voltage C-A 1 1002 MM V Scale D - Voltage
VCN Voltage C-N 1 1005 MM V Scale D - Voltage
VigiAlarm Vigi Alarm Status 1 8860 PM   Bit 1; ON = active; OFF = inactive
VigiPreAlrm Vigi Pre-Alarm Status 1 8864 PM   Bit 1; ON = active; OFF = inactive
VLLAvg Voltage L-L Avg 1 1006 MM V Scale D - Voltage
VLNAvg Voltage L-N Avg 1 1007 MM V Scale D - Voltage
VUnbalAB Voltage Unbalance A-B 1 1008 MM % Tenths
VUnbalAlrm Voltage Unbalance Alarm Status 1 8859 PM   Bit 7; ON = active, OFF = inactive
VUnbalAN Voltage Unbalance A-N 1 1011 MM % Tenths
VUnbalBC Voltage Unbalance B-C 1 1009 MM % Tenths
VUnbalBN Voltage Unbalance B-N 1 1012 MM % Tenths
VUnbalCA Voltage Unbalance C-A 1 1010 MM % Tenths
VUnbalCN Voltage Unbalance C-N 1 1013 MM % Tenths
VUnbalLLW Voltage Unbalance L-L Worst 1 1014 MM % Tenths
VUnbalLNW Voltage Unbalance L-N Worst 1 1015 MM % Tenths
VUnbalPreAlrm Voltage Unbalance Pre-Alarm Status 1 8863 PM   Bit 7; ON = active, OFF = inactive
QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.