990–5939–001

Connect the Signal Cables

NOTE: The illustrations in this procedure show a bottom cable entry system. The procedure is the same for a top cable entry system.
  1. Install the temperature sensor from the optional installation kit E3SOPT003.
    NOTE: The length of the temperature sensor cable is 5.8 meter.

    Front View of the Empty Classic Battery Cabinet

  2. Route the battery temperature sensor cables through the top or the bottom of the empty classic battery cabinet to the UPS dry contact terminal J2–1 and J2–2 and connect as shown.
  3. Route the signal cables through the top or bottom of the empty classic battery cabinet to the battery breaker.
  4. Remove the cover from the battery breaker.
  5. Connect the signal cables:
    1. Connect the Aux switch signal cables from the empty classic battery cabinet to J6–2 and J7–1 in the UPS.
    2. Connect the shunt trip coil signal cables from the empty classic battery cabinet to J5–3 and J6–1 in the UPS.
  6. Reinstall the breaker cover on the battery breaker.
QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?