990-55224-001

Alarm List

Please provide list of alarm messages

Protection Protocols

Protection Protocol for Battery Cabinet with 17 Battery Modules

No Item Level Set condition Software set time (sec) Battery breaker status* Release condition Time (sec) Battery breaker status
1 Over voltage protection - cell Major Max cell ≥ 4.28 V 5 OFF Max cell <4.25 V and press the reset switch 5 ON
2 Under voltage protection - cell Major Min cell ≤ 2.5 V 3 OFF Min cell > 2.70 V and press the reset switch 3 ON
3 Over voltage protection - cabinet Major Cabinet voltage ≥ 582.08 V 5 OFF Cabinet voltage < 578 V and press the reset switch 5 ON
4 Under voltage protection - cabinet Major Cabinet voltage ≤ 340 V 3 OFF Cabinet voltage > 367.2 V and press the reset switch 3 ON
5 Voltage imbalance Major Max cell ≥ 3.80 V and △Vcell ≥ 100 mV 5 OFF △Vcell 30 mV and press the reset switch 5 ON
6 Voltage sensing error (cabinet) Minor │Cabinet V - cell sum V│ ≥ 40.8 V 10 ON │Cabinet V - cell sum V│ < 20.4 V and press the reset switch 3 ON
7 Voltage sensing error (module) Minor │Module V - cell sum V│ ≥ 190 mV 5 ON │Module V - cell sum V│ < 190 mV and press the reset switch 3 ON
8 Over temperature protection Major Max temp ≥ 75 °C (167 °F) 3 OFF Max temp < 65 °C (149 °F) and press the reset switch 3 ON
9 Under temperature protection Minor Min temp ≤ 0 °C (32 °F) 3 ON Min temp > 5 °C (41 °F) and press the reset switch 3 ON
10 Temperature imbalance Major Max cell T - min cell T ≥ 40 ℃ (104 °F) 30 OFF Max cell T - min cell T < 20 °C (68 °F) and press the reset switch 3 ON
11 Over current protection (charge) Major Level2 current ≥ 250 A 2 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level1 current ≥ 200 A 60 OFF |Current| < 10 A and press the reset switch 3 ON
12 Over current protection (discharge) Major Level4 |current| ≥ 600 A 1 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level3 |current| ≥ 540 A 10 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level2 |current| ≥ 495 A 30 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level1 |current| ≥ 470 A 60 OFF |Current| < 10 A and press the reset switch 3 ON
13 Communication lost (module ↔ cabinet) Major No communication 30 OFF Communication reestablished and press the reset switch - ON
14 Communication lost (cabinet ↔ system ) Minor No communication 30 ON Communication reestablished and press the reset switch - ON
15 SW failure - battery breaker Minor Battery breaker OFF and |current| ≥ 2.4 A 3 ON (Battery breaker OFF and (|current| < 2.4 A) and press the reset switch - ON
16 SW sensor failure - battery breaker Minor Battery breaker contact ON = battery breaker trip ON 3 ON (Battery breaker contact ≠ battery breaker trip) and press the reset switch - ON
17 Current sensing error Minor No communication with Current IC 3 ON Communication with current IC OK - ON
18 Fuse failure Minor Fuse blown 10 ON Fuse ON and press the reset switch - ON

Protection Protocol for Battery Cabinet with 16 Battery Modules

No Item Level Set condition Software set time (sec) Battery breaker status* Release condition Time (sec) Battery breaker status
1 Over voltage protection - cell Major Max cell ≥ 4.28 V 5 OFF Max cell < 4.25 V and press the reset switch 5 ON
2 Under voltage protection - cell Major Min cell ≤ 2.5 V 3 OFF Min cell > 2.70 V and press the reset switch 3 ON
3 Over voltage protection - cabinet Major Cabinet voltage ≥ 547.84 V 5 OFF Cabinet voltage < 544 V and press the reset switch 5 ON
4 Under voltage protection - cabinet Major Cabinet voltage ≤ 320 V 3 OFF Cabinet voltage > 345.6 V and press the reset switch 3 ON
5 Voltage imbalance Major Max cell ≥ 3.80 V and △Vcell ≥ 100 mV 5 OFF △Vcell < 30 mV and press the reset switch 5 ON
6 Voltage sensing error (cabinet) Minor │Cabinet V - cell sum V│ ≥ 38.4 V 10 ON │Cabinet V - cell sum V│ < 19.2 V and press the reset switch 3 ON
7 Voltage sensing error (module) Minor │Module V - cell sum V│ ≥ 190 mV 5 ON │Module V - cell sum V│ < 190 mV and press the reset switch 3 ON
8 Over temperature protection Major Max temp ≥ 75 ℃ (167 °F) 3 OFF Max temp < 65 °C (149 °F)and press the reset switch 3 ON
9 Under temperature protection Minor Min temp ≤ 0 ℃ (32 °F) 3 ON Min temp > 5 °C (41 °F)and press the reset switch 3 ON
10 Temperature imbalance Major Max cell T - min cell T ≥ 40 ℃ (104 °F) 30 OFF Max cell T - min cell T < 20 °C (68 °F) and press the reset switch 3 ON
11 Over current protection (charge) Major Level2 current ≥ 250 A 2 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level1 current ≥ 200 A 60 OFF |Current| < 10 A and press the reset switch 3 ON
12 Over current protection (discharge) Major Level4 |current| ≥ 600 A 1 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level3 |current| ≥ 540 A 10 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level2 |current| ≥ 495 A 30 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level1 |current| ≥ 470 A 60 OFF |Current| < 10 A and press the reset switch 3 ON
13 Communication lost (module ↔ cabinet) Major No communication 30 OFF Communication reestablished and press the reset switch - ON
14 Communication lost (cabinet ↔ system ) Minor No communication 30 ON Communication reestablished and press the reset switch - ON
15 SW failure - battery breaker Minor Battery breaker OFF and |current| ≥ 2.4 A 3 ON (Battery breaker OFF and (|current| < 2.4 A) and press the reset switch - ON
16 SW sensor failure - battery breaker Minor Battery breaker contact ON = battery breaker trip ON 3 ON (Battery breaker contact ≠ battery breaker trip) and press the reset switch - ON
17 Current sensing error Minor No communication with Current IC 3 ON Communication with current IC OK - ON
18 Fuse failure Minor Fuse blown 10 ON Fuse ON and press the reset switch - ON

Protection Protocol for Battery Cabinet with 13 Battery Modules

No Item Level Set condition Software set time (sec) Battery breaker status* Release condition Time (sec) Battery breaker status
1 Over voltage protection - cell Major Max cell ≥ 4.28 V 5 OFF Max cell <4.25 V and press the reset switch 5 ON
2 Under voltage protection - cell Major Min cell ≤ 2.5 V 3 OFF Min cell > 2.70 V and press the reset switch 3 ON
3 Over voltage protection - cabinet Major Cabinet voltage ≥ 445.12 V 5 OFF Cabinet voltage < 442 V and press the reset switch 5 ON
4 Under voltage protection - cabinet Major Cabinet voltage ≤ 260 V 3 OFF Cabinet voltage > 280.8 V and press the reset switch 3 ON
5 Voltage imbalance Major Max cell ≥ 3.80 V and △Vcell ≥ 100 mV 5 OFF △Vcell < 30 mV and press the reset switch 5 ON
6 Voltage sensing error (cabinet) Minor │Cabinet V - cell sum V│ ≥ 31.2 V 10 ON │Cabinet V - cell sum V│ < 15.6 V and press the reset switch 3 ON
7 Voltage sensing error (module) Minor │Module V - cell sum V│ ≥ 190 mV 5 ON │Module V - cell sum V│ < 190 mV and press the reset switch 3 ON
8 Over temperature protection Major Max temp ≥ 75 ℃ (167 °F) 3 OFF Max temp < 65 °C (149 °F) and press the reset switch 3 ON
9 Under temperature protection Minor Min temp ≤ 0 ℃ (32 °F) 3 ON Min temp > 5 °C (41 °F) and press the reset switch 3 ON
10 Temperature imbalance Major Max cell T - min cell T ≥ 40 ℃ (104 °F) 30 OFF Max cell T - min cell T < 20 °C (68 °F) and press the reset switch 3 ON
11 Over current protection (charge) Major Level2 current ≥ 250 A 2 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level1 current ≥ 200 A 60 OFF |Current| < 10 A and press the reset switch 3 ON
12 Over current protection (discharge) Major Level4 |current| ≥ 600 A 1 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level3 |current| ≥ 540 A 10 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level2 |current| ≥ 495 A 30 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level1 |current| ≥ 470 A 60 OFF |Current| < 10 A and press the reset switch 3 ON
13 Communication lost (module ↔ cabinet) Major No communication 30 OFF Communication reestablished and press the reset switch - ON
14 Communication lost (cabinet ↔ system ) Minor No communication 30 ON Communication reestablished and press the reset switch - ON
15 SW failure - battery breaker Minor Battery breaker OFF and |current| ≥ 2.4 A 3 ON (Battery breaker OFF and (|current| < 2.4 A) and press the reset switch - ON
16 SW sensor failure - battery breaker Minor Battery breaker contact ON = battery breaker trip ON 3 ON (Battery breaker contact ≠ battery breaker trip) and press the reset switch - ON
17 Current sensing error Minor No communication with Current IC 3 ON Communication with current IC OK - ON
18 Fuse failure Minor Fuse blown 10 ON Fuse ON and press the reset switch - ON

Protection Protocol for Battery Cabinet with 10 Battery Modules

No Item Level Set condition Software set time (sec) Battery breaker status* Release condition Time (sec) Battery breaker status
1 Over voltage protection - cell Major Max cell ≥ 4.28 V 5 OFF Max cell <4.25 V and press the reset switch 5 ON
2 Under voltage protection - cell Major Min cell ≤ 2.5 V 3 OFF Min cell > 2.70 V and press the reset switch 3 ON
3 Over voltage protection - cabinet Major Cabinet voltage ≥ 342.4 V 5 OFF Cabinet voltage < 340 V and press the reset switch 5 ON
4 Under voltage protection - cabinet Major Cabinet voltage ≤ 200 V 3 OFF Cabinet voltage > 216 V and press the reset switch 3 ON
5 Voltage imbalance Major Max cell ≥ 3.80 V and △Vcell ≥ 100 mV 5 OFF △Vcell 30 mV and press the reset switch 5 ON
6 Voltage sensing error (cabinet) Minor │Cabinet V - cell sum V│ ≥ 24 V 10 ON │Cabinet V - cell sum V│ < 12 V and press the reset switch 3 ON
7 Voltage sensing error (module) Minor │Module V - cell sum V│ ≥ 190 mV 5 ON │Module V - cell sum V│ < 190 mV and press the reset switch 3 ON
8 Over temperature protection Major Max temp ≥ 75 °C (167 °F) 3 OFF Max temp < 65 °C (149 °F) and press the reset switch 3 ON
9 Under temperature protection Minor Min temp ≤ 0 °C (32 °F) 3 ON Min temp > 5 °C (41 °F) and press the reset switch 3 ON
10 Temperature imbalance Major Max cell T - min cell T ≥ 40 ℃ (104 °F) 30 OFF Max cell T - min cell T < 20 °C (68 °F) and press the reset switch 3 ON
11 Over current protection (charge) Major Level2 current ≥ 250 A 2 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level1 current ≥ 200 A 60 OFF |Current| < 10 A and press the reset switch 3 ON
12 Over current protection (discharge) Major Level4 |current| ≥ 600 A 1 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level3 |current| ≥ 540 A 10 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level2 |current| ≥ 495 A 30 OFF |Current| < 10 A and press the reset switch 3 ON
Major Level1 |current| ≥ 470 A 60 OFF |Current| < 10 A and press the reset switch 3 ON
13 Communication lost (module ↔ cabinet) Major No communication 30 OFF Communication reestablished and press the reset switch - ON
14 Communication lost (cabinet ↔ system ) Minor No communication 30 ON Communication reestablished and press the reset switch - ON
15 SW failure - battery breaker Minor Battery breaker OFF and |current| ≥ 2.4 A 3 ON (Battery breaker OFF and (|current| < 2.4 A) and press the reset switch - ON
16 SW sensor failure - battery breaker Minor Battery breaker contact ON = battery breaker trip ON 3 ON (Battery breaker contact ≠ battery breaker trip) and press the reset switch - ON
17 Current sensing error Minor No communication with Current IC 3 ON Communication with current IC OK - ON
18 Fuse failure Minor Fuse blown 10 ON Fuse ON and press the reset switch - ON