Activation code is not valid for UPS |
Critical |
The activation code is not valid for
the UPS. |
Enter a valid activation code. |
Activation code missing |
Critical |
The activation code is missing. |
Enter the activation code. |
Air filter technical check recommended |
Informational |
The air filters need to be checked as
preventive maintenance is recommended. |
The air filters may need to be replaced. |
Ambient temperature high |
Warning |
Ambient temperature is high. |
|
Ambient temperature out of tolerance |
Warning |
Ambient temperature is out of tolerance. |
|
Available UPS power lower than configured UPS power rating |
Warning |
The available power from inverter is
lower than the configured UPS power rating. |
|
Batteries are discharging |
Warning |
The load is drawing more power than the
UPS can draw from the input, causing the UPS to draw power from the
batteries. |
|
Battery breaker BB1 open |
Warning |
Battery breaker BB1 is open. |
|
Battery breaker BB2 open |
Warning |
Battery breaker BB2 is open. |
|
Battery capacity is below minimum acceptable level |
Warning |
The battery capacity is below the minimum
acceptable value according to UPS power rating. Risk of battery damage. |
Change battery configuration and/or add larger
capacity battery. |
Battery condition is poor |
Warning |
Battery capacity is lower than 50%. |
Batteries should be replaced. |
Battery condition is weak |
Warning |
Battery capacity is between 50% to 75%. |
|
Battery configuration is incorrect |
Warning |
The configuration of the settings for
number of batteries in series, number of cells in battery and nominal
cell voltage does not match the battery voltage range of the UPS. |
Check and correct battery settings. |
Battery float charge current exceeds expected value |
Warning |
The battery float charge current exceeds
the expected value and has been limited to avoid thermal runaway. |
Check battery. |
Battery is below minimum acceptable runtime |
Warning |
The battery runtime is below configured
minimum acceptable value. |
|
Battery is not working correctly |
Critical |
A battery is not working correctly. |
Contact
Schneider Electric. |
Battery module temperature out of tolerance |
Warning |
Battery module temperature is out of
tolerance. |
Contact
Schneider Electric. |
Battery module temperature sensor not working correctly |
Warning |
Battery module temperature sensor is
not working correctly. |
Contact
Schneider Electric. |
Battery module type unknown |
Warning |
Battery module type is unknown. |
Contact
Schneider Electric. |
Battery room ventilation inoperable |
Warning |
Input contact indicates that the battery
room ventilation is not working correctly. |
|
Battery voltage does not match battery configuration |
Critical |
Battery voltage does not match the battery
configuration settings. |
Check and correct battery settings. |
BMC communication lost - connected |
Warning |
Communication link between battery monitor
controller (BMC) and system level controller (SLC) is lost. Battery
monitor controller (BMC) is connected. |
Contact
Schneider Electric. |
BMC communication lost - disconnected |
Warning |
Communication link between battery monitor
controller (BMC) and system level controller (SLC) is lost. Battery
monitor controller (BMC) is disconnected. |
Contact
Schneider Electric. |
BMC communication not authenticated |
Warning |
Communication link between battery monitor
controller (BMC) and system level controller (SLC) is not authenticated. |
Contact
Schneider Electric. |
Bonding between neutral and ground missing |
Warning |
Bonding between neutral and ground is
missing. |
|
Breaker IMB closed |
Warning |
Internal maintenance breaker IMB is closed,
supplying the load with unprotected power from bypass. |
|
Breaker MBB closed |
Warning |
Maintenance bypass breaker MBB is closed,
supplying the load with unprotected power from bypass. |
|
Breaker RIMB closed |
Warning |
Remote internal maintenance bypass breaker
RIMB is closed, supplying the load with unprotected power from bypass. |
|
Breaker SIB open |
Warning |
System isolation breaker SIB is open,
and system cannot supply the load. |
|
Breaker SSIB open |
Warning |
Static switch input breaker SSIB is open,
preventing static bypass operation. |
|
Breaker UIB open |
Warning |
Unit input breaker UIB is open, and the
UPS is prevented from running in normal operation. |
|
Breaker UOB open |
Warning |
Unit output breaker UOB is open, and
the UPS is prevented from supplying the load. |
|
Bypass frequency out of tolerance |
Warning |
Bypass frequency is out of tolerance. |
Check bypass frequency and bypass frequency setting. |
Bypass phase missing |
Warning |
Bypass is missing a phase. |
Check bypass. Contact
Schneider Electric. |
Bypass phase sequence incorrect |
Warning |
The phase rotation on bypass is incorrect. |
Check bypass. Contact
Schneider Electric. |
Bypass voltage out of tolerance |
Warning |
Bypass voltage is out of tolerance and
UPS is prevented from going into requested bypass mode. |
|
Charge power is reduced |
Informational |
The battery charge power has been reduced. |
The input for this functionality was activated,
or the input current has reached the maximum limit. |
Charger shutdown due to high battery temperature |
Warning |
The charger has been shut down due to
a high battery temperature. |
Check the battery temperature. |
Configured UPS power rating exceeds frame power rating |
Critical |
The configured UPS power rating is higher
than the power rating of the frame. |
Contact
Schneider Electric. |
Confirm redundancy lost and/or transfer to forced static bypass |
Warning |
Inverter OFF button has been pushed and
user must confirm that the redundancy will be lost and/or system will
transfer to forced static bypass. |
Confirm or abort using the display. |
Controller box disabled |
Warning |
Controller box has been disabled by user. |
|
Display communication lost - connected |
Warning |
Communication link between display and
system level controller (SLC) is lost. The display is connected. |
Contact
Schneider Electric. |
Display communication lost - disconnected |
Warning |
Communication link between display and
system level controller (SLC) is lost. The display is disconnected. |
Contact
Schneider Electric. |
Display communication not
authenticated |
Warning |
Communication link between display and
system level controller (SLC) is not authenticated. |
Contact
Schneider Electric. |
EPO switch activated |
Critical |
An emergency power off (EPO) switch is
activated. |
Deactivate the emergency power off (EPO)
switch. |
External battery monitoring detected fault |
Warning |
Input contact indicates external battery
monitoring detected fault. |
|
External energy storage monitoring: Major alarm |
Critical |
Input contact indicates that the external
energy storage monitoring has detected a major alarm. |
Contact
Schneider Electric. |
External energy storage monitoring: Minor alarm |
Warning |
Input contact indicates that the external
energy storage monitoring has detected a minor alarm. |
Contact
Schneider Electric. |
External signal turns charger off: Activated |
Warning |
Input contact for charger off is activated. |
Contact
Schneider Electric. |
Firmware versions in parallel UPS units are not identical |
Warning |
The firmware versions in parallel UPS
units are not identical. |
Firmware update all UPS units in the parallel
system to the same version. |
General parallel system event |
Critical |
The parallel system is not configured
correctly or is not working correctly. |
Contact
Schneider Electric. |
Genset is supplying the UPS |
Informational |
Input contact indicates that a genset
is supplying the UPS. |
|
Ground fault detected |
Warning |
Input contact indicates that a ground
wire fault has been detected. |
Contact
Schneider Electric. |
High Battery Temperature Level |
Warning |
The battery temperature is above the
Alarm setting. |
Check the battery temperature. A high temperature
may decrease the battery lifetime. |
High battery temperature shutdown |
Critical |
The energy storage surveillance has detected
a battery temperature above shutdown limit. |
Check the battery temperature. |
High efficiency mode disabled |
Informational |
High efficiency mode is disabled from
an input contact. |
|
High humidity threshold violation at remote sensor |
Warning |
A high humidity threshold violation exists
for integrated environmental monitor sensor. |
Check the
environment. |
High temperature threshold violation at remote sensor |
Warning |
A high temperature threshold violation
exists for integrated environmental monitor sensor. |
Check the
environment. |
IMB closed in parallel system with MBB |
Warning |
Internal maintenance breaker IMB has
been closed in parallel system with maintenance bypass breaker MBB. |
|
IMB redundant monitoring not working correctly |
Warning |
The two redundant AUX switches of the
internal maintenance breaker IMB do not report the same status. |
Check AUX switch wiring of the internal maintenance
breaker IMB. |
Incomplete battery string detected |
Warning |
Incomplete battery string detected. |
Add missing battery module(s). |
Incorrect 3-wire configuration detected |
Critical |
The UPS is not allowed to operate as
a 3-wire system at the configured UPS system voltage. |
Contact
Schneider Electric. |
Incorrect battery monitor controller (BMC) configuration detected |
Warning |
Incorrect battery monitor controller
(BMC) configuration detected. |
Check that the battery monitor controller (BMC)
address IDs have been assigned correctly, and that the configured
number of modular battery cabinets corresponds to what is installed. |
Incorrect system voltage configuration detected |
Critical |
The configured UPS system voltage is
not within the allowed range. |
Contact
Schneider Electric. |
Incorrect UPS base model number detected |
Critical |
The UPS base model number does not match
the installed frame type, power module type, and/or static bypass
switch module (SBS) type. |
Contact
Schneider Electric. |
Incorrect UPS model number detected |
Critical |
The UPS model number does not match the
UPS base model number. |
Contact
Schneider Electric. |
Input frequency out of tolerance |
Warning |
Input frequency is out of tolerance. |
Check input frequency and input frequency setting. |
Input phase missing |
Warning |
Input is missing a phase. |
Check input. Contact
Schneider Electric. |
Input phase sequence incorrect |
Warning |
The phase rotation on input is incorrect. |
Check input. Contact
Schneider Electric. |
Input voltage out of tolerance |
Warning |
Input voltage is out of tolerance. |
|
Internal power module redundancy lost |
Warning |
The configured internal power module
redundancy is lost because there are not enough power modules available. |
Add more power modules. |
Inverter is off due to a request by the user |
Warning |
The inverter is off due to a request
by the user. |
|
Inverter output is not in phase with bypass input |
Warning |
The UPS inverter output is not in phase
with the bypass input. |
|
Load on UPS is above warning level |
Warning |
Load on UPS has exceeded the warning
level. |
Reduce load on system. |
Lost communication to remote sensor |
Critical |
Lost the local network management interface-to-integrated
environmental monitor communication. |
Check the
environment. |
Low Battery Temperature Level |
Warning |
The battery temperature is below the
alarm setting. |
|
Low humidity threshold violation at remote sensor |
Warning |
A low humidity threshold violation exists
for integrated environmental monitor sensor. |
Check the
environment. |
Low temperature threshold violation at remote sensor |
Warning |
A low temperature threshold violation
exists for integrated environmental monitor sensor. |
Check the
environment. |
Maximum humidity threshold violation at remote sensor |
Critical |
A maximum humidity threshold violation
exists for integrated environmental monitor sensor. |
Check the
environment. |
Maximum temperature threshold violation at remote sensor |
Critical |
A maximum temperature threshold violation
exists for integrated environmental monitor sensor. |
Check the
environment. |
MBB redundant monitoring not working correctly |
Warning |
The two redundant AUX switches of the
maintenance bypass breaker MBB do not report the same status. |
Check AUX switch wiring of the maintenance bypass
breaker MBB. |
Minimum humidity threshold violation at remote sensor |
Critical |
A minimum humidity threshold violation
exists for integrated environmental monitor sensor. |
Check the
environment. |
Minimum temperature threshold violation at remote sensor |
Critical |
A minimum temperature threshold violation
exists for integrated environmental monitor sensor. |
Check the
environment. |
Mixed battery brands on string level detected |
Warning |
The battery modules in the string are
not of the same brand. |
Ensure battery modules in a string are of the
same brand. |
Mixed battery module commercial references on system level detected |
Warning |
Mixed battery module commercial references
on system level detected. |
Ensure all battery modules installed have the
same commercial reference. |
Mixed battery solution detected |
Warning |
The UPS is configured for a classic battery
solution but one or more battery modules are detected present. |
Ensure no battery modules are installed. |
Modular battery breaker open |
Warning |
Modular battery breaker is open. |
|
Modular battery cabinet commercial reference unknown |
Warning |
Modular battery cabinet commercial reference
is unknown. |
Contact
Schneider Electric. |
Modular battery cabinet fuse blown |
Warning |
Modular battery cabinet fuse blown. |
Contact
Schneider Electric. |
Modular battery DC relay open |
Warning |
Modular battery DC relay open. |
|
Modular battery string temperature out of tolerance |
Warning |
Modular battery string temperature is
out of tolerance. |
|
Modular battery temperature out of tolerance |
Warning |
Modular battery temperature is out of
tolerance. |
|
Multiple NTP server connections enabled |
Warning |
Multiple NTP server connections are enabled. |
Disable NTP service. |
Neutral displacement detected |
Warning |
Neutral displacement detected. |
|
NMC communication lost - connected |
Warning |
Communication link between network management
card (NMC) and system level controller (SLC) is lost. The network
management card (NMC) is connected. |
Contact
Schneider Electric. |
NMC communication lost - disconnected |
Warning |
Communication link between network management
card (NMC) and system level controller (SLC) is lost. The network
management card (NMC) is disconnected. |
Contact
Schneider Electric. |
NMC communication not authenticated |
Warning |
Communication link between network management
card (NMC) and system level controller (SLC) is not authenticated. |
Contact
Schneider Electric. |
NMC firmware incompatible |
Warning |
Firmware version of the network management
card (NMC) is incompatible. |
Contact
Schneider Electric. |
No power module(s) present |
Warning |
No power module(s) present. |
|
No SBS present |
Warning |
No static bypass switch module (SBS)
present. |
|
Not enough UPS units ready to turn on inverter |
Warning |
One or more parallel UPS units have been
requested to turn on inverter, but not enough UPS units are ready
for system to enter inverter on operation. |
Turn on inverter of more UPS units and/or check
the setting "Minimum number of parallel UPS required to supply load". |
Output frequency out of tolerance |
Warning |
Output frequency is out of tolerance. |
Check output frequency and output frequency setting. |
Output voltage out of tolerance |
Warning |
The output voltage is out of tolerance. |
|
Overload on UPS due to high ambient temperature |
Warning |
The load exceeds the rated UPS capacity
when running in high ambient temperature. |
Reduce load on system or ambient temperature. |
Overload or short circuit on UPS |
Warning |
The load exceeds 100% of rated capacity
or there is a short circuit on the output. |
Reduce load on system or check for output short
circuit. |
Parallel communication lost on PBUS cable 1 |
Warning |
PBUS cable 1 may be damaged. |
Replace PBUS cable 1. |
Parallel communication lost on PBUS cable 2 |
Warning |
PBUS cable 2 may be damaged. |
Replace PBUS cable 2. |
Parallel mixed operation mode |
Warning |
One or more parallel UPS units are operating
in battery operation, while others are operating in normal operation. |
|
Parallel redundancy lost |
Warning |
The configured parallel redundancy is
lost, either because the output load is too high, or because there
are not enough parallel UPS units available. |
Reduce load on system or add more parallel UPS
units. |
Parallel unit not present |
Warning |
UPS is unable to communicate with parallel
UPS %d. The UPS might have been powered down or PBUS cables may be
damaged. |
Contact
Schneider Electric. |
PMC communication lost - connected |
Warning |
Communication link between power module
controller (PMC) and unit controller (UC) is lost. The power module
controller (PMC) is connected. |
Contact
Schneider Electric. |
PMC communication lost - disconnected |
Warning |
Communication link between power module
controller (PMC) and unit controller (UC) is lost. The power module
controller (PMC) is disconnected. |
Contact
Schneider Electric. |
PMC communication not authenticated |
Warning |
Communication link between power module
controller (PMC) and unit controller (UC) is not authenticated. |
Contact
Schneider Electric. |
Power module disabled |
Warning |
The power module has been disabled. |
|
Power module fan inoperable |
Warning |
The power module has one or more inoperable
fans. Fan redundancy is lost. |
Contact
Schneider Electric. |
Power module inlet temperature high |
Warning |
The power module inlet temperature is
high. |
|
Power module inlet temperature out of tolerance |
Warning |
The power module inlet temperature is
out of tolerance. |
|
Power module inoperable |
Warning |
Power module is inoperable. |
Replace power module or contact Schneider Electric. |
Power module overheated |
Critical |
Power module temperature exceeds critical
level. |
|
Power module surveillance detected fault |
Critical |
Power module surveillance detected a
fault. |
Contact
Schneider Electric. |
Power module temperature warning |
Warning |
Power module temperature exceeds warning
level. |
|
Product not registered |
Informational |
Your UPS is not registered. |
Please register your product. |
RIMB redundant monitoring not working correctly |
Warning |
The two redundant AUX switches of the
remote internal maintenance breaker RIMB do not report the same status. |
Check AUX switch wiring of the remote internal
maintenance breaker RIMB. |
SBS module disabled |
Warning |
The static bypass switch module (SBS)
has been disabled by user. |
|
SBS power rating lower than configured UPS power rating |
Warning |
The static bypass switch module (SBS)
power rating is lower than the configured UPS power rating. UPS power
rating has been derated to match static bypass switch module (SBS)
power rating. |
|
SBSC communication lost - connected |
Warning |
Communication link between static bypass
switch module controller (SBSC) and unit controller (UC) is lost.
The static bypass switch module controller (SBSC) is connected. |
Contact
Schneider Electric. |
SBSC communication lost - disconnected |
Warning |
Communication link between static bypass
switch module controller (SBSC) and unit controller (UC) is lost.
The static bypass switch module controller (SBSC) is disconnected. |
Contact
Schneider Electric. |
SBSC communication not authenticated |
Warning |
Communication link between static bypass
switch module controller (SBSC) and unit controller (UC) is not authenticated. |
Contact
Schneider Electric. |
Settings file not accepted |
Warning |
The settings file is not valid or not
intended for this UPS. |
|
SLC in controller box is not working correctly |
Critical |
The system level controller (SLC) in
the controller box is not working correctly. |
Contact
Schneider Electric. |
Static bypass switch fan inoperable |
Warning |
The static bypass switch module (SBS)
has one or more inoperable fans. Fan redundancy is lost. |
Contact
Schneider Electric. |
Static bypass switch inoperable |
Critical |
Static bypass switch is inoperable. UPS
is prevented from going into static bypass operation. |
Contact
Schneider Electric. |
Static bypass switch warning |
Warning |
The static bypass switch needs a technical
check but is still fully operational. |
Contact
Schneider Electric. |
Synchronization unavailable - system is freerunning |
Warning |
The UPS is unable to synchronize to the
bypass input, external source or parallel system. |
|
System locked in bypass operation |
Critical |
The system is locked in bypass operation. |
The system has toggled between inverter operation
and bypass operation more than 10 times within 75 seconds. Please
press inverter ON button to transfer back to normal operation. |
System operation mode - Forced static bypass |
Critical |
The system is in bypass in response to
a critical event or an inverter off request. |
|
System operation mode - Maintenance bypass |
Warning |
The system load is supplied through the
maintenance bypass breaker (MBB). |
|
System operation mode - Off |
Critical |
The system output power is turned off. |
|
System operation mode - Requested static bypass |
Warning |
The system is in bypass in response to
the UPS front-panel or a user-initiated software command, typically
for maintenance. |
|
System operation mode - Static bypass standby |
Critical |
The system is in static bypass standby
operation in response to a critical event or an inverter off request. |
|
Technical check recommended |
Informational |
The product and its batteries need to
be checked as preventive maintenance is recommended. |
Contact
Schneider Electric. |
Temperature of input and/or output transformer is too high |
Warning |
Temperature of input and/or output transformer
is too high. |
Check temperature of the input and/or output transformer. |
UC communication lost - connected |
Warning |
Communication link between unit controller
(UC) and system level controller (SLC) is lost. The unit controller
(UC) is connected. |
Contact
Schneider Electric. |
UC communication lost - disconnected |
Warning |
Communication link between unit controller
(UC) and system level controller (SLC) is lost. The unit controller
(UC) is disconnected. |
Contact
Schneider Electric. |
UC communication not authenticated |
Warning |
Communication link between unit controller
(UC) and system level controller (SLC) is not authenticated. |
Contact
Schneider Electric. |
UC in controller box is not working correctly |
Critical |
The unit controller (UC) in the controller
box is not working correctly. |
Contact
Schneider Electric. |
Unsupported power frame type detected |
Critical |
The detected UPS power frame type is
not supported by the current UPS power configuration. |
Contact
Schneider Electric. |
Unsupported power module type detected |
Critical |
The detected power module type is not
supported by the current UPS power configuration. |
Contact
Schneider Electric. |
Unsupported SBS module type detected |
Critical |
The detected static bypass switch module
(SBS) type is not supported by the current UPS power configuration. |
Contact
Schneider Electric. |
UOB redundant monitoring not working correctly |
Warning |
The two redundant AUX switches of the
unit output breaker UOB do not report the same status. |
Check AUX switch wiring of the unit output breaker
UOB . |
UPS locked in static bypass mode: Activated |
Warning |
Input contact for UPS locked in static
bypass mode is activated. |
|
UPS operation mode - Battery |
Warning |
On battery power in response to an input
power problem or due to a transfer out of eConversion. |
|
UPS operation mode - Battery test |
Informational |
On battery power in response to a test
of the performance of the batteries. |
|
UPS operation mode - Forced static bypass |
Critical |
The UPS is in forced static bypass. |
Check active alarms and event log to get details
about why UPS is in forced static bypass. |
UPS operation mode - Inverter standby |
Informational |
The UPS is ready to enter battery operation
but awaits permission from the system. UPS output is off. |
|
UPS operation mode - Maintenance bypass |
Warning |
The UPS load is supplied through maintenance
bypass breaker (MBB). |
|
UPS operation mode - Off |
Critical |
The output power is turned off. |
|
UPS operation mode - Requested static bypass |
Warning |
The UPS is in bypass in response to the
UPS front-panel or a user-initiated software command, typically for
maintenance. |
|
UPS operation mode - Static bypass standby |
Warning |
The UPS is ready to enter static bypass
but awaits permission from the system. UPS output is off. |
|
UPS output load is too low to allow eConversion |
Informational |
UPS output load is too low to allow eConversion. |
Increase UPS output load or disable eConversion. |
UPS surveillance detected fault |
Critical |
UPS surveillance detected a fault. |
Contact
Schneider Electric. |
User-defined input 1 activated |
Informational |
User-defined input contact 1 is activated. |
|
User-defined input 2 activated |
Informational |
User-defined input contact 2 is activated. |
|
Warranty expiring soon |
Informational |
The product is reaching the end of warranty. |
Contact
Schneider Electric. |