990-91140G-001

UL 924 and CSA 22.2 NO. 141-15 Solutions

NOTE: In solutions with two classic battery cabinets of the type GVSCBT1ST, GVSCBT2ST, GVSCBT3ST, GVSCBT4ST, or GVSCBT5ST, the GVSOPT011 cable kit is needed for the second battery cabinet.
NOTE: In solutions with two or more classic battery cabinets of the type GVSCBT6ST, one GVSOPT028 cable kit is needed.

UL 924 Solutions (90 Minutes Runtime)

NOTE: The Lithium-ion battery cabinet LIBSESMG13UL requires a minimum charge time of 24 hours to reach full battery capacity. The Lithium-ion battery cabinet LIBSESMG16UL requires a minimum charge time of 36 hours to reach full battery capacity. The minimum charge time to reach full battery capacity is based on the UPS operating with 100% load and at 85% undervoltage.
UPS Classic battery cabinet Lithium-ion battery cabinet
Voltage (V) UPS rating Commercial reference Commercial reference Commercial reference
480 V 20 kW GVSUPS20KGS or GVSUPS20KRGS 2 x GVSCBT3ST or 1 x GVSCBT6ST   2 x LIBSESMG13UL or 1 x LIBSESMG16UL
30 kW GVSUPS30KGS or GVSUPS30KRGS 2 x GVSCBT4ST or 2 x GVSCBT5ST 2 x LIBSESMG13UL or 2 x LIBSESMG16UL
40 kW GVSUPS40KGS or GVSUPS40KRGS 2 x GVSCBT6ST   3 x LIBSESMG13UL or 2 x LIBSESMG16UL
50 kW GVSUPS50KGS or GVSUPS50KRGS 3 x GVSCBT6ST   3 x LIBSESMG16UL
60 kW GVSUPS60KGS or GVSUPS60KRGS 3 x GVSCBT6ST   3 x LIBSESMG16UL
80 kW GVSUPS80KGS or GVSUPS80KRGS 4 x GVSCBT6ST   4 x LIBSESMG16UL
100 kW GVSUPS100KGS or GVSUPS100KRGS 5 x GVSCBT6ST   5 x LIBSESMG16UL
208 V 10 kW GVSUPS10KFS or GVSUPS10KRFS 1 x GVSCBT3ST or 1 x GVSCBT4ST 1 x LIBSESMG13UL or 1 x LIBSESMG16UL
15 kW GVSUPS15KFS or GVSUPS15KRFS 1 x GVSCBT4ST or 1 x GVSCBT5ST 1 x LIBSESMG13UL or 1 x LIBSESMG16UL
20 kW GVSUPS20KFS or GVSUPS20KRFS 2 x GVSCBT3ST or 1 x GVSCBT6ST   2 x LIBSESMG13UL or 1 x LIBSESMG16UL
25 kW GVSUPS25KFS or GVSUPS25KRFS 2 x GVSCBT4ST or 2 x GVSCBT5ST 2 x LIBSESMG16UL
30 kW GVSUPS30KFS or GVSUPS30KRFS 2 x GVSCBT4ST or 2 x GVSCBT5ST 2 x LIBSESMG13UL or 2 x LIBSESMG16UL
40 kW GVSUPS40KFS or GVSUPS40KRFS 2 x GVSCBT6ST   3 x LIBSESMG13UL or 2 x LIBSESMG16UL
50 kW GVSUPS50KFS or GVSUPS50KRFS 3 x GVSCBT6ST   3 x LIBSESMG16UL

CSA 22.2 NO. 141-15 Solutions (30 Minutes Runtime)

UPS Classic battery cabinet
Voltage (V) UPS rating Commercial reference Commercial reference
480 V 20 kW GVSUPS20KGS or GVSUPS20KRGS

1 x GVSCBT3ST or 1 x GVSCBT4ST

30 kW GVSUPS30KGS or GVSUPS30KRGS

1 x GVSCBT4ST or 1 x GVSCBT5ST

40 kW GVSUPS40KGS or GVSUPS40KRGS

1 x GVSCBT5ST or 1 x GVSCBT6ST

50 kW GVSUPS50KGS or GVSUPS50KRGS

2 x GVSCBT4ST or 1 x GVSCBT6ST

60 kW GVSUPS60KGS or GVSUPS60KRGS

2 x GVSCBT4ST or 2 x GVSCBT5ST

80 kW GVSUPS80KGS or GVSUPS80KRGS

2 x GVSCBT5ST or 2 x GVSCBT6ST

100 kW GVSUPS100KGS or GVSUPS100KRGS

2 x GVSCBT6ST

208 V 10 kW GVSUPS10KFS or GVSUPS10KRFS

1 x GVSCBT1ST or 1 x GVSCBT2ST

15 kW GVSUPS15KFS or GVSUPS15KRFS

1 x GVSCBT2ST or 1 x GVSCBT3ST

20 kW GVSUPS20KFS or GVSUPS20KRFS

1 x GVSCBT3ST or 1 x  GVSCBT4ST

25 kW GVSUPS25KFS or GVSUPS25KRFS

1 x GVSCBT4ST or 1 x GVSCBT5ST

30 kW GVSUPS30KFS or GVSUPS30KRFS

1 x GVSCBT4ST or 1 x GVSCBT5ST

40 kW GVSUPS40KFS or GVSUPS40KRFS

1 x GVSCBT5ST or 1 x GVSCBT6ST

50 kW GVSUPS50KFS or GVSUPS50KRFS

2 x GVSCBT4ST or 1 x GVSCBT6ST

CSA 22.2 NO. 141-15 Solutions (60 Minutes Runtime)

UPS Classic battery cabinet
Voltage (V) UPS rating Commercial reference Commercial reference
480 V 20 kW GVSUPS20KGS or GVSUPS20KRGS

1 x GVSCBT4ST or 1 x GVSCBT5ST

30 kW GVSUPS30KGS or GVSUPS30KRGS

2 x GVSCBT4ST

40 kW GVSUPS40KGS or GVSUPS40KRGS

2 x GVSCBT4ST or 2 x GVSCBT5ST

50 kW GVSUPS50KGS or GVSUPS50KRGS

2 x GVSCBT5ST or 2 x GVSCBT6ST

60 kW GVSUPS60KGS or GVSUPS60KRGS

2 x GVSCBT6ST

80 kW GVSUPS80KGS or GVSUPS80KRGS

3 x GVSCBT6ST

100 kW GVSUPS100KGS or GVSUPS100KRGS

4 x GVSCBT6ST

208 V 10 kW GVSUPS10KFS or GVSUPS10KRFS

1 x GVSCBT2ST or 1 x GVSCBT3ST

15 kW GVSUPS15KFS or GVSUPS15KRFS

1 x GVSCBT4ST or 1 x GVSCBT5ST

20 kW GVSUPS20KFS or GVSUPS20KRFS

1 x GVSCBT4ST or 1 x GVSCBT5ST

25 kW GVSUPS25KFS or GVSUPS25KRFS

1 x GVSCBT5ST or 1 x GVSCBT6ST

30 kW GVSUPS30KFS or GVSUPS30KRFS

2 x GVSCBT4ST

40 kW GVSUPS40KFS or GVSUPS40KRFS

2 x GVSCBT4ST or 2 x GVSCBT5ST

50 kW GVSUPS50KFS or GVSUPS50KRFS

2 x GVSCBT5ST or 2 x GVSCBT6ST

CSA 22.2 NO. 141-15 Solutions (120 Minutes Runtime)

UPS Classic battery cabinet
Voltage (V) UPS rating Commercial reference Commercial reference
480 V 20 kW GVSUPS20KGS or GVSUPS20KRGS

2 x GVSCBT4ST or 2 x GVSCBT5ST

30 kW GVSUPS30KGS or GVSUPS30KRGS

2 x GVSCBT5ST or 2 x GVSCBT6ST

40 kW GVSUPS40KGS or GVSUPS40KRGS

3 x GVSCBT6ST

50 kW GVSUPS50KGS or GVSUPS50KRGS

3 x GVSCBT6ST

60 kW GVSUPS60KGS or GVSUPS60KRGS

4 x GVSCBT6ST

80 kW GVSUPS80KGS or GVSUPS80KRGS

5 x GVSCBT6ST

100 kW GVSUPS100KGS or GVSUPS100KRGS

NA

208 V 10 kW GVSUPS10KFS or GVSUPS10KRFS

1 x GVSCBT4ST or 1 x GVSCBT5ST

15 kW GVSUPS15KFS or GVSUPS15KRFS

1 x GVSCBT6ST

20 kW GVSUPS20KFS or GVSUPS20KRFS

2 x GVSCBT4ST or 2 x GVSCBT5ST

25 kW GVSUPS25KFS or GVSUPS25KRFS

2 x GVSCBT4ST or 2 x GVSCBT5ST

30 kW GVSUPS30KFS or GVSUPS30KRFS

2 x GVSCBT5ST or 2 x GVSCBT6ST

40 kW GVSUPS40KFS or GVSUPS40KRFS

3 x GVSCBT6ST

50 kW GVSUPS50KFS or GVSUPS50KRFS

3 x GVSCBT6ST

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?