7EN52–0378–01

Configuring the cell modem using the display

Use the display to navigate to the setup menus to perform cell modem setup on your meter.
NOTE: The following configuration steps must be completed for the cell modem to function properly.
  1. Press and hold the ALT/ENTER button to access the meter’s setup screens.
  2. Use the up or down arrow buttons to select CELL SETUP and press ALT/ENTER.
  3. Configure the settings (Protocol and Port Number) for each connection.
    NOTE: To disable the connection to a port, set the Protocol to None. This allows you to restrict the number of simultaneous connections to the meter through the cell modem.
    Setting Description Range (values) Default
    IP Address Displays the IP address assigned to the cell modem by the network xxx.xxx.xxx.xxx Not configurable
    MEID/CCID Displays Mobile Equipment Identifier Not configurable Not configurable
    Protocol 1–6 Specifies the protocol used for connection 1–6 None, ION, Modbus TCP, DNP 3.0 None
    Port Number 1–6 Specifies the port number to establish connection 1–6 1 - 65535 0
QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.