7EN02–0305–02

Digital outputs

Type

4 Form C solid state outputs (I/O option B & C)

1 Form A solid state output (I/O option C only)

Wire

1.3 to 0.13 mm2 (16 to 26 AWG)

Max load voltage

130 V AC / 200 V DC

Max load current

100 mA

ON Resistance

30 ohms typical, 50 ohms maximum

OFF Resistance

400 Mohms minimum

Isolation

2000 V rms, 60 Hz for 1 minute (to ground).

1000 V rms, 60 Hz for 1 minute (between outputs)

Rated impulse voltage

2500 V peak (to ground)

1500 V peak (between inputs or outputs)

(CAT II)

Update Rate

20 ms (accuracy = +/- 7 ms), not including communication lag time. State changes occur within 20 ms. 1/2 cycle for internal I/O

Signal Type

Continuous or pulse

Fusing

Protect with 100 mA slow-blow fuse (such as Littlefuse 201 Series 100 mA fuse)

Max output transition

50 per second

Min Pulse Width

1 ms

Timing resolution

1/2 cycle or 1 s

Transient suppression device for digital outputs

Install according to diagrams in the section, “Digital outputs”. The customer-supplied transient suppression device must meet these specifications: 

Polarization = Bidirectional. Breakdown voltage = 300 V maximum. Peak power dissipation = 10 kw for 10 microseconds (minimum), and 1.5 kW for 1 millisecond (minimum). 

State change latency

20 ms (Digital output)

40 ms (Digital input modules)

Control schemes

Use intermediate mechanisms so relay control can be disabled for servicing.

Feedback