Wiring diagrams
After completing all electrical wiring, mounting and installation steps, refer to “Step 10: Use phasor diagrams to verify wiring” for details on meter operation for different systems and volts modes, as well as verification of correct phase wiring.
Form 9 (3-element)
Set the meter’s Volts Mode to 9S - 4 Wire Wye/Delta. Voltage measurement limit is 57 to 277 VLN.
Form 29 (2.5-element)
Set the meter’s Volts Mode to 29S - 4 Wire Wye. Voltage measurement limit is 57 to 277 VLN.
Form 36 (2.5-element)
Set the meter’s Volts Mode to 36S - 4 Wire Wye. Voltage measurement limit is 57 to 277 VLN.
Form 35 (2-element)
Set the meter’s Volts Mode to 35S - 3 Wire. Voltage measurement limit is 120 to 480 VLN.
| Form 35, 3-Wire Delta, 2 PTs, 2 CTs | Form
                              35, 4-Wire Wye, 2 PTs, 3 CTs1 | 
| 1 This configuration can affect some of the meter’s parameter calculations. Contact Technical Support for more details. | |
|  DANGER | 
|---|
| HAZARD OF ELECTRIC SHOCK, EXPLOSION,
                           OR ARC FLASH Do not connect Vref to ground when using the Form 35,
                        3-Wire Delta, No PTs, 2 CTs wiring diagram. Failure to follow these instructions will result in death or serious injury. |