Voltage measurement inputs
Inputs |
Form 9: Va, Vb, Vc, Vref Form 29 & 36: Va, Vc, Vref Form 35: Vab, Vcb, Vref |
Recommended wire gauge |
5.26 mm2 (10 AWG) |
Nominal voltage |
Form 9, 29 & 36: 57 to 277 V L-N rms (-20%,+25%) Form 35: 100 to 480 V L-L rms (-20%,+25%) |
Maximum voltage, auxiliary powered meters |
Form 9, 29 & 36: 347 V L-N rms, 600 V L-L rms 35: 600 V L-L rms |
Dielectric withstand |
2500 V rms, 60 Hz for 1 minute |
Rated impulse voltage |
6 kV |
Measurement / installation category |
CAT III |
Operating fundamental frequency range |
42-69 Hz |
Input impedance |
5 MW per phase (phase to Vref) |
Fuse (customer supplied) |
2 A slow-blow (see wiring diagrams) |