3 Phase Main Devices (Busway Center Tap)

Class 4162 / Refer to Catalog 4100CT0701

EZM Busway Center Tap Mains

The EZM Busway Center Tap mains offer provides a convenient space saving method for connecting EZM Branch Meter sections to I-Line II Busway in vertical riser applications. The mains are connected "inline" with the Busway column conserving precious electrical room space.

  1. The Part Number Coding Table is to be used for interpreting existing part numbers only. All possible combinations are not available. Please contact product support for additional references needed.

  2. Outgoing Feeder Bus Joint-Pak is included with each EZM CTM Section.

  3. EZM Horizontal Cross Bus is 1200 A Copper Only

  4. Busway Center Tap Mains are fully NEMA 3R Rated.

  5. Mains Devices are fully sealable by utility.

  6. EZM Branch units are installed using the mounting kit - EZMCTMKIT.

  7. Short circuit current rating = 150,000 symmetrical amps.

  8. EZM CTM is configured for neutral front only (G-> N-> C-> B->A-> G) as viewed front to rear.

  9. Compatible with I-LINE II Busway rated 2000–5000 A.

  10. Includes factory installed PowerPact M- and P-frame Circuit Breakers and Switches (Rated 600–1200 A.)

  11. Fully compatible with all standard EZ Meter-Pak Branch Devices and Extenders.

Part Number Coding

Number Segment

Character

Description

EZM

3

1000

JCB

C

20

Device Name

EZM

EZM Busway Center Tap Main

     

System Connection (Phase Order: Front to Back)

3

3 Phase (N, C, B, A)

   

Maximum Current of Main Service Disconnect

600

600 A

       

800

800 A

       

1000

1000 A

       

1200

1200 A

       

Type of Main Service Disconnect (with AIC Rating)

GCB

65 kAIC Circuit Breaker

 

JCB

100 kAIC Circuit Breaker

 

FS

100 kAIC Fused Switch

 

Material of I-Line II Busway

C

Copper

         

A

Aluminum

         

Amperage of I-Line II Busway

20

2000 A

25

2500 A

30

3000 A

32

3200 A

40

4000 A

50

5000 A

This table is for interpreting existing part numbers only. All possible combinations are not available.

EZM Busway Center Tap Mains

 

Main CB Ampere Rating (A)

I-Line II Busway Rating, Material

Cat. No.

Height
(in.)

Width
(in.)

Depth
(in.)

MC [1]Height
(in.)

Main Circuit Breakers (3Ø Incoming and 3Ø Outgoing)

SCCR

65 kA

100 kA

       

600

2000A, Al

EZM3600JCBA20

43.08

22.70

14.78

56.11

3000A, Al

EZM3600JCBA30

43.08

22.70

14.78

56.11

4000A, Al

EZM3600GCBA40

EZM3600JCBA40

43.08

27.96

14.78

56.11

800

2000A, Al

EZM3800GCBA20

43.08

22.70

14.78

56.11

2500A, Al

EZM3800GCBA25

43.08

22.70

14.78

56.11

3000A, Al

EZM3800GCBA30

EZM3800JCBA30

43.08

22.70

14.78

56.11

4000A, Al

EZM3800GCBA40

EZM3800JCBA40

43.08

27.96

14.78

56.11

1000

4000A, Al

EZM31000JCBA40

43.08

27.96

14.78

56.11

1200

3000A, Al

EZM31200GCBA30

43.08

22.70

14.78

56.11

4000A, Al

EZM31200GCBA40

EZM31200JCBA40

43.08

27.96

14.78

56.11