3 Phase Main Devices
Class 4162 / Refer to Catalog 4100CT0701
3Ø4W 208Y/120 Vac or 240/120 Vac Delta EZ Meter-Pak™ Meter Centers—3Ø Indoor/Rainproof, UL Listed
1200 A Main CB/Fusible Switch Devices come Standard with 2-STEP Removable Service Entrance Endwalls
Select EZM meter center short circuit current rating from UL Listed Meter Center (SCCR). Using this table as a reference, make the following selections:
-
Select 3Ø EZM main device below with an equal or higher short circuit rating than the application from Overhead/Underground Feed and Main Devices, Overhead/Underground Feed.
-
Select EZM 3Ø branch units from 3Ø Incoming and 1Ø Outgoing, 225 A Maximum Commercial, and 400 A Maximum Commercial .
-
Select proper 2P type QO, QO-VH, QOH, QBP-TM, QDP-TM, QGP-TM or QJP-TM or 3P QBP-TM, QDP-TM, QGP-TM or QJP-TM branch circuit breakers for use as tenant mains in branch unit; from 125 A Max. EZM Branch Unit Tenant Circuit Breakers and 225 A Max. EZM Branch Unit Tenant Circuit Breakers.
-
Select accessories as required, from Tenant Circuit Breakers and EZM Accessories.
-
Dimensions see Main Devices Dimensions (in.).
3 Phase Main Devices—NEMA 3R Construction
3Ø Main Devices
|
Ampere Rating |
Service |
Horizontal Cross Bus Rating |
Cat. No.[1] |
Width |
Factory-Installed Line Side Lug (Conductors per Phase and Neutral) Wire Size (AWG–kcmil) |
||
|---|---|---|---|---|---|---|---|
EZM31200FST |
Main Circuit Breakers (3Ø Incoming and 3Ø Outgoing) 65 kA Short Circuit Current Rating (400–1600 A Max.), 100 kA Short Circuit Current Rating (2000 A Max.) |
||||||
|
Short Circuit Rating |
65 kA |
100 kA |
|||||
|
400 |
OH/UG |
400 A |
— |
18.66 |
(1) 1–600 or (2) 1–250 |
||
|
600 |
OH/UG |
600 A |
— |
18.66 |
(3) 3/0–500 |
||
|
800 |
OH/UG |
800 A |
— |
18.66 |
(3) 3/0–500 |
||
|
1000 |
OH/UG |
1200 A |
— |
18.66 |
(3) 3/0–500 |
||
|
1200 |
OH |
1200 A |
— |
23.69 |
(4) 3/0-500 |
||
|
1200 |
UG |
1200 A |
23.69 |
(4) 3/0-500 |
|||
|
1600 |
OH/UG |
1200 A |
30.19 |
(6) 1/0–750 or (12) 1/0–250 |
|||
|
1600 |
UG |
1200 A |
30.19 |
6 (Order Lugs Separately) |
|||
|
2000 |
OH/UG |
1200 A |
— |
30.19 |
(6) 1/0–750 or (12) 1/0–250 |
||
|
2000 |
UG |
1200 A |
— |
30.19 |
6 (Order Lugs Separately) |
||
|
Main Fusible Switches (3Ø Incoming and 3Ø Outgoing) Requires 300 Vac Class T Fuses (Order Separately) |
|||||||
|
400 |
OH/UG |
400 A |
— |
18.66 |
(1) 1–600 or (2 )1–250 |
||
|
600 |
OH/UG |
600 A |
— |
18.66 |
(3) 3/0–500 |
||
|
800 |
OH/UG |
800 A |
— |
18.66 |
(3) 3/0–500 |
||
|
1200 |
OH |
1200 A |
— |
23.69 |
(4) 3/0–500 |
||
|
1200 |
UG |
1200 A |
— |
23.69 |
(4) 3/0-500 |
||
|
Main Lug Terminal Boxes (3Ø Incoming and 3Ø Outgoing) |
|||||||
|
225 |
OH/UG |
800 A |
— |
11.66 |
(1) 4–300 |
||
|
400 |
OH/UG |
800 A |
— |
17.15 |
(2) 3/0–500 |
||
|
600 |
OH/UG |
800 A |
— |
17.15 |
(2) 1/0–750 or (4) 1/0–300 |
||
|
800 |
OH/UG |
800 A |
— |
18.66 |
(4) 3/0–500 |
||
|
800 |
OH/UG |
800 A |
— |
24.08 |
(4) 3/0–500 |
||
|
1600 |
OH/UG |
1200 A |
— |
22.48 |
(6) 1/0-600 or (12) 1/0-300 |
||
|
2000 |
OH/UG |
1200 A |
— |
30.19 |
6 (Order Lugs Separately) |
||
|
Main Circuit Breakers (3Ø Incoming and 3Ø Outgoing) with Energy Reduction Maintenance Switch (ERMS) |
|||||||
|
1200 |
OH |
1200 A |
23.69 |
(4) 3/0–500 |
|||
|
1200 |
UG |
1200 A |
23.69 |
(4) 3/0–500 |
|||
|
1600 |
OH/UG |
1200 A |
30.19 |
(6) 1/0–750 or (12) 1/0–250 |
|||
|
1600 |
UG |
1200 A |
30.19 |
6 (Order Lugs Separately) |
|||
|
2000 |
OH/UG |
1200 A |
— |
30.19 |
(6) 1/0–750 or (12) 1/0–250 |
||
|
2000 |
UG |
1200 A |
— |
30.19 |
6 (Order Lugs Separately) |
||
3Ø Main Devices, EUSERC
|
Ampere Rating |
Horizontal Cross Bus Rating |
Cat. No. |
Width |
Factory-Installed Lug Landings For use with Crimp-Type Lugs (2-Hole Mounting) Qty. per Phase and Neutral, except non-EUSERC device.[8] |
||
|---|---|---|---|---|---|---|
EZM31200GCBEMS |
Main Circuit Breakers (3Ø Incoming and 3Ø Outgoing) |
|||||
|
Short Circuit Rating |
65 kA |
100 kA |
||||
|
400 |
400 A |
— |
20.46 |
1 (Order Lugs Separately) |
||
|
600 |
600 A |
— |
26.19 |
2 (Order Lugs Separately) |
||
|
800 |
800 A |
— |
26.19 |
2 (Order Lugs Separately) |
||
|
1000 |
1200 A |
— |
34.19 |
3 (Order Lugs Separately) |
||
|
1200 |
1200 A |
— |
32.39 |
3 (Order Lugs Separately) |
||
|
Main Fusible Switches (3Ø Incoming and 3Ø Outgoing) Requires 300 Vac Class T Fuses (Order Separately) |
||||||
|
400 |
400 A |
— |
20.46 |
1 (Order Lugs Separately) |
||
|
600 |
600 A |
— |
26.19 |
2 (Order Lugs Separately) |
||
|
800 |
800 A |
— |
26.19 |
2 (Order Lugs Separately) |
||
|
1200 |
1200 A |
— |
32.39 |
3 (Order Lugs Separately) |
||
|
Main Lugs Terminal Boxes (3Ø Incoming and 3Ø Outgoing) |
||||||
|
400 |
400 A |
— |
17.16 |
1 (Order Lugs Separately) |
||
|
800 |
800 A |
— |
25.16 |
2 (Order Lugs Separately) |
||
|
1200 |
1200 A |
— |
33.16 |
3 (Order Lugs Separately) |
||
|
Main Circuit Breaker (3Ø Incoming and 3Ø Outgoing) with Energy reduction Maintenance Switch (ERMS) |
||||||
|
1200 |
1200 A |
32.39 |
3 (Order Lugs Separately) |
|||