I-Line Electrical Data
Electrical Data
-
Standards: UL857 (File Number E22182); CSA C22.2 No. 27-1973 (File Number LL-61778)
-
Systems: AC–3Ø3W, 3Ø4W, 1Ø2W, 1Ø3W, DC-2 Pole. All neutrals are 100% capacity.
-
Voltage: 600 Volts AC/DC, 50 Hz and 60 Hz
-
Ground: 50% capacity as standard for 800–5000 A, as an option on
225–600 A -
Enclosure: Indoor and outdoor (800–5000 A only)
Short Circuit Ratings
Short Circuit Ratings: UL 3-Cycle Test (kA, RMS Symmetrical)
Ampere Rating | Aluminum | Copper | ||||||
---|---|---|---|---|---|---|---|---|
AOF2 / AF2 | AOFH2 / AFH2 | AP / AP2 | APH / APH2 | COF2 / CF2 | COFH2 / CFH2 | CP / CP2 | CPH / CPH2 | |
225 | — | — | 22 | — | — | — | 22 | — |
400 | — | — | 22 | 42 | — | — | 22 | 42 |
600 | — | — | 22 | 42 | — | — | 22 | 42 |
800 | 50 | 85 | 50 | 75 | 50 | 85 | 50 | 75 |
1000 | 50 | 100 | 50 | 100 | 50 | 85 | 50 | 75 |
1200 | 50 | 100 | 50 | 100 | 50 | 100 | 50 | 100 |
1350 | 50 | 100 | 50 | 100 | 50 | 100 | 50 | 100 |
1600 | 50 | 100 | 50 | 100 | 50 | 100 | 50 | 100 |
2000 | 100 | 150 | 125 | 150 | 50 | 100 | 65 | 100 |
2500 | 100 | 150 | 125 | 150 | 100 | 150 | 125 | 150 |
3000 | 100 | 150 | 125 | 150 | 100 | 150 | 125 | 150 |
3200 | — | — | — | — | 100 | 150 | 125 | — |
4000 | 150 | 200* | 200 | — | 150 | 200* | 200 | — |
5000 | — | — | — | — | 150 | 200* | 200 |
Short Circuit Ratings: 6-Cycle and 30-Cycle Tests (kA, RMS Symmetrical)
Ampere Rating | Aluminum | Copper | ||||||
---|---|---|---|---|---|---|---|---|
AF2, AOF2, AP2 | AFH2, AOFH2, APH2 | CF2, COF2, CP2 | CFH2, COFH2, CPH2 | |||||
6-Cycle | 30-Cycle | 6-Cycle | 30-Cycle | 6-Cycle | 30-Cycle | 6-Cycle | 30-Cycle | |
800 | 42 | 35 | 75 | 52 | 42 | 35 | 65 | 45 |
1000 | 50 | 35 | 100 | 70 | 50 | 35 | 75 | 52 |
1200 | 50 | 35 | 100 | 70 | 50 | 35 | 100 | 70 |
1350 | 50 | 35 | 100 | 70 | 50 | 35 | 100 | 70 |
1600 | 50 | 35 | 100 | 70 | 50 | 35 | 100 | 70 |
2000 | 100 | 70 | 150 | 105 | 50 | 35 | 100 | 70 |
2500 | 100 | 70 | 150 | 105 | 100 | 70 | 150 | 105 |
3000 | 100 | 70 | 150 | 105 | 100 | 70 | 150 | 105 |
3200 | — | — | — | — | 100 | 70 | 150 | 105 |
4000 | 150 | 105 | 200* | 140* | 150 | 105 | 200* | 1401* |
5000 | — | — | — | — | 150 | 105 | 200* | 14* |
Short Circuit Ratings: KA, RMS Symmetrical (Series Connected with a Fuse)
Ampere Rating | Aluminum | Copper | ||||||
---|---|---|---|---|---|---|---|---|
AF2 | AFH2 | AP / AP2 | APH / APH2 | CF2 | CFH2 | CP / CP2 | CPH / CPH2 | |
225 | — | — | 200 | — | — | — | 200 | — |
400 | — | — | 100 | 200 | — | — | 100 | 200 |
600 | — | — | 50 | 200 | — | — | 50 | 200 |
800 | 100 | 200 | 200 | 200 | 100 | 200 | 200 | 200 |
1000 | 100* | 200* | 100* | 200* | 100* | 200* | 200* | 200* |
1200 | 100 | 200 | 100 | 200 | 100 | 200 | 100 | 200 |
1350 | 100* | 200* | 100* | 200* | 100* | 200* | 100* | 200* |
1600 | 100 | 200 | 100 | 200 | 100 | 200 | 100 | 200 |
2000 | — | 200 | 200 | 200 | — | 200 | 100 | 200 |
2500 | — | — | 200 | 200 | — | 200 | 200 | 200 |
3000 | — | — | 200 | 200 | — | — | 200 | 200 |
3200 | — | — | — | — | — | — | 200 | 200 |
4000 | 200 | — | — | — | 200 | — | — | — |
5000 | — | — | — | — | 200 | — | — | — |
Aluminum I-Line Short Circuit Ratings: KA, RMS Symmetrical (Series Connected with a Breaker)
Ampere Rating* | ANSI Circuit Breaker | Aluminum | |||||||
---|---|---|---|---|---|---|---|---|---|
AF2 | AFH2 | AP2 | APH2 | ||||||
480 V Max. | 600 V Max. | 480 V Max. | 600 V Max. | 480 V Max. | 600 V Max. | 480 V Max. | 600 V Max. | ||
800 | — | — | — | — | — | — | — | — | — |
1000 | NW16L1 | — | — | 200 | 130 | — | — | 200 | 130 |
1200 | — | — | 200 | 130 | — | — | 200 | 130 | |
1350 | — | — | 200 | 130 | — | — | 200 | 130 | |
1600 | — | — | 200 | 130 | — | — | 200 | 130 | |
2000 | NW20L1 | — | — | 200 | 130 | — | — | 200 | 130 |
2500 | — | — | — | — | — | — | — | — | — |
3000 | — | — | — | — | — | — | — | — | — |
4000 | — | — | — | — | — | — | — | — | — |
5000 | — | — | — | — | — | — | — | — | — |
Copper I-Line Short Circuit Ratings: KA, RMS Symmetrical (Series Connected with a Breaker)
Ampere Rating* | ANSI Circuit Breaker | Copper | |||||||
---|---|---|---|---|---|---|---|---|---|
CF2 | CFH2 | CP2 | CPH2 | ||||||
480 V Max. | 600 V Max. | 480 V Max. | 600 V Max. | 480 V Max. | 600 V Max. | 480 V Max. | 600 V Max. | ||
800 | — | — | — | — | — | — | — | — | — |
1000 | NW16L1 | — | — | — | — | — | — | — | — |
1200 | — | — | 200 | 130 | — | — | 200 | 130 | |
1350 | — | — | 200 | 130 | — | — | 200 | 130 | |
1600 | — | — | 200 | 130 | — | — | 200 | 130 | |
2000 | NW20L1 | — | — | 200 | 130 | — | — | 200 | 130 |
2500 | — | — | — | — | — | — | — | — | — |
3000 | — | — | — | — | — | — | — | — | — |
4000 | — | — | — | — | — | — | — | — | — |
5000 | — | — | — | — | — | — | — | — | — |
Impedance Values
Line-to-Neutral (Milliohms Per 100 Feet)
Ampere Rating | Aluminum Busway | Copper Busway | ||||
---|---|---|---|---|---|---|
R | X60 Hz | X50 Hz | R | X60 Hz | X50 Hz | |
225 | 7.3 | 3.42 | 2.85 | 4.06 | 3.75 | 3.12 |
400 | 3.71 | 2.6 | 2.17 | 2.13 | 2.3 | 1.92 |
600 | 2.04 | 1.59 | 1.32 | 2.13 | 2.3 | 1.92 |
800 | 2.67 | 0.91 | 0.76 | 1.86 | 1.1 | 0.92 |
1000 | 2.15 | 0.74 | 0.62 | 1.92 | 1.07 | 0.89 |
1200 | 1.62 | 0.6 | 0.5 | 1.52 | 0.92 | 0.76 |
1350 | 1.36 | 0.53 | 0.44 | 1.17 | 0.75 | 0.62 |
1600 | 1.2 | 0.5 | 0.42 | 1.04 | 0.69 | 0.58 |
2000 | 0.99 | 0.41 | 0.34 | 0.84 | 0.54 | 0.44 |
2500 | 0.85 | 0.35 | 0.29 | 0.6 | 0.42 | 0.35 |
3000 | 0.61 | 0.26 | 0.22 | 0.53 | 0.37 | 0.31 |
3200 | — | — | — | 0.48 | 0.32 | 0.27 |
4000 | 0.44 | 0.15 | 0.13 | 0.39 | 0.23 | 0.19 |
5000 | — | — | — | 0.28 | 0.19 | 0.15 |
-
For optimized values on a specific application, contact your local Schneider Electric Representative.
-
Impedance values are for busway operating at
176°F (80°C) temperature.
Resistance Values for Aluminum Integral Ground Bus
Ampere Rating 3Ø3W and 3Ø4W | DC Resistance (Milliohms per 100 Feet) | |
---|---|---|
Aluminum Phase Conductors | Copper Phase Conductors | |
225 | 8.1 | 8.1 |
400 | 6.4 | 6.4 |
600 | 5.3 | 6.4 |
800 | 4 | 4.4 |
1000 | 3.5 | 4 |
1200 | 3.2 | 3.5 |
1350 | 3 | 3.4 |
1600 | 2.8 | 3 |
2000 | 2.2 | 3 |
2500 | 2 | 2.2 |
3000 | 1.8 | 2 |
3200 | — | 1.7 |
4000 | 1.7 | 1.7 |
5000 | — | 1.7 |
Voltage Drop Data (60 Hz At Rated Load)
The values expressed below are based on a single concentrated load at the end of the busway run. For distributed loading, divide the values shown by two (2).
Power Factor–Average Phase Line-To-Line Voltage Drop in Volts Per 100 ft (3048 cm)
Ampere Rating | Power Factor – Aluminum Busway | Power Factor – Copper Busway | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
100 | 90 | 80 | 70 | 50 | 30 | 20 | 100 | 90 | 80 | 70 | 50 | 30 | 20 | |
225 | 2.84 | 3.14 | 3.08 | 2.94 | 2.58 | 2.12 | 1.87 | 1.58 | 2.06 | 2.14 | 2.15 | 2.06 | 1.87 | 1.75 |
400 | 2.57 | 3.1 | 3.14 | 3.09 | 2.84 | 2.49 | 2.28 | 1.48 | 2.02 | 2.14 | 2.17 | 2.12 | 1.96 | 1.86 |
600 | 2.12 | 2.63 | 2.69 | 2.66 | 2.49 | 2.21 | 2.04 | 2.21 | 3.03 | 3.2 | 3.26 | 3.18 | 2.94 | 2.79 |
Aluminum Busway–Average Phase Line-to-Line Voltage Drop in Volts Per 100 ft (3048 cm)
Ampere Rating | Aluminum Busway – Power Factor % | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
100 | 95 | 90 | 85 | 80 | 75 | 70 | 60 | 50 | 40 | 30 | 20 | |
800 | 3.7 | 3.91 | 3.88 | 3.81 | 3.72 | 3.61 | 3.49 | 3.23 | 2.94 | 2.64 | 2.31 | 1.98 |
1000 | 3.72 | 3.94 | 3.91 | 3.84 | 3.75 | 3.64 | 3.52 | 3.26 | 2.97 | 2.66 | 2.34 | 2 |
1200 | 3.37 | 3.59 | 3.57 | 3.52 | 3.44 | 3.35 | 3.25 | 3.02 | 2.76 | 2.49 | 2.2 | 1.9 |
1350 | 3.18 | 3.41 | 3.4 | 3.36 | 3.29 | 3.2 | 3.11 | 2.9 | 2.66 | 2.41 | 2.14 | 1.85 |
1600 | 3.33 | 3.6 | 3.6 | 3.56 | 3.5 | 3.42 | 3.32 | 3.11 | 2.87 | 2.6 | 2.32 | 2.02 |
2000 | 3.42 | 3.69 | 3.7 | 3.65 | 3.59 | 3.5 | 3.41 | 3.18 | 2.94 | 2.66 | 2.38 | 2.07 |
2500 | 3.68 | 3.97 | 3.98 | 3.93 | 3.86 | 3.77 | 3.66 | 3.42 | 3.16 | 2.87 | 2.55 | 2.23 |
3000 | 3.17 | 3.43 | 3.44 | 3.41 | 3.35 | 3.27 | 3.19 | 2.99 | 2.76 | 2.51 | 2.24 | 1.96 |
4000 | 3.07 | 3.24 | 3.22 | 3.16 | 3.08 | 2.99 | 2.89 | 2.67 | 2.43 | 2.18 | 1.91 | 1.63 |
-
For optimized values on a specific application, contact your local Schneider Electric Representative.
-
For balanced 3-phase line-to-line voltage drop 4-wire busway, use values from tables.
-
For balanced 3-phase line-to-neutral voltage drop, multiply values from tables by .577.
-
For single-phase voltage drop, multiply values from tables by 1.15.
-
For other than rated current, multiply values from tables by Actual Current ÷ Rated Current.
For different lengths, multiply values from 60 Hz tables by Actual Footage ÷ 100 ft. -
Voltage drop calculations for 50 Hz can be made by substituting the appropriate “x” value from Voltage Drop Sample Calculations (60 Hz) into samples No.1 and 2 above. For other frequency values (e.g., 400 Hz), contact your local Schneider Electric representative for assistance.
-
For plug-in distributed loads, divide the voltage drop by 2. See IEEE Standard 141-13.8.3.
Copper Busway–Average Phase Line-to-Line Voltage Drop in Volts Per 100 ft (3048 cm)
Ampere Rating | Copper Busway – Power Factor % | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
100 | 95 | 90 | 85 | 80 | 75 | 70 | 60 | 50 | 40 | 30 | 20 | |
800 | 2.58 | 2.92 | 2.98 | 2.99 | 2.98 | 2.94 | 2.89 | 2.77 | 2.61 | 2.43 | 2.23 | 2.01 |
1000 | 3.33 | 3.74 | 3.8 | 3.8 | 3.77 | 3.72 | 3.65 | 3.48 | 3.27 | 3.03 | 2.76 | 2.48 |
1200 | 3.17 | 3.61 | 3.69 | 3.7 | 3.68 | 3.64 | 3.59 | 3.43 | 3.24 | 3.02 | 2.78 | 2.51 |
1350 | 2.73 | 3.14 | 3.22 | 3.25 | 3.24 | 3.21 | 3.17 | 3.05 | 2.89 | 2.71 | 2.5 | 2.27 |
1600 | 2.88 | 3.33 | 3.43 | 3.46 | 3.45 | 3.43 | 3.38 | 3.26 | 3.1 | 2.91 | 2.69 | 2.45 |
2000 | 2.9 | 3.34 | 3.42 | 3.45 | 3.44 | 3.41 | 3.36 | 3.23 | 3.06 | 2.87 | 2.65 | 2.4 |
2500 | 2.62 | 3.06 | 3.15 | 3.19 | 3.19 | 3.17 | 3.13 | 3.03 | 2.88 | 2.71 | 2.52 | 2.31 |
3000 | 2.76 | 3.23 | 3.33 | 3.37 | 3.37 | 3.35 | 3.32 | 3.21 | 3.06 | 2.88 | 2.68 | 2.45 |
3200 | 2.65 | 3.06 | 3.15 | 3.17 | 3.17 | 3.14 | 3.1 | 2.99 | 2.84 | 2.67 | 2.47 | 2.25 |
4000 | 2.72 | 3.09 | 3.15 | 3.16 | 3.14 | 3.11 | 3.05 | 2.92 | 2.75 | 2.56 | 2.35 | 2.12 |
5000 | 2.4 | 2.78 | 2.86 | 2.89 | 2.89 | 2.87 | 2.83 | 2.73 | 2.6 | 2.44 | 2.26 | 2.06 |
-
For optimized values on a specific application, contact your local Schneider Electric Representative.
-
For balanced 3-phase line-to-line voltage drop 4-wire busway, use values from tables.
-
For balanced 3-phase line-to-neutral voltage drop, multiply values from tables by .577.
-
For single-phase voltage drop, multiply values from tables by 1.15.
-
For other than rated current, multiply values from tables by Actual Current ÷ Rated Current
For different lengths, multiply values from 60 Hz tables by Actual Footage ÷ 100 ft -
Voltage drop calculations for 50 Hz can be made by substituting the appropriate “x” value from Voltage Drop Sample Calculations (60 Hz) into samples No.1 and 2 above. For other frequency values (e.g., 400 Hz), contact your local Schneider Electric representative for assistance.
-
For plug-in distributed loads, divide the voltage drop by 2. See IEEE Standard 141-13.8.3.
Voltage Drop Sample Calculations (60 Hz)
Sample No. 1 | Sample No. 2 |
---|---|
1000 A aluminum busway at 50% power factor–60 Hz |
1000 A copper busway at 50% power factor–60 Hz |
Voltage Drop | Voltage Drop |
= √3 I (R cos Ø + x sin Ø) | = √3 I (R cos Ø + x sin Ø) |
= √3 X 1000 (.00215 x .50 + .00074 x .866) | = √3 X 1000 (.00163 x .50 + .00096 x .866) |
= 2.97 Volts/100 ft = concentrated load | = 2.85 Volts/100 ft = concentrated load |
= 2.85 ÷ 2 = 1.43 Volts/100 ft = distributed load |