Prepare the Maintenance Bypass Cabinet for Cables in Top Cable Entry Systems
![]() |
---|
hazard of electric shock, explosion, or arc flash
Do not drill/punch holes for cables or conduits with the
gland plates installed and do not drill/punch holes in close proximity
to the UPS system.
Failure to follow these instructions will result in death or serious injury.
|
- Remove the indicated plate in the bottom of the maintenance bypass cabinet.
- Remove the indicated plate in the bottom of the maintenance bypass cabinet.
- Remove the indicated plate in the top of the maintenance bypass cabinet.
- Remove the indicated plate in the top of the maintenance bypass cabinet.
- Loosen the bolts and remove the top gland plates of the maintenance bypass cabinet. Drill or cut holes for cables/conduits.
- Install conduits and reinstall the top gland plates in
the maintenance bypass cabinet.
DANGER
hazard of electric shock, explosion, or arc flashEnsure that there are no sharp edges that can damage the cables.Failure to follow these instructions will result in death or serious injury.