0611IB1302-09

MicroLogic Trip Unit Registers

Real-Time Measurements

General Description

The real-time measurements are refreshed every second. Real-time measurements include:

  • voltage and voltage unbalance

  • current and current unbalance

  • active, reactive, apparent, and distortion power

  • reactive power with harmonic

  • power factor and fundamental power factor

  • frequency

  • THD (total harmonic distortion)

Voltage

Register = 0 if voltage < 25 V.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x03E7

1000

R

1

V

INT16U

0–850

E

RMS phase-to-phase voltage VAB

0x03E8

1001

R

1

V

INT16U

0–850

E

RMS phase-to-phase voltage VBC

0x03E9

1002

R

1

V

INT16U

0–850

E

RMS phase-to-phase voltage VCA

0x03EA

1003

R

1

V

INT16U

0–850

E

RMS phase-to-neutral voltage VAN (1)

0x03EB

1004

R

1

V

INT16U

0–850

E

RMS phase-to-neutral voltage VBN (1)

0x03EC

1005

R

1

V

INT16U

0–850

E

RMS phase-to-neutral voltage VCN (1)

0x03ED

1006

R

1

V

INT16U

0–850

E

Arithmetic mean of VAB, VBC, and VCA: (VAB + VBC + VCA) / 3 = Vavg L-L

0x03EE

1007

R

1

V

INT16U

0–850

E

Arithmetic mean of VAN, VBN, and VCN: (VAN + VBN + VCN) / 3 = Vavg L-N (1)

0x0478

1145

R

1

V

INT16U

0–850

E

Vmax: maximum of VAB, VBC, and VCA (2)

0x0479

1146

R

1

V

INT16U

0–850

E

Vmin: minimum of VAB, VBC, and VCA (2)

(1) This value is not available for motor application and not accessible when the system type in register 3314 is 30 or 31. Refer to System Type.

(2) This value can be reset with the reset minimum/maximum command Reset Minimum/Maximum.

Voltage Unbalance

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x03EF

1008

R

10

%

INT16U

-1000–+1000

E

VAB phase-to-phase voltage unbalance in relation to the arithmetic mean of phase-to-phase voltages

0x03F0

1009

R

10

%

INT16U

-1000–+1000

E

VBC phase-to-phase voltage unbalance in relation to the arithmetic mean of phase-to-phase voltages

0x03F1

1010

R

10

%

INT16U

-1000–+1000

E

VCA phase-to-phase voltage unbalance in relation to the arithmetic mean of phase-to-phase voltages

0x03F2

1011

R

10

%

INT16U

-1000–+1000

E

VAN phase-to-neutral voltage unbalance in relation to the arithmetic mean of phase-to-neutral voltages (1)

0x03F3

1012

R

10

%

INT16U

-1000–+1000

E

VBN phase-to-neutral voltage unbalance in relation to the arithmetic mean of phase-to-neutral voltages (1)

0x03F4

1013

R

10

%

INT16U

-1000–+1000

E

VCN phase-to-neutral voltage unbalance in relation to the arithmetic mean of phase-to-neutral voltages (1)

0x03F5

1014

R

10

%

INT16U

-1000–+1000

E

Maximum phase-to-phase voltage unbalance value of registers 1008, 1009, and 1010 (2)

0x03F6

1015

R

10

%

INT16U

-1000–+1000

E

Maximum phase-to-neutral voltage unbalance value of registers 1011, 1012, and 1013 (1)(2)

(1) This value is not available for motor application and when the system type in register 3314 is 30 or 31. Refer to System Type.

(2) This value can be reset with the reset minimum/maximum command Reset Minimum/Maximum.

Current

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x03F7

1016

R

1

A

INT16U

0–20xIn

A/E

RMS current on phase A: IA

0x03F8

1017

R

1

A

INT16U

0–20xIn

A/E

RMS current on phase B: IB

0x03F9

1018

R

1

A

INT16U

0–20xIn

A/E

RMS current on phase C: IC

0x03FA

1019

R

1

A

INT16U

0–20xIn

A/E

RMS current on the neutral: IN (1)

0x03FB

1020

R

1

A

INT16U

0–20xIn

A/E

Maximum of IA, IB, IC, and IN (2)

0x03FC

1021

R

1

%Ig

INT16U

0–20xIn

A/E

Ground-fault current

0x03FD

1022

R

Reserved

0x0401

1026

R

1

A

INT16U

0–20xIn

A/E

Minimum of IA, IB, and IC (2)

0x0402

1027

R

1

A

INT16U

0–20xIn

A/E

Arithmetic mean of IA, IB, and IC: (IA + IB + IC) / 3 = Iavg

(1) This value is not available for motor application and when the system type in register 3314 is 31 or 40. Refer to System Type.

(2) This value can be reset with the reset minimum/maximum command Reset Minimum/Maximum.

Current Unbalance

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0403

1028

R

10

%

INT16

-1000–+1000

E

IA current unbalance in relation to the arithmetic mean of the phase currents

0x0404

1029

R

10

%

INT16

-1000–+1000

E

IB current unbalance in relation to the arithmetic mean of the phase currents

0x0405

1030

R

10

%

INT16

-1000–+1000

E

IC current unbalance in relation to the arithmetic mean of the phase currents

0x0406

1031

R

10

%

INT16

-1000–+1000

E

IN current unbalance in relation to the arithmetic mean of the phase current (1)

0x0407

1032

R

10

%

INT16

-1000–+1000

E

Maximum current unbalance of registers 1028, 1029, and 1030 (2)

(1) This value is not available for motor application and when the system type in register 3314 is 31 or 40. Refer to System Type.

(2) This value can be reset with the reset minimum/maximum command Reset Minimum/Maximum.

Active Power

The flow sign of the active power depends on the configuration of register 3316 Power Flow Sign.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0409

1034

R

10

kW

INT16

-10000–+10000

E

Active power on phase A: PA (1)

0x040A

1035

R

10

kW

INT16

-10000–+10000

E

Active power on phase B: PB (1)

0x040B

1036

R

10

kW

INT16

-10000–+10000

E

Active power on phase C: PC (1)

0x040C

1037

R

10

kW

INT16

-30000–+30000

E

Total active power: Ptot

(1) This value is not available for motor application and when the system type in register 3314 is 30 or 31. Refer to System Type.

Reactive Power

The flow sign of the reactive power depends on the configuration of register 3316 Power Flow Sign.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x040D

1038

R

10

kVAR

INT16

-10000–+10000

E

Reactive power on phase A: QA (1)

0x040E

1039

R

10

kVAR

INT16

-10000–+10000

E

Reactive power on phase B: QB (1)

0x040F

1040

R

10

kVAR

INT16

-10000–+10000

E

Reactive power on phase C: QC (1)

0x0410

1041

R

10

kVAR

INT16

-30000–+30000

E

Total reactive power: Qtot

(1) This value is not available for motor application and when the system type in register 3314 is 30 or 31. Refer to System Type.

Apparent Power

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0411

1042

R

10

kVAR

INT16

0–10000

E

Apparent power on phase A: SA (1)

0x0412

1043

R

10

kVAR

INT16

0–10000

E

Apparent power on phase B: SB (1)

0x0413

1044

R

10

kVAR

INT16

0–10000

E

Apparent power on phase C: SC (1)

0x0414

1045

R

10

kVAR

INT16

0–30000

E

Total apparent power: Stot

(1) This value is not available for motor application and when the system type in register 3314 is 30 or 31. Refer to System Type.

Power Factor

The sign of the power factor depends on the configuration of register 3318 Power Factor Sign.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0415

1046

R

100

INT16

-100–+100

E

Power factor on phase A: PFA (1)

0x0416

1047

R

100

INT16

-100–+100

E

Power factor on phase B: PFB (1)

0x0417

1048

R

100

INT16

-100–+100

E

Power factor on phase C: PFC (1)

0x0418

1049

R

100

INT16

-100–+100

E

Total power factor: PF

(1) This value is not available for motor application and when the system type in register 3314 is 30 or 31. Refer to System Type.

Fundamental Power Factor (cosϕ)

The sign of the fundamental power factor (cosϕ) depends on the configuration of register 3318 Power Factor Sign.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0419

1050

R

100

INT16

-100–+100

E

Fundamental power factor on phase A: cosϕ A (1)

0x041A

1051

R

100

INT16

-100–+100

E

Fundamental power factor on phase B: cosϕ B (1)

0x041B

1052

R

100

INT16

-100–+100

E

Fundamental power factor on phase C: cosϕ C (1)

0x041C

1053

R

100

INT16

-100–+100

E

Total fundamental power factor: cosφ

(1) This value is not available for motor application and when the system type in register 3314 is 30 or 31. Refer to System Type.

Frequency

When the MicroLogic trip unit cannot calculate the frequency, it returns Not Evaluated = 32768 (0x8000).

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x041D

1054

R

10

Hz

INT16U

150–4400

E

System frequency: F

Fundamental Reactive Power

The flow sign of the reactive power depends on the configuration of register 3316 Power Flow Sign.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0437

1080

R

10

kVAR

INT16

-10000–+10000

E

Fundamental reactive power on phase A: QA Fund (1)

0x0438

1081

R

10

kVAR

INT16

-10000–+10000

E

Fundamental reactive power on phase B: QB Fund (1)

0x0439

1082

R

10

kVAR

INT16

-10000–+10000

E

Fundamental reactive power on phase C: QC Fund (1)

0x043A

1083

R

10

kVAR

INT16

-10000–+10000

E

Total fundamental reactive power: Qtot Fund

(1) This value is not available for motor application and when the system type in register 3314 is 30 or 31. Refer to System Type.

Distortion Power

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x043F

1088

R

10

kVAR

INT16U

0–10000

E

Distortion power on phase A: DA (1)

0x0440

1089

R

10

kVAR

INT16U

0–10000

E

Distortion power on phase B: DB (1)

0x0441

1090

R

10

kVAR

INT16U

0–10000

E

Distortion power on phase C: DC (1)

0x0442

1091

R

10

kVAR

INT16U

0–10000

E

Total distortion power: Dtot

(1) This value is not available for motor application and when the system type in register 3314 is 30 or 31. Refer to System Type.

Total Harmonic Distortion (THD)

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0443

1092

R

10

%

INT16U

0–32766

E

Total harmonic distortion of VAB in relation to the fundamental

0x0444

1093

R

10

%

INT16U

0–32766

E

Total harmonic distortion of VBC in relation to the fundamental

0x0445

1094

R

10

%

INT16U

0–32766

E

Total harmonic distortion of VCA in relation to the fundamental

0x0446

1095

R

10

%

INT16U

0–32766

E

Total harmonic distortion of VAN in relation to the fundamental (1)

0x0447

1096

R

10

%

INT16U

0–32766

E

Total harmonic distortion of VBN in relation to the fundamental (1)

0x0448

1097

R

10

%

INT16U

0–32766

E

Total harmonic distortion of VCN in relation to the fundamental (1)

0x0449

1098

R

10

%

INT16U

0–32766

E

Total harmonic distortion of IA in relation to the fundamental

0x044A

1099

R

10

%

INT16U

0–32766

E

Total harmonic distortion of IB in relation to the fundamental

0x044B

1100

R

10

%

INT16U

0–32766

E

Total harmonic distortion of IC in relation to the fundamental

(1) This value is not available for motor application and when the system type in register 3314 is 30 or 31. Refer to System Type.

Thermal Image of Motor

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0477

1144

R

1

%

INT16U

0–32766

E

Ith image

Minimum/Maximum Values of Real-Time Measurements

Minimum/Maximum Measurements Rule

Minimum and maximum measurements take into account the absolute value of real-time measurements. Therefore the following rule applies:

0<10<200<-400<600<-3800.

In this case:

  • the minimum value = 0

  • the maximum value = -3800

NOTE: This rule does not apply for the power factor (PF) and for the fundamental power factor (cosϕ):
  • PFmax (or cosϕ max.) is obtained for the smallest positive value of PF (or cosϕ).

  • PFmin (or cosϕ min.) is obtained for the highest negative value of PF (or cosϕ).

The reset minimum/maximum command (command code = 46728) can reset the content of the minimum/maximum real-time measurement registers.

Minimum of Real-Time Measurements

Registers 1300 to 1599 hold the minimum values of real-time metering parameters:

  • The register of the minimum value of a real-time metering parameter is equal to the register of the real-time metering parameter plus 300.

    Examples

    • Register 1300 holds the minimum value of the phase-to-phase voltage VAB (register 1000).

    • Register 1316 holds the minimum value of the current on phase A (register 1016).

  • The order of the registers is the same as that of the real-time metering variables.

  • The scale factors of the minimum values are the same as those of the real-time metering parameters.

  • The minimum values of unbalance current and unbalance voltage are not available.

  • The minimum values of Imin (register 1026), Vmax (register 1145), and Vmin (register 1146) are not available.

Maximum of Real-Time Measurements

Registers 1600 to 1899 hold the maximum values of real-time metering parameters:

  • The register of the maximum value of a real-time metering parameter is equal to the register of the real-time metering parameter plus 600.

    Examples

    • Register 1600 holds the maximum value of the phase-to-phase voltage VAB (register 1000).

    • Register 1616 holds the maximum value of the current on phase A (register 1016).

  • The order of the registers is the same as that of the real-time metering variables.

  • The scale factors of the maximum values are the same as those of the real-time metering parameters.

  • The maximum values of Imin (register 1026), Vmax (register 1145), and Vmin (register 1146) are not available.

Energy Measurements

General Description

The energy measurements are refreshed every second. Energy measurements are saved every hour in the non-volatile memory of the MicroLogic trip unit.

Energy measurements include:

  • active energy Ep

  • reactive energy Eq

  • apparent energy Es

  • active energy counted positively (EpIn) or negatively (EpOut), according to the configuration of register 3316 Power Flow Sign.

  • reactive energy counted positively (EqIn) or negatively (EqOut), according to the configuration of register 3316 Power Flow Sign.

  • active energy and reactive energy are accumulated according to the configuration of register 3324 (absolute mode by factory setting) Energy Accumulation Mode.

The reset minimum/maximum command (command code = 46728) can reset the content of the energy measurement registers, cumulative energy measurements excepted.

NOTE: The power flow sign configuration command (command code =47240) can reset the content of the energy measurement registers excluding the cumulative energy measurements.

Energy Registers

Energies are stored in big-endian format: the most significant word is transmitted first and the least significant second.

Examples

If Ep = 7589 kWh, then:

  • register 2000 = 0 (0x0000)

  • register 2001 = 7589 (0x1DA5)

If Ep = 4,589,625 kWh, then:

  • register 2000 = 70 (0x0046)

  • register 2001 = 2105 (0x0839)

4589625 = 70x65536 + 2105

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x07CF–

0x07D0

2000–

2001

R

1

kWh

INT32

-1 999 999 999–+1 999 999 999

E

Active energy: Ep

0x07D3–

0x07D4–

2004–

2005

R

1

kVARh

INT32

-1 999 999 999–+1 999 999 999

E

Reactive energy: Eq

0x07D7–

0x07D8

2008–

2009

R

1

kWh

INT32

0–1 999 999 999

E

Active energy counted positively: EpIn

0x07DB–

0x07DC

2012–

2013

R

1

kWh

INT32

0–1 999 999 999

E

Active energy counted negatively: EpOut

0x07DF–

0x07E0

2016–

2017

R

1

kVARh

INT32

0–1 999 999 999

E

Reactive energy counted positively: EqIn

0x07E3–

0x07E4

2020–

2021

R

1

kVARh

INT32

0–1 999 999 999

E

Reactive energy counted negatively: EqOut

0x07E7–

0x07E8

2024–

2025

R

1

kVAh

INT32

0–1 999 999 999

E

Apparent energy: Es

0x07EB–

0x07EC

2028–

2029

R

1

kWh

INT32

0–1 999 999 999

E

Cumulative active energy counted positively (cannot be reset): EpIn

0x07ED–

0x07EE

2030–

2031

R

1

kWh

INT32

0–1 999 999 999

E

Cumulative active energy counted negatively (cannot be reset): EpOut

Demand Measurements

General Description

Demand registers include:

  • current demand

  • active, reactive, and apparent power demand

The window duration of current demand depends on the configuration of register 3352 Demand Time.

The window duration and the window type of power demand depend on the configuration of registers 3354 and 3355 Demand Time.

The demand measurements are refreshed every minute with the sliding window type.

The demand measurements are refreshed at the end of the window interval with the block window type.

Current Demand

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0897

2200

R

1

A

INT16U

0–20xIn

E

Current demand on phase A: IA Dmd

0x0898

2201

R

1

A

INT16U

0–20xIn

E

Current demand on phase B: IB Dmd

0x0899

2202

R

1

A

INT16U

0–20xIn

E

Current demand on phase C: IC Dmd

0x089A

2203

R

1

A

INT16U

0–20xIn

E

Current demand on the neutral: IN Dmd (1)

0x089B

2204

R

1

A

INT16U

0–20xIn

E

Maximum of current demand on phase A: IA Peak Dmd (2)

0x089C

2205

R

1

A

INT16U

0–20xIn

E

Maximum of current demand on phase B: IB Peak Dmd (2)

0x089D

2206

R

1

A

INT16U

0–20xIn

E

Maximum of current demand on phase C: IC Peak Dmd (2)

0x089E

2207

R

1

A

INT16U

0–20xIn

E

Maximum of current demand on the neutral: IN Peak Dmd (1) (2)

(1) This value is not available when the system type in register 3314 is 31 or 40. Refer to System Type.

(2) This value can be reset with the reset minimum/maximum command Reset Minimum/Maximum.

Active Power Demand

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x08AF

2224

R

10

kW

INT16

-30000–+30000

E

Total active power demand: P Dmd (1)

0x08B0

2225

R

10

kW

INT16

-30000–+30000

E

Maximum of total active power demand: P Peak Dmd (2)

(1) For the block window type, this value is updated at the end of the window interval. For the sliding window type, the value is updated every minute.

(2) This value can be reset with the reset minimum/maximum command Reset Minimum/Maximum.

Reactive Power Demand

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x08B5

2230

R

10

kVAR

INT16

-30000–+30000

E

Total reactive power demand: Q Dmd (1)

0x08B6

2231

R

10

kVAR

INT16

-30000–+30000

E

Maximum of total reactive power demand: Q Peak Dmd (2)

(1) For the block window type, this value is updated at the end of the window interval. For the sliding window type, the value is updated every minute.

(2) This value can be reset with the reset minimum/maximum command Reset Minimum/Maximum.

Apparent Power Demand

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x08BB

2236

R

10

kVA

INT16

0–30000

E

Total apparent power demand: S Dmd (1)

0x08BC

2237

R

10

kVA

INT16

0–30000

E

Maximum of total apparent power demand: S Peak Dmd (2)

(1) For the block window type, this value is updated at the end of the window interval. For the sliding window type, the value is updated every minute.

(2) This value can be reset with the reset minimum/maximum command Reset Minimum/Maximum.

Minimum/Maximum Measurements Reset Time

Overview

The minimum/maximum measurements reset time registers enable the user to know all the dates relative to the last reset minimum/maximum command.

The reset minimum/maximum command (command code 46728) can reset the content of the minimum/maximum measurements registers.

A read request of 30 registers is necessary to read the minimum/maximum measurements reset time.

Minimum/Maximum Measurements Reset Time

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0B53–

0x0B55

2900–

2902

R

ULP DATE

A/E

Date and time of reset of minimum/maximum current. Data Type: ULP DATE

0x0B56–

0x0B58

2903–

2905

R

ULP DATE

E

Date and time of reset of minimum/maximum voltage.

0x0B59–

0x0B5B

2906–

2908

R

ULP DATE

E

Date and time of reset of minimum/maximum power (P, Q, S).

0x0B5C–

0x0B5E

2909–

2911

R

ULP DATE

E

Date and time of reset of minimum/maximum power factor and cosϕ.

0x0B5F–

0x0B61

2912–

2914

R

ULP DATE

E

Date and time of reset of minimum/maximum total harmonic distortion.

0x0B62–

0x0B64

2915–

2917

R

ULP DATE

E

Date and time of reset of peak current demand.

0x0B65–

0x0B67

2918–

2920

R

ULP DATE

E

Date and time of reset of peak active, reactive, and apparent power demand.

0x0B68–

0x0B6A

2921–

2923

R

ULP DATE

E

Date and time of reset of minimum/maximum frequency.

0x0B6B–

0x0B6D

2924–

2926

R

ULP DATE

E

Date and time of reset of minimum/maximum thermal image of motor.

0x0B6E–

0x0B70

2927–

2929

R

ULP DATE

E

Date and time of reset of energy (active, reactive, and apparent).

MicroLogic Trip Unit Identification

Serial Number

The MicroLogic trip unit serial number is composed of a maximum of 11 alphanumeric characters with the following format: PPYYWWDnnnn.

  • PP = plant code

  • YY = year of fabrication (05–99)

  • WW = week of fabrication (01–53)

  • D = day of fabrication (1–7)

  • nnnn = sequence number (0001–9999)

A read request of 6 registers is necessary to read the MicroLogic trip unit serial number.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x21FB

8700

R

OCTET STRING

A/E

‘PP’

0x21FC

8701

R

OCTET STRING

‘05’–‘99’

A/E

‘YY’

0x21FD

8702

R

OCTET STRING

‘01’–‘52’

A/E

‘WW’

0x21FE

8703

R

OCTET STRING

D: ‘1’–‘7’

n: ‘0’–‘9’

A/E

‘Dn’

0x21FF

8704

R

OCTET STRING

‘00’–‘99’

A/E

‘nn’

0x2200

8705

R

OCTET STRING

‘0’–‘9’

A/E

‘n’ (the NULL character ends the serial number)

Hardware Revision

For MicroLogic trip units with firmware revision up to V1.2.1, the hardware revision is an integer.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x2204

8709

R

INT16U

0–15

A/E

Hardware revision of the MicroLogic trip unit.

For MicroLogic trip units with firmware revision greater than or equal to V1.2.2, the hardware revision is an ASCII string using the format XXX.YYY.ZZZ with:

  • XXX = major version (000-127)

  • YYY = minor version (000-255)

  • ZZZ = revision number (000-255)

The NULL character ends the revision number.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x2212–0x2217

8723-8728

R

OCTET STRING

A/E

Hardware revision of the MicroLogic trip unit.

Product Identification

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x220B

8716

R

INT16U

15143–15145

A/E

Product identification:

  • 15143 = distribution application, type A

  • 15144 = distribution application, type E

  • 15145 = motor application, type E

Protection Type

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x2223

8740

R

OCTET STRING

52–73

A/E

MicroLogic trip unit protection type:

  • For H- and J-frame:

    ‘52’ = LSI

    ‘62’ = LSIG

    ‘72’ = LSIV

  • For L-frame:

    ‘53’ = LSI

    ‘63’ = LSIG

    ‘73’ = LSIV

Metering Type

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x2224

8741

R

OCTET STRING

A–E

A/E

MicroLogic trip unit metering type:

‘A’ or ‘E’

Application

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x222A

8747

R

INT16U

1–2

A/E

Application:

1 = distribution

2 = motor

Standard

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x222B

8748

R

INT16U

1–3

A/E

Standard:

1 = UL

2 = IEC

3 = JIS

Sensor Rating

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x222D

8750

R

INT16U

0–8000

A/E

Circuit breaker sensor rating In

Pole

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x222E

8751

R

INT16U

0–1

A/E

0 = 3-pole

1 = 4-pole

16 Hz 2/3

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x222F

8752

R

INT16U

0–1

A/E

0 = not a 16 Hz 2/3 MicroLogic trip unit application

1 = 16 Hz 2/3 MicroLogic trip unit application

Firmware Revision

For MicroLogic trip units with firmware revision up to V1.2.1, the firmware revision is an ASCII string using the format VXXX.YYY.ZZZ with:

  • XXX = major version (001-999)

  • YYY = minor version (001-999)

  • ZZZ = revision number (001-999)

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7529–0x752D

29994–29998

R

OCTET STRING

A/E

Firmware revision of the MicroLogic trip unit.

For MicroLogic trip units with firmware revision greater than or equal to V1.2.2, the firmware revision is an ASCII string using the format XXX.YYY.ZZZ with:

  • XXX = major version (000-127)

  • YYY = minor version (000-255)

  • ZZZ = revision number (000-255)

The NULL character ends the revision number.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x220C–0x2211

8717–8722

R

OCTET STRING

A/E

Firmware revision of the MicroLogic trip unit.

Part Number

The part number starts with LV4 characters and has the following format: LV4XYZTW.

A read request of 4 registers is necessary to read the MicroLogic trip unit part number.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x752F

30000

R

OCTET STRING

A/E

Example: ‘LV

0x7530

30001

R

OCTET STRING

A/E

Example: ‘4X

0x7531

30002

R

OCTET STRING

A/E

Example: ‘YZ

0x7532

30003

R

OCTET STRING

A/E

Example: ‘TW

Status

Alarms Status

The alarms status register indicates the current status of the alarms:

  • alarm bit = 0: alarm is not active.

  • alarm bit = 1: alarm is active.

The following table describes the values for each bit of the alarm status register:

Address

Register

RW

X

Unit

Type

Range

A/E

Bit

Description

0x1647

5704

R

INT16U

A/E

Alarm status

A/E

0

User-defined alarm 201

A/E

1

User-defined alarm 202

A/E

2

User-defined alarm 203

A/E

3

User-defined alarm 204

A/E

4

User-defined alarm 205

A/E

5

User-defined alarm 206

A/E

6

User-defined alarm 207

A/E

7

User-defined alarm 208

A/E

8

User-defined alarm 209

A/E

9

User-defined alarm 210

A/E

10

Long-time protection Ir pre-alarm (PAL Ir)

11

Reserved

A/E

12

Ground-fault protection Ig pre-alarm (PAL Ig)

13–15

Reserved

SDx Module Status

The SDx module status register indicates the status and the validity of the SDx outputs (2 outputs maximum):

  • status bit = 0: the output is open.

  • status bit = 1: the output is closed.

  • validity bit = 0: the output status is unknown.

  • validity bit = 1: the output status is known.

The following table describes the values for each bit of the SDx module status register:

Address

Register

RW

X

Unit

Type

Range

A/E

Bit

Description

0x2298

8857

R

INT16U

A/E

SDx module status

A/E

0

Status of output 1

A/E

1

Status of output 2

2–7

Reserved

A/E

8

Validity of output 1

A/E

9

Validity of output 2

10–15

Reserved

Trip Status

The trip status register indicates the current status of the trip:

  • trip bit = 0: trip is not active.

  • trip bit = 1: trip is active.

The following table describes the values for each bit of the trip status register:

Address

Register

RW

X

Unit

Type

Range

A/E

Bit

Description

0x270F

10000

R

INT16U

A/E

Trip status

A/E

0

Long-time protection Ir

A/E

1

Short-time protection Isd

A/E

2

Instantaneous protection Ii

A/E

3

Ground-fault protection Ig

E

4

Reserved

A/E

5

Integrated instantaneous protection

A/E

6

Trip unit internal failure (STOP)

E

7

Reserved

A/E

8

Unbalance motor protection Iunbal

A/E

9

Jam motor protection Ijam

A/E

10

Underload motor protection Iunderload

A/E

11

Long-start motor protection Ilongstart

A/E

12

Reflex tripping protection

13–15

Reserved

Alarm History

General Description

The alarm history registers describe the last 10 encountered alarms. The alarm history format corresponds to a series of 10 records. Each record is composed of 5 registers describing one alarm.

The alarm history registers return 32768 (0x8000) when they are not used.

Record Number

A read request of 5x(n) registers is necessary to read the last n alarm records, where 5 is the number of registers for each alarm record.

For example, a read request of 5 x 3 = 15 registers is necessary to read the last 3 alarm records of the alarm history:

  • The first 5 registers describe the first alarm record (most recent alarm).

  • The next 5 registers describe the second alarm record.

  • The last 5 registers describe the third alarm record.

Address

Register

Description

0x1663–0x1667

5732–5736

Alarm record 1 (most recent alarm)

0x1668–0x166C

5737–5741

Alarm record 2

0x166D–0x1671

5742–5746

Alarm record 3

0x1672–0x1676

5747–5751

Alarm record 4

0x1677–0x167B

5752–5756

Alarm record 5

0x167C–0x1680

5757–5761

Alarm record 6

0x1681–0x1685

5762–5766

Alarm record 7

0x1686–0x168A

5767–5771

Alarm record 8

0x168B–0x168F

5772–5776

Alarm record 9

0x1690–0x1694

5777–5781

Alarm record 10 (oldest alarm)

Alarm Record

A read request of 5 registers is necessary to read an alarm record.

The order and the description of the alarm records registers are the same as that of the alarm record 1:

Alarm Record 1 (Most Recent Alarm)

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x1663

5732

R

1

INT16U

0–65535

A/E

Alarm code (see next paragraph)

0x1664–

0x1666

5733–

5735

R

ULP DATE

A/E

Date and time of alarm Data Type: ULP DATE

0x1667

5736

R

1

INT16U

1–2

A/E

Event type

MSB = 0 (reserved)

Event occurrence: LSB = 1

Event completion: LSB = 2

Alarm Codes

Alarm Code

Description

201 (0x00C8)

User-defined alarm 201

202 (0x00C9)

User-defined alarm 202

203 (0x00CA)

User-defined alarm 203

204 (0x00CB)

User-defined alarm 204

205 (0x00CC)

User-defined alarm 205

206 (0x00CD)

User-defined alarm 206

207 (0x00CE)

User-defined alarm 207

208 (0x00CF)

User-defined alarm 208

209 (0x00D0)

User-defined alarm 209

210 (0x00D1)

User-defined alarm 210

1013 (0x03F4)

Long-time protection Ir pre-alarm (PAL Ir)

1014 (0x03F5)

Ground-fault protection Ig pre-alarm (PAL Ig)

1015 (0x03F6)

Reserved

The list of the predefined alarms from which the user can choose the 10 user-defined alarms is available at User-Defined Alarms.

Trip History

General Description

The trip history registers describe the last 17 encountered trips. The trip history format corresponds to a series of 17 records. Each record is composed of 7 registers describing one trip.

The trip history registers return 32768 (0x8000) when they are not used.

Trip Record Number

A read request of 7x(n) registers is necessary to read the last n trip records, where 7 is the number of registers for each trip record.

For example, a read request of 7 x 4 = 28 registers is necessary to read the last 4 trip records of the trip history:

  • The first 7 registers describe the first trip record (most recent trip).

  • The next 7 registers describe the second trip record.

  • The last 7 registers describe the third trip record.

  • The last 7 registers describe the fourth trip record.

Address

Register

Description

0x238B–0x2391

9100–9106

Trip record 1 (most recent trip)

0x2392–0x2398

9107–9113

Trip record 2

0x2399–0x239F

9114–9120

Trip record 3

0x23A0–0x23A6

9121–9127

Trip record 4

0x23A7–0x23AD

9128–9134

Trip record 5

0x23AE–0x23B4

9135–9141

Trip record 6

0x23B5–0x23BB

9142–9148

Trip record 7

0x23BC–0x23C2

9149–9155

Trip record 8

0x23C3–0x23C9

9156–9162

Trip record 9

0x23CA–0x23D0

9163–9169

Trip record 10

0x23D1–0x23D7

9170–9176

Trip record 11

0x23D8–0x23DE

9177–9183

Trip record 12

0x23DF–0x23E5

9184–9190

Trip record 13

0x23E6–0x23EC

9191–9197

Trip record 14

0x23ED–0x23F3

9198–9204

Trip record 15

0x23F4–0x23FA

9205–9211

Trip record 16

0x23FB–0x2401

9212–9218

Trip record 17 (oldest trip)

Trip Record

A read request of 7 registers is necessary to read a trip record.

The order and the description of the trip record registers are the same as that of the trip record 1:

Trip Record 1 (Most Recent Trip)

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x238B

9100

R

1

INT16U

0–65535

A/E

Trip code (see next paragraph)

0x238C–

0x238E

9101–

9103

R

ULP DATE

A/E

Date and time of event (trip or acknowledge. Data Type: ULP DATE

0x238F

9104

R

1

INT16U

1–2

A/E

Event type

MSB = 0 (reserved)

Event occurrence: LSB = 1

Event completion: LSB = 2

0x2390

9105

R

1

INT16U

0–5

A/E

Faulty phase

0 = failure (no faulty phase)

1 = phase A

2 = phase B

3 = phase C

4 = phase N

5 = phase A B C (motor application, ground-fault)

0x2391

9106

R

1

A

INT16U

0–65535

A/E

Interrupted current (peak) (1)

(1) Measurement depends on the application:

  • For electrical distribution application, the interrupted current is measured when a trip occurs, due to the long-time protection, the short-time protection, or the instantaneous protection.

  • For motor-feeder application, the interrupted current is measured when a trip occurs, due to the short-time protection.

  • In case of other trip types, the interrupted current is not measured and the value recorded is 65535 (0xFFFF).

Trip Codes

Trip Code

Description

1000 (0x03E8)

Long-time protection Ir

1001 (0x03E9)

Short-time protection Isd

1002 (0x03EA)

Instantaneous protection Ii

1003 (0x03EB)

Ground-fault protection Ig

1004 (0x03EC)

Reserved

1005–1009 (0x03ED–0x03F1)

Reserved

1010 (0x03F2)

Integrated instantaneous protection

1011 (0x03F3)

STOP (trip unit internal failure)

1012 (0x03F4)

Reserved

1013–1031 (0x03F5–0x0407)

Reserved

1032 (0x0408)

Unbalance motor protection

1033 (0x0409)

Jam motor protection

1034 (0x040A)

Underload motor protection

1035 (0x040B)

Long-start motor protection

1036 (0x040C)

Reflex tripping protection

Maintenance Operation History

General Description

The maintenance operation history registers describe the last 10 maintenance operations. The maintenance operation history format corresponds to a series of 10 records. Each record is composed of 5 registers describing one maintenance operation.

The maintenance operation history registers return 32768 (0x8000) when they are not used.

Maintenance Operation Number

A read request of 5 x n registers is necessary to read the last n maintenance operation records, where 5 is the number of registers for each maintenance operation record.

For example, a read request of 5 x 2 = 10 registers is necessary to read the last 2 maintenance operation records of the maintenance operation history:

  • The first 5 registers describe the first maintenance operation record (most recent maintenance operation).

  • The last 5 registers describe the second maintenance operation record.

Address

Register

Description

0x733B–0x733F

29500–29504

Maintenance operation record 1 (most recent maintenance operation)

0x7340–0x7344

29505–29509

Maintenance operation record 2

0x7345–0x7349

29510–29514

Maintenance operation record 3

0x734A–0x734E

29515–29519

Maintenance operation record 4

0x734F–0x7353

29520–29524

Maintenance operation record 5

0x7354–0x7358

29525–29529

Maintenance operation record 6

0x7359–0x735D

29530–29534

Maintenance operation record 7

0x735E–0x7362

29535–29539

Maintenance operation record 8

0x7363–0x7367

29540–29544

Maintenance operation record 9

0x7368–0x736C

29545–29549

Maintenance operation record 10 (oldest maintenance operation)

Maintenance Operation Record

A read request of 5 registers is necessary to read a maintenance operation record.

The order and the description of the maintenance operation record registers are the same as that of the maintenance operation record 1:

Maintenance Operation Record 1 (Most Recent Maintenance Operation)

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x733B

29500

R

1

INT16U

0–65535

A/E

Maintenance operation code (see next paragraph)

0x733C–

0x733E

29501–

29503

R

ULP DATE

A/E

Date and time of maintenance operation Data Type: ULP DATE

0x733F

29504

Reserved

Maintenance Operation Codes

Maintenance Operation Code

Description

2001 (0x07D0)

Ground-fault inhibition

2002 (0x07D1)

Reserved

2003 (0x07D2)

Start numerical injection test

2004 (0x07D3)

End numerical injection test

2005 (0x07D4)

Ground-fault test

2006 (0x07D5

Reserved

2007 (0x07D6)

Start alarm test

2008 (0x07D7)

End alarm test

2009 (0x07D8)

Start long-time protection

2010 (0x07D9

End long-time protection

2011 (0x07DA)

Start short-time protection

2012 (0x07DB)

End short-time protection

2013 (0x07DC)

Start instantaneous protection

2014 (0x07DD)

Stop instantaneous protection

2015 (0x07DE)

Start integrated instant protection

2016 (0x07DF)

Stop integrated instant protection

2017 (0x07E0)

Start unbalance protection

2018 (0x07E1)

Stop unbalance protection

2019 (0x07E2)

Start ground-fault protection

2020 (0x07E3)

Stop ground-fault protection

2021 (0x07E4)

Reserved

2022 (0x07E5)

Reserved

2023 (0x07E6)

Start thermal memory

2024 (0x07E7)

Stop thermal memory

2025 (0x07E8)

Start connection with UTA Maintenance Module or Service Interface Kit

2027 (0x07EA)

Turn rotary wheel 1

2028 (0x07EB)

Turn rotary wheel 2

2029 (0x07EC)

Locking pad open

2030 (0x07ED)

Locking pad closed

2031 (0x07EE)

ZSI test

2032 (0x07EF)

Reserved

2033 (0x07F0)

Reset software

2034 (0x07F1)

Reset minimum/maximum of current measurements

2035 (0x07F2)

Reset minimum/maximum of voltage measurements

2036 (0x07F3)

Reset minimum/maximum of power measurements

2037 (0x07F4)

Reset minimum/maximum of power factor measurements

2038 (0x07F5)

Reset minimum/maximum of total harmonic distortion measurements

2039 (0x07F6)

Reset maximum of current demand measurement

2040 (0x07F7)

Reset maximum of power demand (active, reactive, and apparent)

2041 (0x07F8)

Reset minimum/maximum of frequency measurement

2042 (0x07F9)

Reset minimum/maximum of thermal image measurements

2043 (0x07FA)

Reset energy measurements

2044 (0x07FB)

Reset energy counter

Pre-Alarms

General Description

The EcoStruxure Power Commission software enables the configuration of the following 2 pre-alarms:

  • long-time protection pre-alarm (PAL Ir)

  • ground-fault protection pre-alarm (PAL Ig)

Each alarm has a corresponding alarm code:

  • PAL Ir = 1013

  • PAL Ig = 1014

Each alarm has a priority level that manages the alarm display on the FDM121 display:

  • no priority = N/A (not affected)

  • low priority = 1. No alarm display on the FDM121 display.

  • medium priority = 2. The FDM121 display LED is steady ON.

  • high priority = 3. The FDM121 display LED blinks and a pop-up screen informs the user that the alarm is active.

Refer to the PowerPacT H-, J-, and L-Frame MicroLogic 5 and 6 Trip Units - User Guide Related Documents for more information regarding the relationship between alarm priority and FDM121 display.

The pre-alarms registers describe the settings of the pre-alarms:

Address

Register

Description

0x19F9–0x1A02

6650–6659

Long-time protection pre-alarm (PAL Ir)

0x1A03–0x1A0C

6660–6669

Ground-fault protection pre-alarm (PAL Ig)

0x1A0D–0x1A16

6670–6679

Reserved

Long-Time Protection Pre-Alarm (PAL Ir)

A read request of 10 registers is necessary to read the long-time protection pre-alarm parameters.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x19F9

6650

R

INT16U

A/E

The MSB gives the activity of the alarm: 0 = On, 1 = Off. The factory setting is 0 (On).

The LSB gives the priority of the alarm: N/A, 1, 2, or 3. The factory setting is 2 (medium priority).

0x19FA

6651

Reserved

0x19FB

6652

R

1

%

INT16

(1)

A/E

% of Ir pick-up value. The factory setting is 90.

0x19FC

6653

Reserved

0x19FD

6654

R

1

s

INT16U

1

A/E

Pick-up time delay (fixed to 1 s)

0x19FE

6655

R

1

%

INT16

(1)

A/E

% of Ir drop-out value. The factory setting is 85.

0x19FF

6656

Reserved

0x1A00

6657

R

1

s

INT16U

1

A/E

Drop-out time delay (fixed to 1 s)

0x1A01–0x1A02

6658– 6659

Reserved

(1) For distribution application, the range is 40–100. For motor application, the range is 10–95.

Ground-Fault Protection Pre-Alarm (PAL Ig)

A read request of 10 registers is necessary to read the ground-fault protection pre-alarm parameters.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x1A03

6660

R

INT16U

A/E

The MSB gives the activity of the alarm: 0 = On, 1 = Off. The factory setting is 0 (On).

The LSB gives the priority of the alarm: N/A, 1, 2, or 3. The factory setting is 2 (medium priority).

0x1A04

6661

Reserved

0x1A05

6662

R

1

%

INT16

40–100

A/E

% of Ig pick-up value. The factory setting is 90.

0x1A06

6663

Reserved

0x1A07

6664

R

1

s

INT16U

1

A/E

Pick-up time delay (fixed to 1 s)

0x1A08

6665

R

1

%

INT16

40–100

A/E

% of Ig drop-out value. The factory setting is 85.

0x1A09

6666

Reserved

0x1A0A

6667

R

1

s

INT16U

1

A/E

Drop-out time delay (fixed to 1 s)

0x1A0B–0x1A0C

6668–6669

Reserved

User-Defined Alarms

General Description

The EcoStruxure Power Commission software enables the configuration of 10 user-defined alarms that can be chosen from a list of 150 predefined alarms.

Each user-defined alarm has a corresponding user-defined alarm number (201–210) and a corresponding alarm code (see next paragraph).

Each alarm has a priority level that manages the alarm display on the FDM121 display:

  • no priority = N/A (not affected)

  • low priority = 1. No alarm display on the FDM121 display.

  • medium priority = 2. The FDM121 display LED is steady ON.

  • high priority = 3. The FDM121 display LED blinks and a pop-up screen informs the user the alarm is active.

Refer to the PowerPacT H-, J-, and L-Frame MicroLogic 5 and 6 Trip Units - User Guide Related Documents for more information regarding the relationship between alarm priority and FDM121 display.

The settings of the 10 user-defined alarms are in the user-defined alarms registers:

Address

Register

Description

0x1A71–0x1A7C

6770–6781

User-defined alarm 201

0x1A7D–0x1A88

6782–6793

User-defined alarm 202

0x1A89–0x1A94

6794–6805

User-defined alarm 203

0x1A95–0x1AA0

6806–6817

User-defined alarm 204

0x1AA1–0x1AAC

6818–6829

User-defined alarm 205

0x1AAD–0x1AB8

6830–6841

User-defined alarm 206

0x1AB9–0x1AC4

6842–6853

User-defined alarm 207

0x1AC5–0x1AD0

6854–6865

User-defined alarm 208

0x1AD1–0x1ADC

6866–6877

User-defined alarm 209

0x1ADD–0x1AE8

6878–6889

User-defined alarm 210

User-Defined Alarm Record

A read request of 12 registers is necessary to read a user-defined alarm record.

The order and the description of the user-defined alarms records are the same as that of user-defined alarm record 1:

User-Defined Alarm 201

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x1A71

6770

R

INT16U

A/E

The MSB gives the activity of the alarm: 0 = On, 1 = Off. The factory setting is 1 (Off).

The LSB gives the priority of the alarm: N/A, 1, 2, or 3. The factory setting is N/A (no priority).

0x1A72

6771

R

INT16U

A/E

Measurement identifier (1)

0x1A73

6772

Reserved

0x1A74

6773

R

1

(2)

INT16

-32767–

+32767

A/E

Threshold pick-up value. The factory setting is 0.

0x1A75

6774

Reserved

0x1A76

6775

R

1

s

INT16U

0–3000

A/E

Pick-up time delay. The factory setting is 0.

0x1A77

6776

R

1

(2)

INT16

-32767–

+32767

A/E

Threshold drop-out value. The factory setting is 0.

0x1A78

6777

Reserved

0x1A79

6778

R

1

s

INT16

0–3000

A/E

Drop-out time delay. The factory setting is 0.

0x1A7A

6779

R

INT16U

0–300

A/E

Operator: 0: ≥, 1: ≤, 2: =, 3: I ≥ I

0x1A7B

6780

R

INT16U

1–1919

Alarm code

0x1A7C

6781

Reserved

(1) The value of the measurement identifier is the register number of the measurement. For example, the measurement identifier of current on phase A (IA) is 1016.

(2) The unit of the threshold depends on the measurement identifier. For example, if the measurement identifier is IA, then the unit is A.

Predefined Alarms Codes

The following table describes the list of predefined alarms and corresponding codes from which the user can choose the 10 user-defined alarms and configure them with the EcoStruxure Power Commission software.

Alarm Code

Alarm Description

1 (0x0000)

Overcurrent instantaneous phase A

2 (0x0001)

Overcurrent instantaneous phase B

3 (0x0002)

Overcurrent instantaneous phase C

4 (0x0003)

Overcurrent instantaneous neutral

5 (0x0004)

Ground-fault current

6 (0x0005)

Undercurrent instantaneous phase A

7 (0x0006)

Undercurrent instantaneous phase B

8 (0x0007)

Undercurrent instantaneous phase C

9 (0x0008)

Overcurrent unbalance phase A

10 (0x0009)

Overcurrent unbalance phase B

11 (0x000A)

Overcurrent unbalance phase C

12 (0x000B)

Overvoltage (phase A to neutral)

13 (0x000C)

Overvoltage (phase B to neutral)

14 (0x000D)

Overvoltage (phase C to neutral)

15 (0x000E)

Undervoltage (phase A to neutral)

16 (0x000F)

Undervoltage (phase B to neutral)

17 (0x0010)

Undervoltage (phase C to neutral)

18 (0x0011)

Overvoltage unbalance (phase A to neutral)

19 (0x0012)

Overvoltage unbalance (phase B to neutral)

20 (0x0013)

Overvoltage unbalance (phase C to neutral)

21 (0x0014)

Over total apparent power

22 (0x0015)

Over total active power

23 (0x0016)

Over total active reverse power

24 (0x0017)

Over total reactive power

25 (0x0018)

Over total reactive reverse power

26 (0x0019)

Under total apparent power

27 (0x001A)

Under total active power

28 (0x001B)

Reserved

29 (0x001C)

Under total reactive power

30 (0x001D)

Reserved

31 (0x001E)

Leading power factor (IEEE)

32 (0x001F)

Reserved

33 (0x001E)

Leading or lagging power factor (IEC)

34 (0x0021)

Lagging power factor (IEEE)

35 (0x0022)

Over total harmonic distortion current phase A

36 (0x0023)

Over total harmonic distortion current phase B

37 (0x0024)

Over total harmonic distortion current phase C

38 (0x0025)

Over total harmonic distortion voltage (phase A to neutral)

39 (0x0026)

Over total harmonic distortion voltage (phase B to neutral)

40 (0x0027)

Over total harmonic distortion voltage (phase C to neutral)

41 (0x0028)

Over total harmonic distortion voltage (phase A B)

42 (0x0029)

Over total harmonic distortion voltage (phase B C)

43 (0x002A)

Over total harmonic distortion voltage (phase C A)

44–53 (0x002B–0x0034)

Reserved

54 (0x0035)

Reserved

55 (0x0036)

Overcurrent (average)

56 (0x0037)

Over maximum current (IA, IB, IC, or neutral)

57 (0x0038)

Undercurrent instantaneous neutral

58–59 (0x0039–0x003A)

Reserved

60 (0x003B)

Undercurrent (average)

61 (0x003C)

Overcurrent demand phase A

62 (0x003D)

Overcurrent demand phase B

63 (0x003E)

Overcurrent demand phase C

64 (0x003F)

Overcurrent demand neutral

65 (0x0040)

Under minimum current (IA, IB, or IC)

66 (0x0041)

Undercurrent demand phase A

67 (0x0042)

Undercurrent demand phase B

68 (0x0043)

Undercurrent demand phase C

69 (0x0044)

Undercurrent demand neutral

70 (0x0045)

Over maximum current unbalance (IA, IB, or IC)

71 (0x0046)

Overvoltage (phase A B)

72 (0x0047)

Overvoltage (phase B C)

73 (0x0048)

Overvoltage (phase C A)

74 (0x0049)

Reserved

75 (0x004A)

Overvoltage (average)

76 (0x004B)

Undervoltage (phase A B)

77 (0x004C)

Undervoltage (phase B C)

78 (0x004D)

Undervoltage (phase C A)

79 (0x004E)

Over maximum voltage

80 (0x004F)

Undervoltage (average)

81 (0x0050)

Under minimum voltage

82 (0x0051)

Over maximum voltage unbalance (phases to neutral)

83–85 (0x0052–0x0054)

Reserved

86 (0x0055)

Overvoltage unbalance (phase A B)

87 (0x0056)

Overvoltage unbalance (phase B C)

88 (0x0057)

Overvoltage unbalance (phase C A)

89 (0x0058)

Over maximum voltage unbalance

90 (0x0059)

Phase sequence

91 (0x005A)

Reserved

92 (0x005B)

Under frequency

93 (0x005C)

Over frequency

94–98 (0x005D–0x0061)

Reserved

99 (0x0062)

Over active power demand

100–120 (0x0063–0x0077)

Reserved

121 (0x0078)

Leading cosϕ (IEEE)

122 (0x0079)

Reserved

123 (0x007A)

Leading or lagging cosϕ (IEC)

124 (0x007B)

Lagging cosϕ (IEEE)

125 (0x007C)

Overcurrent thermal image motor

126 (0x007D)

Undercurrent thermal image motor

127–140 (0x007E–0x008B)

Reserved

141 (0x008C)

Overcurrent maximum demand phase A

142 (0x008D)

Overcurrent maximum demand phase B

143 (0x008E)

Overcurrent maximum demand phase C

144 (0x008F)

Overcurrent maximum demand neutral

145 (0x0090)

Lead

146 (0x0091)

Lag

147 (0x0092)

Quadrant 1

148 (0x0093)

Quadrant 2

149 (0x0094)

Quadrant 3

150 (0x0095)

Quadrant 4

151–255 (0x0096–0x00FE)

Reserved

256 (0x00FF)

Contact wear

Protection Parameters

Long-Time Protection Parameters

A read request of 10 registers is necessary to read the long-time protection parameters.

The long-time protection command (command code = 45192) configures the content of the long-time protection registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x2231

8754

R

INT16U

1–2

A/E

Status: 1 = On, 2 = Inhibit

0x2232

8755

Reserved

0x2233

8756

R-WC

1

A

INT16U

A/E

Ir pick-up value. The Ir range depends on the sensor rating In.

0x2234

8757

Reserved

0x2235

8758

R-WC

1

ms

INT16U

500–

16000

A/E

tr time delay (distribution application)

tr = 500, 1000, 2000, 4000, 8000, 16000 ms

0x2236

8759

R-WC

1

s

INT16U

5–30

E

Motor class (motor application only)

Possible values = 5, 10, 20, 30 s

0x2237

8760

Reserved

0x2238

8761

R-WC

1

INT16U

1–2

E

Cool fan (motor application only)

1 = auto, 2 = motor

0x2239–0x223A

8762–8763

Reserved

Short-Time Protection Parameters

A read request of 10 registers is necessary to read the short-time protection parameters.

The short-time protection command (command code = 45193) configures the content of the short-time protection registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x223B

8764

R

INT16U

1–2

A/E

Status: 1 = On, 2 = Inhibit

0x223C

8765

R-WC

INT16U

0–1

A/E

Type of protection: 0 = I2t On, 1 = I2t Off.

For motor application, tsd = 30 ms and I2t is Off (fixed values).

0x223D

8766

R-WC

10

INT16U

(1)

A/E

Isd coefficient, adjustable in step of 5

0x223E

8767

R

1

A

INT16U

A/E

Isd pick-up value = (Ir) x (Isd coefficient) / 10

0x223F

8768

R-WC

1

ms

INT16U

0–400

A/E

tsd time delay

tsd = 0, 30, 100, 200, 300, 400 ms

If tsd = 0 ms, then I2t must be Off.

0x2240–

0x2244

8769–

8773

Reserved

(1) For distribution application, the range is 15–100. For motor application, the range is 50–130.

Instantaneous Protection Parameters

A read request of 10 registers is necessary to read the instantaneous protection parameters.

The instantaneous protection command (command code = 45194) configures the content of the instantaneous protection registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x2245

8774

R

INT16U

1–2

A/E

Status: 1 = On, 2 = Inhibit

0x2246

8775

Reserved

0x2247

8776

R-WC

10

INT16U

(1)

A/E

Ii coefficient, adjustable in step of 5

0x2248

8777

R

1

A

INT16U

A/E

Ii pick-up value = (In) x (Ii coefficient) / 10

0x2249– 0x224E

8778– 8783

Reserved

(1) The Ii coefficient range depends on the circuit breaker size:

  • for 100–160 A, the range is 15–150.

  • for 250–400 A, the range is 15–120.

  • for 630 A, the range is 15–110.

Ground-Fault Protection Parameters

A read request of 10 registers is necessary to read the ground-fault protection parameters.

The ground-fault protection command (command code = 45195) configures the content of the ground-fault protection registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x224F

8784

R

INT16U

0–2

A/E

Status: 0 = Off, 1 = On, 2 = Inhibit

0x2250

8785

R-WC

INT16U

0–1

A/E

Type of protection: 0 = I2t On, 1 = I2t Off

For motor application, tg = 0 ms and I2t is Off (fixed values).

0x2251

8786

R-WC

100

INT16U

A/E

Ig coefficient, adjustable in step of 5

0x2252

8787

R

1

A

INT16U

A/E

Ig pick-up value = (In) x (Ig coefficient) / 100

If ground-fault protection is set to Off, Ig pick-up value = In.

0x2253

8788

R-WC

1

ms

INT16U

0–400

A/E

tg time delay

tg = 0, 100, 200, 300, 400 ms.

If tg = 0 ms, then I2t must be Off.

0x2254–

0x2258

8789–

8793

Reserved

Jam Protection Parameters

A read request of 4 registers is necessary to read the jam protection parameters.

The jam protection is available for motor application only. The jam protection command (command code = 45448) configures the content of the jam protection registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x22C3

8900

R-WC

INT16U

0–1

E

Status: 0 = Off, 1 = On

0x22C4

8901

R-WC

10

INT16U

10–80

E

Ijam coefficient, adjustable in step of 1

0x22C5

8902

R

1

A

INT16U

E

Ijam pick-up value = (Ir) x (Ijam coefficient) / 10

0x22C6

8903

R-WC

1

s

INT16U

1–30

E

tjam time delay

Unbalance Protection Parameters

A read request of 4 registers is necessary to read the unbalance protection parameters.

The unbalance protection is available for motor application only. The unbalance protection command (command code = 45450) configures the content of the unbalance protection registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x22C7

8904

R

INT16U

0–2

E

Status: 0 = Off, 1 = On, 2 = Inhibit

0x22C8

8905

R-WC

1

%

INT16U

10–40

E

Iunbal coefficient

0x22C9

8906

R-WC

1

s

INT16U

1–10

E

tunbal time delay

0x22CA

8907

Reserved

Underload Protection Parameters

A read request of 4 registers is necessary to read the underload protection parameters.

The underload protection is available for motor application only. The underload protection command (command code = 45449) configures the content of the underload protection registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x22CB

8908

R-WC

INT16U

0–1

E

Status: 0 = Off, 1 = On

0x22CC

8909

R-WC

100

INT16U

30–90

E

underload coefficient, adjustable in step of 1

0x22CD

8910

R

1

A

INT16U

E

underload pick-up value = (Ir) x (Iunderload) / 100

0x22CE

8911

R-WC

1

s

INT16U

1–200

E

underload time delay

Long-Start Protection Parameters

A read request of 4 registers is necessary to read the long-start protection parameters.

The long-start protection is available for motor application only. The long-start protection command (command code = 45451) configures the content of the long-start protection registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x22CF

8912

R-WC

INT16U

0–1

E

Status: 0 = Off, 1 = On

0x22D0

8913

R-WC

10

INT16U

10–80

E

longstart coefficient, adjustable in step of 1

0x22D1

8914

R

1

A

INT16U

E

longstart pick-up value = (Ir) x (Ilongstart coefficient) / 10

0x22D2

8915

R-WC

1

s

INT16U

1–200

E

longstart time delay

Neutral Protection Parameters

The neutral protection is only available when system type in register 3314 is 30 or 41 System Type.

A read request of 4 registers is necessary to read the neutral protection parameters.

The neutral protection command (command code = 45197) configures the content of the neutral protection registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x22D3

8916

R

INT16U

0–2

A/E

Status: 0 = Off, 1 = On, 2 = Inhibit (1)

0x22D4

8917

R-WC

INT16U

0–3

A/E

Neutral coefficient pickup value

0 = Off

1 = 0.5

2 = 1.0

3 = OSN

0x22D5

8918

R

1

A

INT16U

0–32766

A/E

Ir pick-up value

0x22D6

8919

R

1

A

INT16U

0–32766

A/E

Isd pick-up value

(1) For 40 A IEC and 60 A UL circuit breakers, the user cannot set up the neutral coefficient pickup value to 0.5.

Thermal Memory Inhibit Parameter

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x22E1

8930

R

INT16U

1–2

A/E

Status: 1 = On, 2 = Inhibit

Configuration of the SDx Module

Output 1

A read request of 3 registers is necessary to read the output 1 parameters.

The user can check the status and the validity of output 1 at register 8857.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x2648

9801

R

1

INT16U

0–4

A/E

Output mode

0 = normal mode

1 = latched mode

2 = time delayed mode

3 = closed forced mode

4 = open forced mode

0x2649

9802

R

1

s

INT16U

1–360

A/E

Delay (if the output mode is set to 2).

The factory setting is 1 s.

0x264A

9803

R

1

INT16U

0–65535

A/E

Alarm identifier (201–210, 1013, 1014, 1015).

The alarm identifier is set to 0 if there is no alarm.

Output 2

A read request of 3 registers is necessary to read the output 2 parameters.

The user can check the status and the validity of output 2 at register 8857.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x264F

9808

R

1

INT16U

0–4

A/E

Output mode

0 = normal mode

1 = latched mode

2 = time delayed mode

3 = closed forced mode

4 = open forced mode

0x2650

9809

R

1

s

INT16U

1–360

A/E

Delay (if the output mode is set to 2).

The factory setting is 1 s.

0x2651

9810

R

1

INT16U

0–65535

A/E

Alarm identifier (201–210, 1013, 1014, 1015).

The alarm identifier is set to 0 if there is no alarm.

Measurement Parameters

System Type

The setup ENVT (External Neutral Voltage Tap) presence command (command code = 46472) configures the content of the system type register.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0CF1

3314

R-WC

INT16U

30–41

A/E

System type

Determining system type:

If...

Then...

Result

the system type is 3-pole circuit breaker with external neutral current transformer and without external neutral voltage tap

system type = 30

  • Measurements of the phase-to-phase voltages are available.

  • Measurements of the phase-to-neutral voltages are not available.

  • Measurement of the neutral current is available.

  • 3 wattmeters method is not possible.

the system type is 3-pole circuit breaker without external neutral current transformer and without external neutral voltage tap

system type = 31

  • Measurements of the phase-to-phase voltages are available.

  • Measurements of the phase-to-neutral voltages are not available.

  • Measurement of the neutral current is not available.

  • 3 wattmeters method is not possible.

the system type is 3-pole circuit breaker without external neutral current transformer and with external neutral voltage tap

system type = 40

  • Measurements of the phase-to-phase voltages are available.

  • Measurements of the phase-to-neutral voltages are available.

  • Measurement of the neutral current is not available.

  • 3 wattmeters method is possible.

the system type is 3-pole circuit breaker with external neutral current transformer and external neutral voltage tap, or if the system type is 4-pole circuit breaker

system type = 41

  • Measurements of the phase-to-phase voltages are available.

  • Measurements of the phase-to-neutral voltages are available.

  • Measurement of the neutral current is available.

  • 3 wattmeters method is possible.

Quadrant Total

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x08C1

2242

R

INT16U

1–4

E

Quadrant total

0x08C2

2243

R

INT16U

0–1

E

0 = lead

1 = lag

Power Flow Sign

The power flow sign command (command code = 47240) configures the content of the power flow sign register.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0CF3

3316

R-WC

INT16U

0–1

E

Power flow sign:

0 = the active power flows from upstream (top) to downstream (bottom) (factory setting).

1 = the active power flows from downstream (bottom) to upstream (top).

Power Factor Sign

The power factor sign configuration command (command code = 47241) configures the content of the power factor sign register.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0CF5

3318

R-WC

INT16U

0–2

E

Sign convention for the power factor and the fundamental power factor (cosϕ):

0 = IEC convention

2 = IEEE convention (factory setting)

Energy Accumulation Mode

The energy accumulation mode configuration command (command code = 47242) configures the content of the energy accumulation mode register.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0CFB

3324

R-WC

INT16U

0–1

E

Energy accumulation mode:

0 = absolute accumulation (factory setting)

Ep = EpIn + EpOut

Eq = EqIn + EqOut

1 = signed accumulation

Ep = EpIn – EpOut

Eq = EqIn – EqOut

Demand Time

The current demand configuration command (command code 47243) configures the content of register 3352.

The power demand configuration command (command code 47244) configures the content of registers 3354 and 3355.

Refer to the PowerPacT H-, J-, and L-Frame MicroLogic 5 and 6 Trip Units - User Guide Related Documents for more information regarding the demand calculation method.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0D17

3352

R-WC

min

INT16U

5–60

E

Duration of the current demand calculation window, adjustable in steps of 1 minute.

The factory setting is 15 minutes.

0x0D19

3354

R-WC

INT16U

0–5

E

Power demand calculation method (window type):

0 = sliding (factory setting)

2 = block

5 = synchronized to communication

0x0D1A

3355

R-WC

min

INT16U

5–60

E

Duration of the power demand calculation window, adjustable in steps of 1 minute.

The factory setting is 15 minutes.

Nominal Voltage

The setup nominal voltage Vn display command (command code = 47245) configures the content of the nominal voltage register.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x258F

9616

R-WC

1

V

INT16U

0–65535

A/E

Nominal voltage Vn.

Factory setting = 400 V

Time-Stamped Information

General Description

The time-stamped information enables the user to know all the dates relative to important information such as previous protection settings and minimum/maximum values of currents, voltages, and system frequency.

The time-stamped information table describes:

  • the previous protection setup parameters and corresponding dates

  • the minimum and maximum values of voltage measurements and corresponding dates

  • the maximum values of current measurements and corresponding dates

  • the minimum and maximum system frequencies and corresponding dates

  • the peak demand of current and power and corresponding dates

A read request of 100 registers is necessary to read the time-stamped previous protection registers (29600–29699).

Previous Long-Time Protection Setup

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x739F

29600

R

1

A

INT16U

A/E

Previous Ir pick-up value. The Ir range depends on the sensor rating In.

0x73A0–

0x73A2

29601–

29603

R

ULP DATE

A/E

Date and time of the previous setup.

0x73A3

29604

R

1

ms

INT16U

500– 16000

A/E

Previous tr time delay (distribution application)

tr = 500, 1000, 2000, 4000, 8000, 16000 ms

0x73A4–

0x73A6

29605–

29607

R

ULP DATE

A/E

Date and time of the previous setup.

0x73A7

29608

R

1

INT16U

5–30

A/E

Motor class (motor application only)

Possible values = 5, 10, 20, 30 s

0x73A8–

0x73AA

29609–

29611

R

ULP DATE

A/E

Date and time of the previous setup.

0x73AB

29612

R

INT16U

1–2

A/E

Previous cool fan setup (motor application only)

1 = auto, 2 =motor

0x73AC–

0x73AE

29613–

29615

R

ULP DATE

A/E

Date and time of the previous setup.

Previous Short-Time Protection Setup

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x73AF

29616

R

10

INT16U

(1)

A/E

Previous Isd coefficient pick-up value

0x73B0–

0x73B2

29617–

29619

R

ULP DATE

A/E

Date and time of the previous setup.

0x73B3

29620

R

1

ms

INT16U

0–400

A/E

Previous tsd time delay

tsd = 0, 100, 200, 300, 400 ms

If tsd = 0 ms, then I2t must be Off.

0x73B4–

0x73B6

29621–

29623

R

ULP DATE

A/E

Date and time of the previous setup.

0x73B7

29624

R

INT16U

0–1

A/E

Previous type of protection: 0 = I2t On, 1 = I2t Off

0x73B8–

0x73BA

29625–

29627

R

ULP DATE

A/E

Date and time of the previous setup.

(1) The Isd coefficient range depends on:

  • the application:

    • for distribution application, the range is 15–100, adjustable in step of 5.

    • for motor application, the range is 50–130, adjustable in step of 5.

  • the MicroLogic trip unit rotary switch if it exists.

Previous Instantaneous Protection Setup

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x73BB

29628

R

10

INT16U

(1)

A/E

Previous Ii coefficient pick-up value

0x73BC–

0x73BE

29629–

29631

R

ULP DATE

A/E

Date and time of the previous setup.

(1) The Ii coefficient range depends on the circuit breaker size:

  • for 100–160 A, the range is 15–150.

  • for 250–400 A, the range is 15–120.

  • for 630 A, the range is 15–110.

Previous Ground-Fault Protection Setup

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x73BF

29632

R

100

ms

INT16U

(1)

A/E

Previous Ig coefficient pick-up value.

0x73C0–

0x73C2

29633–

29635

R

ULP DATE

A/E

Date and time of the previous setup.

0x73C3

29636

R

1

ms

INT16U

0–400

A/E

Previous tg time delay

tg = 0, 100, 200, 300, 400 ms

0x73C4–

0x73C6

29637–

29639

R

ULP DATE

A/E

Date and time of the previous setup.

0x73C7

29640

R

INT16U

0–1

A/E

Previous type of protection: 0 = I2t On, 1 = I2t Off

0x73C8–

0x73CA

29641–

29643

R

ULP DATE

A/E

Date and time of the previous setup.

(1) The Ig coefficient range depends on the sensor rating In and the MicroLogic trip unit rotary switch if it exists.

For example, 0 (protection off) or 0.40 In to In in step of 0.05.

Previous Jam Protection Setup

The jam protection is available for motor application only.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x73D3

29652

R

INT16U

0–2

E

Previous setup status: 0 = Off, 1 = On

0x73D4–

0x73D6

29653–

29655

R

ULP DATE

E

Date and time of the previous setup.

0x73D7

29656

R

10

INT16U

10–80

E

Previous jam coefficient pick-up value

0x73D8–

0x73DA

29657–

29659

R

ULP DATE

E

Date and time of the previous setup.

0x73DB

29660

R

1

s

INT16U

1–30

E

Previous jam time delay

0x73DC–

0x73DE

29661–

29663

R

ULP DATE

E

Date and time of the previous setup.

Previous Unbalance Protection Setup

The unbalance protection is available for motor application only.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x73DF

29664

R

1

%

INT16U

10–40

E

Previous unbalance coefficient pick-up value

0x73E0–

0x73E2

29665–

29667

R

ULP DATE

E

Date and time of the previous setup.

0x73E3

29668

R

1

s

INT16U

1–10

E

Previous tunbal time delay

0x73E4–

0x73E6

29669–

29671

R

ULP DATE

E

Date and time of the previous setup.

Previous Underload Protection Setup

The underload protection is available for motor application only.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x73E7

29672

R

INT16U

0–2

E

Previous setup status: 0 = Off, 1 = On

0x73E8–

0x73EA

29673–

29675

R

ULP DATE

E

Date and time of the previous setup.

0x73EB

29676

R

100

INT16U

30–90

E

Previous underload coefficient pick-up value

0x73EC–

0x73EE

29677–

29679

R

ULP DATE

E

Date and time of the previous setup.

0x73EF

29680

R

1

s

INT16U

1–200

E

Previous underload time delay

0x73F0–

0x73F2

29681–

29683

R

ULP DATE

E

Date and time of the previous setup.

Previous Long-Start Protection Setup

The long-start protection is available for motor application only.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x73F3

29684

R

INT16U

0–2

E

Previous setup status: 0 = Off, 1 = On

0x73F4–

0x73F6

29685–

29687

R

ULP DATE

E

Date and time of the previous setup.

0x73F7

29688

R

10

INT16U

10–50

E

Previous longstart coefficient pick-up value

0x73F8–

0x73FA

29689–

29691

R

ULP DATE

E

Date and time of the previous setup.

0x73FB

29692

R

1

s

INT16U

1–30

E

Previous longstart time delay

0x73FC–

0x73FE

29693–

29695

R

ULP DATE

E

Date and time of the previous setup.

Previous Neutral Protection Setup

The neutral protection is only available when system type in register 3314 is 30 or 41 System Type.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x73FF

29696

R

INT16U

0–3

A/E

Previous neutral coefficient pick-up value:

0 = Off

1 = 0.5

2 = 1.0

3 = OSN

0x7400–

0x7402

29697–

29699

R

ULP DATE

A/E

Date and time of the previous setup.

Minimum/Maximum VAB Voltage Measurements

A read request of 48 registers is necessary to read the time-stamped minimum/maximum values of voltage, current, and frequency registers (29780–29827).

Register = 0 if voltage < 25 V.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7453

29780

R

1

V

INT16U

0–850

E

Minimum of RMS phase-to-phase voltage VAB

0x7454–

0x7456

29781–

29783

R

ULP DATE

E

Date and time.

0x7457

29784

R

1

V

INT16U

0–850

E

Maximum of RMS phase-to-phase voltage VAB

0x7458–

0x745A

29785–

29787

R

ULP DATE

E

Date and time.

Minimum/Maximum VBC Voltage Measurements

Register = 0 if voltage < 25 V.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x745B

29788

R

1

V

INT16U

0–850

E

Minimum of RMS phase-to-phase voltage VBC

0x745C–

0x745E

29789–

29791

R

ULP DATE

E

Date and time.

0x745F

29792

R

1

V

INT16U

0–850

E

Maximum of RMS phase-to-phase voltage VBC

0x7460–

0x7462

29793–

29795

R

ULP DATE

E

Date and time.

Minimum/Maximum VCA Voltage Measurements

Register = 0 if voltage < 25 V.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7463

29796

R

1

V

INT16U

0–850

E

Minimum of RMS phase-to-phase voltage VCA

0x7464–

0x7466

29797–

29799

R

ULP DATE

E

Date and time.

0x7467

29800

R

1

V

INT16U

0–850

E

Maximum of RMS phase-to-phase voltage VCA

0x7468–

0x746A

29801–

29803

R

ULP DATE

E

Date and time.

Maximum IA Current Measurement

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x746B

29804

R

1

A

INT16U

0–20xIn

A/E

Maximum of RMS current on phase A: IA

0x746C–

0x746E

29805–

29807

R

ULP DATE

A/E

Date and time.

Maximum IB Current Measurement

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x746F

29808

R

1

A

INT16U

0–20xIn

A/E

Maximum of RMS current on phase B: IB

0x7470–

0x7472

29809–

29811

R

ULP DATE

A/E

Date and time.

Maximum IC Current Measurement

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7473

29812

R

1

A

INT16U

0–20xIn

A/E

Maximum of RMS current on phase C: IC

0x7474–

0x7476

29813–

29815

R

ULP DATE

A/E

Date and time.

Maximum IN Current Measurement

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7477

29816

R

1

A

INT16U

0–20xIn

A/E

Maximum of RMS current on neutral: IN

0x7478–

0x747A

29817–

29819

R

ULP DATE

A/E

Date and time.

Minimum System Frequency

When the MicroLogic trip unit cannot calculate the frequency, it returns Not Evaluated = 32768 (0x8000).

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x747B

29820

R

10

Hz

INT16U

150–4400

E

Minimum of system frequency

0x747C–

0x747E

29821–

29823

R

ULP DATE

E

Date and time.

Maximum System Frequency

When the MicroLogic trip unit cannot calculate the frequency, it returns Not Evaluated = 32768 (0x8000).

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x747F

29824

R

10

Hz

INT16U

150–4400

E

Maximum of system frequency

0x7480–

0x7482

29825–

29827

R

ULP DATE

E

Date and time.

IA Peak Demand Measurement

A read request of 20 registers is necessary to read the time-stamped peak demand of current and power (29828–29847).

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7483

29828

R

1

A

INT16U

0–20xIn

E

IA peak demand

0x7484–

0x7486

29829–

29831

R

ULP DATE

E

Date and time.

IB Peak Demand Measurement

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7487

29832

R

1

A

INT16U

0–20xIn

E

IB peak demand

0x7488–

0x748A

29833–

29835

R

ULP DATE

E

Date and time.

IC Peak Demand Measurement

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x748B

29836

R

1

A

INT16U

0–20xIn

E

IC peak demand

0x748C–

0x748E

29837–

29839

R

ULP DATE

E

Date and time.

IN Peak Demand Measurement

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x748F

29840

R

1

A

INT16U

0–20xIn

E

IN peak demand

0x7490–

0x7492

29841–

29843

R

ULP DATE

E

Date and time.

P Peak Demand Measurement

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7493

29844

R

10

kW

INT16

-30000–

+30000

E

P peak demand

0x7494–

0x7496

29845–

29847

R

ULP DATE

E

Date and time.

Maintenance Indicators

Time of Use Counter

The time of use counter reports the time of use of the circuit breaker. The time of use is written in the EEPROM every hour. If the time of use counter reaches the maximum value 4 294 967 295 and a new time of use event occurs, then the counter is reset to 0.

A read request of 2 registers is necessary to read the time of use counter.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x749A–0x749B

29851–29852

R

1

Hour

INT32U

0–4 294 967 295

A/E

Time of use counter

Rate of Wear Counter

The rate of wear counter reports the percentage of the circuit breaker contact use.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x749C

29853

R

1

%

INT16U

0–32766

A/E

Rate of wear contact

0% = The circuit breaker contact is new.

> 100% = The circuit breaker contact must be changed.

Boot Counter

The boot counter reports the number of cold starts (power-up) and the number of warm starts (software reset of the MicroLogic trip unit).

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x749D

29854

R

1

INT16U

0–32766

A/E

Boot counter

EEPROM Writing Counter

The EEPROM writing counter reports the number of storages of the energy measurement in the EEPROM. The energy measurement is written in the EEPROM every hour. If the EEPROM writing counter reaches the maximum value 4 294 967 295 and a new EEPROM writing event occurs, then the EEPROM writing counter is reset to 0.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x749E–

0x749F

29855–

29856

R

1

INT32U

0–4 294 967 295

A/E

Counter of EEPROM writing

Load Profile Counters

The load profile counters report the number of hours for each range of current in the MicroLogic trip unit. If the load profile counters reach the maximum value 4 294 967 295 and a new load profile event occurs, then the load profile counters are reset to 0.

A read request of 8 registers is necessary to read the load profile counters.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x74B7–

0x74B8

29880–

29881

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours current was 0‑49% of nominal range

0x74B9–

0x74BA

29882–

29883

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours current was 50‑79% of nominal range

0x74BB–

0x74BC

29884–

29885

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours current was 80‑89% of nominal range

0x74BD–

0x74BE

29886–

29887

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours current was 90‑100% of nominal range

Temperature Profile Counters

The temperature profile counters report the number of hours for each range of temperature in the MicroLogic trip unit. If the temperature profile counters reach the maximum value 4 294 967 295 and a new temperature profile event occurs, then the temperature profile counters are reset to 0.

A read request of 12 registers is necessary to read the temperature profile counters.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x74C1–

0x74C2

29890–

29891

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours temperature was < -30 °C (-22 °F)

0x74C3–

0x74C4

29892–

29893

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours temperature was in the -30–+59 °C range (22–1 38.2 °F)

0x74C5–

0x74C6

29894–

29895

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours temperature was in the +60–+74 °C range (140–165.2 °F)

0x74C7–

0x74C8

29896–

29897

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours temperature was in the +75–+89 °C range (167–192.2 °F)

0x74C9–

0x74CA

29898–

29899

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours temperature was in the +90–+99 °C range (194–210.2 °F)

0x74CB–

0x74CC

29900–

29901

R

1

Hour

INT32U

0–4 294 967 295

A/E

Hours temperature was > +100 °C (212 °F)

Protection Trips Counters

The protection trips counters report the number of protection trips for each type of protection: long-time, short-time, instantaneous, ground-fault, jam, unbalance, long-start, and underload protections.

The protection trips counters stop incrementing when they reach the maximum value 10000.

A read request of 9 registers is necessary to read the protection trips counters.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x74D5

29910

R

1

INT16U

0–10000

A/E

Number of long-time protection trips

0x74D6

29911

R

1

INT16U

0–10000

A/E

Number of short-time protection trips

0x74D7

29912

R

1

INT16U

0–10000

A/E

Number of instantaneous protection trips

0x74D8

29913

R

1

INT16U

0–10000

A/E

Number of ground-fault protection trips

0x74D9

29914

R

1

INT16U

0–10000

E

Reserved

0x74DA

29915

R

1

INT16U

0–10000

A/E

Number of jam protection trips

0x74DB

29916

R

1

INT16U

0–10000

A/E

Number of unbalance protection trips

0x74DC

29917

R

1

INT16U

0–10000

A/E

Number of long-start protection trips

0x74DD

29918

R

1

INT16U

0–10000

A/E

Number of underload protection trips

Alarms Counters

The alarms counters report the number of occurrences of the alarms. When an alarm is configured, the associated counter is set to 0. The alarm counters stop incrementing when they reach the maximum value 10000.

A read request of 13 registers is necessary to read the alarms counters.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x74F3

29940

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 201

0x74F4

29941

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 202

0x74F5

29942

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 203

0x74F6

29943

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 204

0x74F7

29944

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 205

0x74F8

29945

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 206

0x74F9

29946

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 207

0x74FA

29947

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 208

0x74FB

29948

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 209

0x74FC

29949

R

1

INT16U

0–10000

A/E

Counter of user-defined alarm 210

0x74FD

29950

R

1

INT16U

0–10000

A/E

Counter of pre-alarm Ir

0x74FE

29951

R

1

INT16U

0–10000

A/E

Counter of pre-alarm Ig

0x74FF

29952

R

1

INT16U

0–10000

A/E

Counter of pre-alarm IΔn

Maintenance Operation Counters

The maintenance operation counters report the number of some maintenance operations. The maintenance operation counters stop incrementing when they reach the maximum value 10000.

A read request of 7 registers is necessary to read the maintenance operation counters.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x751B

29980

R

1

INT16U

0–10000

A/E

Counter of MicroLogic trip unit locking pad activation

0x751C

29981

R

1

INT16U

0–10000

A/E

Counter of connections of a test kit

0x751D

29982

R

1

INT16U

0–10000

A/E

Counter of ground-fault test operation (using MicroLogic keypad only)

0x751E

29983

R

1

INT16U

0–10000

E

Reserved

0x751F

29984

R

1

INT16U

0–10000

A/E

Counter of ZSI (Zone Selective Interlocking) test operation

0x7520

29985

R

1

INT16U

0–10000

A/E

Counter of numerical injection test operation

0x7521

29986

R

1

INT16U

0–10000

A/E

Counter of reset Firmware command

Miscellaneous

Current Date and Time

A read request of 3 registers is necessary to read the current date.

The set absolute time command (command code 769) configures the content of the current date registers.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x0BB7–

0x0BB9

3000–

3002

R-WC

ULP DATE

A/E

Current date and time

Temperature

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x2292

8851

R

1

°C

INT16

-30– +120

A/E

Temperature of the MicroLogic trip unit

Time Remaining Until Long-Time Tripping

Time remaining until long-time tripping is evaluated every second. If another protection is tripped, then time remaining until long-time tripping continues to be evaluated.

Time remaining until long-time tripping = 32768 (0x8000) if

  • long-time protection is already tripped, or

  • time remaining until long-time tripping is below 1 s, or

  • no default is detected by long-time protection.

If time remaining until long-time tripping is > 7200 s, then time remaining until long-time tripping = 7200 s.

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x22A0

8865

R

1

s

INT16U

1–7200

A/E

Time remaining until long-time tripping

Phase Rotation

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x22A7

8872

R

1

INT16U

0–1

E

0 = ABC phase sequence

1 = ACB phase sequence

Failure Status

Address

Register

RW

X

Unit

Type

Range

A/E

Bit

Description

0x72CD

29390

R

INT16U

A/E

Failure status

A/E

0

Reserved

A/E

1

STOP (internal failure)

0 = No internal failure

1 = Internal failure

A/E

2

ERROR (internal failure)

0 = No internal failure

1 = Internal failure

A/E

3–15

Reserved

NOTE: In the case of a STOP event, it is mandatory to replace the MicroLogic trip unit. In the case of an ERROR event, it is advised to replace the MicroLogic trip unit (the core protection functions still work but it is preferable to replace the MicroLogic trip unit).

MicroLogic Trip Unit Rotary Switches

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7525

29990

R

1

INT16U

1–9

A/E

Position of MicroLogic trip unit rotary switch 1 (Ir)

0x7526

29991

R

1

INT16U

1–9

A/E

Position of MicroLogic trip unit rotary switch 2 (Isd, Ig/IΔn)

MicroLogic Trip Unit Locking Pad Status

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7527

29992

R

1

INT16U

0–1

A/E

0 = MicroLogic trip unit locking pad open

1 = MicroLogic trip unit locking pad closed

Auxiliary 24 Vdc Power Supply

Address

Register

RW

X

Unit

Type

Range

A/E

Description

0x7528

29993

R

1

INT16U

0–1

A/E

0 = auxiliary 24 Vdc power supply is not present.

1 = auxiliary 24 Vdc power supply is present.

MicroLogic Trip Unit LED

Address

Register

RW

X

Unit

Type

Range

A/E

Bit

Description

0x7534

30005

R

INT16U

A/E

MicroLogic trip unit LED

A/E

0

Ready LED

0 = not ready (LED is not blinking).

1 = ready (LED is blinking).

A/E

1

Pre-alarm LED (distribution application only)

0 = pre-alarm is not active (LED is steady off).

1 = pre-alarm is active (LED is steady on).

A/E

2

Overload LED

0 = overload is not active (LED is steady off).

1 = overload is active (LED is steady on).

A/E

3–15

Reserved

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?