Short-Circuit Current Ratings

Short-Circuit Current Ratings with Combination of Enclosed Power Distribution Blocks and Circuit Breakers

Catalog Number

Wire Type (Class)

Suitable Conductors kcmil/AWG (mm2) CU

Overcurrent Protection Circuit Breaker Required

SCCR, RMS Sym. Amperes

Volts Max.

Line

Load

Type

Maximum Amperes

NSYEBAD11611

B, C

4–2 (25–35)

10–2 (6–35)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

12–2 (4–35)

12–2 (4–35)

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

12–2 (4–35)

12–2 (4–35)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

 

NSYEBAD11614

B, C

4–2 (25–35)

10 (6)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

10–2 (6–35)

10 (6)

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

12–2 (4–35)

12–10 (4–6)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

 

NSYEBAD12611

B, C

4–3/0 (25–95)

8–3/0 (10–95)

JDL36250

250

18 kA

480

NSYEBAP12611

JGL36250

250

35 kA

NSYEBCD12611

JJL36250

250

65 kA

NSYEBCP12611

JLL36250

250

65 kA

 

NSYEBAD12614

B, C

4–3/0 (25–95)

10–2 (6–35)

JDL36250

250

18 kA

480

NSYEBAP12614

JGL36250

250

35 kA

NSYEBCD12614

JJL36250

250

65 kA

NSYEBCP12614

JLL36250

250

65 kA

Enclosed Power Distribution Blocks Short-Circuit Current Ratings with Fuses

Catalog Number

Wire Type (Class)

Suitable Copper Conductors Range AWG (mm2)

Fuse Type / Amperage

SCCR

Line

Load

J

T

RK1

RK5

G

CC

NSYEBAD11611

B, C

14–2 (2.5–35)

14–2 (2.5–35)

175

225

100

100 kA

G, H, I, K

14–4 (2.5–25)

14–4 (2.5–25)

175

225

100

100 kA

*

14–2 (2.5–35)

14–2 (2.5–35)

10 kA

 

NSYEBAD11614

B, C

10–2 (6–35)

14–10 (2.5–6)

125

200

100

65 kA

G, H, I, K

10–4 (6–25)

14–10 (2.5–6)

125

200

100

65 kA

*

14–2 (2.5–35)

14–10 (2.5–6)

10 kA

 

NSYEBAD12611

NSYEBAP12611

NSYEBCD12611

NSYEBCP12611

B, C

8–3/0
(10–95)

8–3/0
(10–95)

225

225

200

60

60

30

100 kA

G, H, I

8–2/0
(10–70)

8–2/0
(10–70)

300

300

200

100

60

30

100 kA

*

14–3/0
(2.5–95)

14–3/0
(2.5–95)

10 kA

 

NSYEBAD12614

NSYEBAP12614

NSYEBCD12614

NSYEBCP12614

B, C

8–3/0 (10–95)

8–2 (10–35)

225

225

200

60

60

30

100 kA

B, C

8–3/0 (10–95)

12–8 (4–10)

100

110

100

30

60

30

100 kA

G, H, I

8–2/0 (10–70)

8–4 (10–25)

225

225

200

60

60

30

100 kA

G, H, I

8–2/0 (10–70)

12–8 (4–10)

100

110

100

30

60

30

100 kA

*

14–3/0
(2.5–95)

14–2 (2.5–35)

10 kA

 

NSYEBAD13618

NSYEBCD13618

*

6–400 (16–202.7)
and
14–3/0 (2.5–95)

14–2 (2.5–35)

10 kA

 

NSYEBAP13618

NSYEBCP13618

B, C

3/0–400
(95–202.7)

8–2 (10–35)

400

400

400

200

60

30

100 kA

B, C

6–400
(16–202.7)

10–2 (6–35)

200

200

200

100

60

30

100 kA

G, H, I

6–400
(16–202.7)

10–2 (6–35)

300

300

200

100

60

30

100 kA

*

6–400 (16–202.7)
and
14–3/0 (2.5–95)

14–2 (2.5–35)

10 kA

 

NSYEBAD25622

NSYEBCD25622

*

6–250
(16–126.7)

6–250 (16–126.7)

10 kA

 

NSYEBAP25622

NSYEBCP25622

B, C

1/0–250
(50–126.7)

1/0–250
(50–126.7)

600

600

50 kA

B, C

1/0–250
(50–126.7)

1/0–250
(50–126.7)

400

400

400

200

60

30

100 kA

B, C

6–250
(16–126.7)

6–250
(16–126.7)

400

400

400

100

60

30

100 kA

G, H, I

1/0–250
(50–126.7)

1/0–250
(50–126.7)

300

300

200

100

60

30

100 kA

*

6–250
(16–126.7)

6–250
(16–126.7)

10 kA

 

NSYEBAP27622

B, C

4–500 (25–240)

4–500 (25–240)

600

600

600

200

60

30

100 kA

G, H, I

2–350 (35–185)

2–350 (35–185)

600

600

600

200

60

30

100 kA

*

4–500 (25–240)

4–500 (25–240)

10 kA

 

NSYEBAP27628

B, C

250–500
(126.7–240)

4–2/0 (25–70)

600

600

400

200

60

30

100 kA

NSYEBCP27628

B, C

250–500
(126.7–240)

4–2/0 (25–70)

600

600

600

200

60

30

100 kA

NSYEBAP27628

NSYEBCP27628

B, C

4–500
(25–240)

10–2/0 (6–70)

350

350

200

100

60

30

100 kA

G, H, I

250–350
(126.7–185)

4–1 (25–50)

600

600

600

200

60

30

100 kA

G, H, I

4–350
(25–185)

8–1 (10–50)

350

350

200

100

60

30

100 kA

*

4–500
(25–240)

10–2/0 (6–70)

10 kA

9080LBA and 9080LBC Power Distribution Blocks Short-Circuit Current Ratings with Circuit Breakers

Catalog Number

Suitable Conductors MCM/AWG (mm2) Cu

Overcurrent Protection Circuit Breaker Required

SCCR, RMS Sym. Amperes

Volts Max.

Line

Load

Type

Max A

9080LBA161101

9080LBA361101

6–2 (16–35)

6–2 (16–35)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

10–8 (6–10)

10–8 (6–10)

HDL36100

100

18 kA

HGL36100

100

35 kA

HJL36100

100

65 kA

HLL36100

100

65 kA

 

9080LBA161104

9080LBA261104

9080LBA361104

6–2 (16–35)

12–10 (4–6)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

10–8 (6–10)

12–14 (4–2.5)

HDL36100

100

18 kA

HGL36100

100

35 kA

HJL36100

100

65 kA

HLL36100

100

65 kA

 

9080LBA162104L

9080LBA262104L

9080LBA362104L

14–2/0 (2.5–70)

14–4 (2.5–25)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

HJL36150

150

25 kA

600

HLL36150

150

35 kA

HLL36150

150

50 kA

JJL36250

250

25 kA

JLL36250

250

35 kA

JLL36250

250

50 kA

 

9080LBC162104L

9080LBC262104L

9080LBC362104L

14–2/0 (2.5–70)

14–4 (2.5–25)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

HJL36150

150

25 kA

600

HLL36150

150

35 kA

HLL36150

150

50 kA

JJL36250

250

25 kA

JLL36250

250

35 kA

JLL36250

250

50 kA

 

9080LBA162101L

9080LBA262101L

9080LBA362101L

14–2/0 (2.5–70)

14–2/0 (2.5–70)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

HJL36150

150

25 kA

600

HLL36150

150

35 kA

HLL36150

150

50 kA

JJL36250

250

25 kA

JLL36250

250

35 kA

JLL36250

250

50 kA

 

9080LBC162101L

9080LBC362101L

14–2/0 (2.5–70)

14–2/0 (2.5–70)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

14–2 (2.5–35)

14–2 (2.5–35)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

14–2/0 (2.5–70)

14–2/0 (2.5–70)

HJL36150

150

25 kA

600

HLL36150

150

35 kA

HLL36150

150

50 kA

JJL36250

250

25 kA

JLL36250

250

35 kA

JLL36250

250

50 kA

 

9080LBA163106L

9080LBA263106L

9080LBA363106L

6–250 (16–126.7)

14–2 (2.5–35)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

6–2/0 (16–70)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

6–400 (16–202.7)

LJL36600

600

65 kA

LLL36600

600

65 kA

6–250 (16–126.7)

JJL36250

250

25 kA

600

6–400 (16–202.7)

LJL36600

600

25 kA

6–250 (16–126.7)

JLL36250

250

50 kA

6–400 (16–202.7)

LLL36600

600

50 kA

 

9080LBA163206L

9080LBA263206L

9080LBA363206L

14–2/0 (2.5–70)

14–4 (2.5–25)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

HJL36150

150

25 kA

600

HLL36150

150

35 kA

HLL36150

150

50 kA

JJL36250

250

25 kA

JLL36250

250

35 kA

JLL36250

250

50 kA

 

9080LBC163106L

9080LBC263106L

9080LBC363106L

4–250 (25–126.7)

14–2 (2.5–35)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

4–2/0 (25–70)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

4–500 (25–240)

LJL36600

600

65 kA

LLL36600

600

65 kA

4–250 (25–126.7)

JJL36250

250

25 kA

600

4–500 (25–240)

LJL36600

600

25 kA

LJL36600

600

35 kA

4–250 (25–126.7)

JLL36250

250

50 kA

4–500 (25–240)

LLL36600

600

50 kA

 

9080LBC163206L

9080LBC263206L

9080LBC363206L

14–2/0 (2.5–70)

14–4 (2.5–25)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

14–4 (2.5–25)

14–10 (2.5–6)

JDL36175

175

18 kA

JGL36175

175

35 kA

JJL36175

175

65 kA

JLL36175

175

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

14–2/0 (2.5–70)

14–4 (2.5–25)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

14–2/0 (2.5–70)

14–4 (2.5–25)

HJL36150

150

25 kA

600

HLL36150

150

35 kA

HLL36150

150

50 kA

JJL36250

250

25 kA

JLL36250

250

35 kA

JLL36250

250

50 kA

 

9080LBA1652021L

9080LBA2652021L

9080LBA3652021L

4–350 (25–185)

4–350 (25–185)

LJL36600

600

65 kA

480

4–250 (25–126.7)

4–250 (25–126.7)

JDL36250

250

18 kA

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

4–250 (25–126.7)

4–250 (25–126.7)

JJL36250

250

25 kA

600

JLL36250

250

50 kA

4–350 (25–185)

4–350 (25–185)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBA165112L

9080LBA265112L

9080LBA365112L

4–250 (25–126.7)

14–2 (2.5–35)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

4–250 (25–126.7)

JJL36250

250

25 kA

600

JLL36250

250

50 kA

4–500 (25–240)

LJL36600

600

25 kA

LJL36600

600

50 kA

 

9080LBA165106L

9080LBA265106L

9080LBA365106L

4–250 (25–126.7)

14–2/0 (2.5–70)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

4–500 (25–240)

LJL36600

600

65 kA

LLL36600

600

65 kA

4–2/0 (25–70)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

4–250 (25–126.7)

JJL36250

250

25 kA

600

JLL36250

250

50 kA

4–500 (25–240)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBA165208L

9080LBA265208L

9080LBA365208L

6–250 (16–126.7)

14–2/0 (2.5–70)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

6–2/0 (16–70)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

6–500 (16–240)

LJL36600

600

65 kA

LLL36600

600

65 kA

6–250 (16–126.7)

JJL36250

250

25 kA

600

JLL36250

250

50 kA

6–500 (16–240)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBA164108L

9080LBA264108L

9080LBA364108L

2–250 (35–126.7)

14–2/0 (2.5–70)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

2–500 (35–240)

LJL36600

600

65 kA

LLL36600

600

65 kA

4–250 (25–126.7)

JLL36250

250

25 kA

600

JLL36250

250

50 kA

2–600 (35–300)

LJL36400

400

25 kA

LLL36400

400

50 kA

2–500 (35–240)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBA164101L

9080LBA364101L

2–250 (35–126.7)

2–250 (35–126.7)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

LJL36600

600

65 kA

2–500 (35–240)

2–500 (35–240)

LJL36600

600

65 kA

LLL36600

600

65 kA

2–250 (35–126.7)

2–250 (35–126.7)

JLL36250

250

25 kA

600

JLL36250

250

50 kA

2–500 (35–240)

2–500 (35–240)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBA362106L

14–2/0 (2.5–70)

14–4 (2.5–25)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

HJL36150

150

25 kA

600

HLL36150

150

35 kA

HLL36150

150

50 kA

JJL36250

250

25 kA

JLL36250

250

35 kA

JLL36250

250

50 kA

 

9080LBA163101L

9080LBA263101L

9080LBA363101L

6–250 (16–126.7)

6–250 (16–126.7)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

6–2/0 (16–70)

6–2/0 (16–70)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

6–350 (16–185)

6–350 (16–185)

LJL36600

600

65 kA

LLL36600

600

65 kA

6–250 (16–126.7)

6–250 (16–126.7)

JLL36250

250

25 kA

600

JLL36250

250

50 kA

6–350 (16–186)

6–350 (16–186)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBA165202L

9080LBA265202L

9080LBA365202L

6–250 (16–126.7)

6–250 (16–126.7)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

6–2/0 (16–70)

6–2/0 (16–70)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

6–350 (16–185)

6–350 (16–185)

LJL36600

600

65kA

LJL36600

600

65 kA

6–250 (16–126.7)

6–250 (16–126.7)

JJL36250

250

25 kA

600

JLL36250

250

50 kA

6–350 (16–185)

6–350 (16–185)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBA165212L

9080LBA265212L

9080LBA365212L

6–250 (16–126.7)

14–4 (2.5–25)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

6–500 (16–240)

LJL36600

600

65 kA

LJL36600

600

65 kA

6–250 (16–126.7)

JLL36250

250

25 kA

600

JLL36250

250

50 kA

6–500 (16–240)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBC165212L

9080LBC365212L

6–250 (16–126.7)

14–2 (2.5–35)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

6–500 (16–240)

LJL36600

600

65 kA

LJL36600

600

65 kA

6–250 (16–126.7)

JJL36250

250

25 kA

600

JLL36250

250

50 kA

6–500 (16–240)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBC165208L

9080LBC365208L

4–250 (25–126.7)

14–2/0 (2.5–70)

JDL36250

250

18 kA

480

JGL36250

250

35 kA

JJL36250

250

65 kA

JLL36250

250

65 kA

HDL36150

150

18 kA

HGL36150

150

35 kA

HJL36150

150

65 kA

HLL36150

150

65 kA

4–2/0 (25–70)

BDL36125

125

18 kA

BGL36125

125

35 kA

BJL36125

125

65 kA

4–500 (25–240)

LJL36600

600

65 kA

LLL36600

600

65 kA

4–250 (25–126.7)

JLL36250

250

25 kA

600

JLL36250

250

50 kA

4–500 (25–240)

LJL36600

600

25 kA

LLL36600

600

50 kA

 

9080LBA and 9080LBC Power Distribution Blocks Short-Circuit Current Ratings with Fuses

Catalog Numbers

Suitable Conductors kcmil/AWG (mm2)

Fuse Type / Amperage

SCCR

1-Pole

2-Pole

3-Pole

Line

Load

J

T

RK1

RK5

G

CC

9080LBA161101

9080LBA361101

6–2 (16–35)

6–2 (16–35)

200

200

200

100

60

30

100 kA

10–2 (6–35)

10–2 (6–35)

100

100

100

30

60

30

100 kA

10–2 (6–35)

10–2 (6–35)

125

125

60

30

60

30

65 kA

10–4 (6–25)
(class G,H,I,K)

10–4 (6–25)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2 (2.5–35)

14–2 (2.5–35)

10 kA

 

9080LBA161104

9080LBA261104

9080LBA361104

6–2 (16–35)

10 (6)

200

200

200

60

60

30

100 kA

10–2 (6–35)

14–10 (2.5–6)

150

150

100

30

60

30

100 kA

12–2 (4–35)

14–10 (2.5–6)

60

60

30

50

30

100 kA

10–4 (6–25)
(class G,H,I,K)

14–10 (2.5–6)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2 (2.5–35)

14–10 (2.5–6)

10 kA

 

9080LBA162101L

9080LBA262101L

9080LBA362101L

6–2/0 (16–70)

6–2/0 (16–70)

300

300

200

100

60

30

65 kA

6–1 (16–50)
(class G,H,I,K)

6–1 (16–50)
(class G,H,I,K)

300

300

200

100

60

30

65 kA

14–2/0 (2.5–70)

14–2/0 (2.5–70)

10 kA

 

9080LBA162104L

9080LBA262104L

9080LBA362104L

6–2/0 (16–70)

10–4 (6–25)

200

200

200

100

60

30

100 kA

6–2/0 (16–70)

14–4 (2.5–25)

150

150

100

30

60

30

100 kA

6–1 (16–50)
(class G,H,I,K)

12–6 (4–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0
(2.5–70)

14–4
(2.5–25)

10 kA

 

9080LBA362106L

6–2/0 (16–70)

10–4 (6–25)

200

200

200

100

60

30

100 kA

10–2/0 (6–70)

14–4 (2.5–25)

60

60

60

30

30

100 kA

6–1 (16–50)
(class G,H,I,K)

10–6 (6–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

10–1 (6–50)
(class G,H,I)

14–6 (2.5–16)
(class G,H,I)

60

60

60

30

30

100 kA

14–2/0 (2.5–70)

14–4 (2.5–25)

10 kA

 

9080LBA163101L

9080LBA263101L

9080LBA363101L

1/0–350 (50–185)

1/0–350 (50–185)

400

400

400

100

60

30

100 kA

6–350 (16–185)

6–350 (16–185)

300

300

200

100

60

30

100 kA

1/0–250
(50–126.7)
(class G,H,I,K)

1/0–250
(50–126.7)
(class G,H,I,K)

300

300

200

100

60

30

100 kA

6–350 (16–185)

6–350 (16–185)

10 kA

 

9080LBA163106L

9080LBA263106L

9080LBA363106L

3/0–400
(95–202.7)

8–2 (10–35)

500

500

400

200

60

30

100 kA

6–400 (16–202.7)

10–2 (6–35)

350

350

200

100

60

30

100 kA

1/0–250
(70–126.7)
(class G,H,I,K)

10–4 (6–25)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

6–400 (16–202.7)

14–2 (2.5–35)

10 kA

 

9080LBA163206L

9080LBA263206L

9080LBA363206L

2–2/0 (35–70)

8–4 (10–25)

400

400

400

100

60

30

100 kA

6–2/0 (16–70)

8–4 (10–25)

350

350

200

100

60

30

100 kA

6–2/0 (16–70)

10–4 (6–25)

250

250

200

60

60

30

100 kA

(1) 6 (16)

(2) 12 (4)

225

225

100

60

60

30

100 kA

6–1 (16–50)
(class G,H,I,K)

8–6 (10–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0
(2.5–70)

14–4
(2.5–25)

10 kA

 

9080LBA164101L

9080LBA364101L

2–600 (35–300)

2–600 (35–300)

600

600

50 kA

2–600 (35–300)

2–600 (35–300)

400

400

400

200

60

30

100 kA

2–350 (35–185)
(class G,H,I,K)

2–350 (35–185)
(class G,H,I,K)

400

400

400

200

60

30

100 kA

2–600
(35–300)

2–600
(35–300)

10 kA

 

9080LBA164108L

9080LBA264108L

9080LBA364108L

3/0–400
(95–202.7)

8–2 (10–35)

400

400

400

200

60

30

100 kA

6–400 (16–202.7)

10–2 (6–35)

200

200

200

100

60

30

100 kA

1/0–250
(50–126.7)
(class G,H,I,K)

14–4 (2.5–25)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

6–400 (16–202.7)

14–2 (2.5–35)

10 kA

 

9080LBA165202L

9080LBA265202L

9080LBA365202L

4–350 (25–185)

4–350 (25–185)

450

450

400

200

60

30

100 kA

4–350 (25–185)

4–350 (25–185)

600

600

50 kA

2–250 (35–126.7)
(class G,H,I,K)

2–250 (35–126.7)
(class G,H,I,K)

600

600

50 kA

2–250 (35–126.7)
(class G,H,I,K)

2–250 (35–126.7)
(class G,H,I,K)

450

450

400

200

60

30

100 kA

4–350 (25–185)

4–350 (25–185)

10 kA

9080LBA1652021L

9080LBA2652021L

9080LBA3652021L

4–500 (25–240)

4–500 (25–240)

500

500

400

200

60

30

100 kA

2–350 (35–185)
(class G,H,I,K)

2–350 (35–185)
(class G,H,I,K)

500

500

400

200

60

30

100 kA

4–500 (25–240)

4–500 (25–240)

10 kA

 

9080LBA165106L

9080LBA265106L

9080LBA365106L

3/0–500 (95–240)

6–2/0 (16–70)

400

400

400

100

60

30

100 kA

4–500 (25–240)

10–2/0 (6–70)

200

200

200

100

60

30

100 kA

2–350 (35–185)
(class G,H,I,K)

6–1 (16–50)
(class G,H,I,K)

400

400

400

100

60

30

100 kA

2–350 (35–185)
(class G,H,I,K)

10–1 (6–50)
(class G,H,I,K)

250

250

200

100

60

30

100 kA

4–500 (25–240)

14–2/0 (2.5–70)

10 kA

 

9080LBA165112L

9080LBA265112L

9080LBA365112L

3/0–500 (95–240)

6–2 (16–35)

400

400

400

200

60

30

100 kA

4–500 (25–240)

10–2 (6–35)

250

250

200

100

60

30

100 kA

2–350 (35–185)
(class G,H,I,K)

6–4 (16–25)
(class G,H,I,K)

400

400

400

200

60

30

100 kA

2–350 (35–185)
(class G,H,I,K)

10–4 (6–25)
(class G,H,I,K)

250

250

200

200

60

20

100 kA

4–500 (25–240)

14–2 (2.5–35)

10 kA

 

9080LBA165208L

9080LBA265208L

9080LBA365208L

250–500
(126.7–240)

4–2/0 (25–70)

600

600

400

200

60

30

100 kA

4–500 (25–240)

10–2/0 (6–70)

350

350

200

100

60

30

100 kA

250–350
(126.7–185)
(class G,H,I,K)

4–1 (25–50)
(class G,H,I,K)

600

600

400

200

60

30

100 kA

4–350 (25–185)
(class G,H,I,K)

10–6 (6–16)
(class G,H,I,K)

350

350

200

100

60

30

100 kA

4–500 (25–240)

14–2/0 (2.5–70)

10 kA

 

9080LBA165212L

9080LBA265212L

9080LBA365212L

250–500
(126.7–240)

8–4 (10–25)

400

400

200

100

60

30

100 kA

4–500 (25–240)

10–4 (6–25)

350

350

200

100

60

30

100 kA

250–350
(126.7–185)
(class G,H,I,K)

8–6 (10–16)
(class G,H,I,K)

400

400

200

100

60

30

100 kA

4–350 (25–185)
(class G,H,I,K)

10–6 (6–16)
(class G,H,I,K)

350

350

200

100

60

30

100 kA

4–500 (25–240)

14–4 (2.5–25)

10 kA

9080LBC162101L

9080LBC362101L

6–1/0 (16–50)

6–1/0 (16–50)

175

175

100

60

60

30

100 kA

6–1 (16–50)
(class G,H,I,K)

6–1 (16–50)
(class G,H,I,K)

175

175

100

60

60

30

100 kA

14–1/0 (2.5–50)

14–1/0 (2.5–50)

10 kA

 

9080LBC162104L

9080LBC262104L

9080LBC362104L

6–2/0 (16–70)

10–4 (6–25)

200

200

200

100

60

30

100 kA

10–2/0 (6–70)

14–4 (2.5–25)

150

150

100

30

60

30

100 kA

6–1 (16–50)
(class G,H,I,K)

12–6 (4–16)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0 (2.5–70)

14–4 (2.5–25)

10 kA

 

9080LBC163106L

9080LBC263106L

9080LBC363106L

3/0–500 (95–240)

8–2 (10–35)

400

400

400

200

60

30

100 kA

4–500 (25–240)

10–2 (6–35)

300

300

200

100

60

30

100 kA

1/0–250
(50–126.7)
(class G,H,I,K)

10–4 (6–25)
(class G,H,I,K)

150

150

100

30

60

30

100 kA

4–500 (25–240)

14–4 (2.5–25)

10 kA

 

9080LBC163206L

9080LBC263206L

9080LBC363206L

2–2/0
(35–70)

8–4
(10–25)

400

400

400

100

60

30

100 kA

6–2/0
(16–70)

8–4
(10–25)

350

350

200

100

60

30

100 kA

10–4 (6–25)
(class G,H,I,K)

14–10 (2.5–6)
class G,H,I,K)

150

150

100

30

60

30

100 kA

14–2/0
(2.5–70)

14–4
(2.5–25)

10 kA

 

9080LBC165208L

9080LBC365208L

250–500
(126.7–240)

4–2/0 (25–70)

500

500

400

200

60

30

100 kA

4–500 (25–240)

6–2/0 (16–70)

450

450

400

200

60

30

100 kA

250–350
(126.7–185)
(class G,H,I,K)

4–1 (25–50)
(class G,H,I,K)

500

500

400

200

60

30

100 kA

2–350 (35–185)
(class G,H,I,K)

6–1 (16–50)
(class G,H,I,K)

450

450

400

200

60

30

100 kA

4–500 (25–240)

14–2/0 (2.5–70)

10 kA

9080LBC165212L

9080LBC365212L

4–500 (25–240)

10–2 (6–35)

400

400

400

200

60

30

100 kA

250–500
(126.7–240)

8–2 (10–35)

600

600

50 kA

2–350 (35–185)
(class G,H,I,K)

10–4 (6–25)
(class G,H,I,K)

400

400

400

200

60

30

100 kA

250–350
(126.7–185)
(class G,H,I,K)

8–4 (10–25)
(class G,H,I,K)

600

600

50 kA

4–500 (25–240)

14–2 (2.5–35)

10 kA

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?